Owner's Manual
CAUTION
1. Before starting, read instructions carefully.
2. Verify all connections are in accordance to the drawings.
3. Check device cover is properly installed and all ventilation holes are
clear and uncovered.
4. High voltages are present in this device. Do not make any inspections
unless the supply has been disconnected by the main switch. Before
opening the device cover wait at least 5 minutes after display lamps turn
off.
5. The filter unit includes capasitors. Measure the filter unit voltage from
phase to ground before making any inspections or connections.
6. Insulation resistance test with megger requires special precautions.
7. Do not make any measurements inside the device when it is connected
to the main supply.
8. Do not touch the components on the circuit boards. Static voltage
discharge may cause damage or destroy the IC-circuits.
9. It is forbidden to use radiophones and portable phones near this device
with the doors open.
10. All the doors and covers must be closed during crane in operation.
CONTENTS
F Supply voltage
F 380 - 500VAC, 50/60Hz
K 525 - 690VAC, 50/60Hz
12 Revision code
The latest DynAReg may be of
different revision.
C Filter type
C LCL-filter
0 Special-filter
DynAReg V 400 F 12 - C - L - 0 - 0 - 0
Display type
L LED-display L
Expansion
0 None 0
Reserved
0 None 0
Special
0 None 0
The line current distortion of six pulse diode rectifier is seldom below 40%. Distortion levels
exceeding 100% are not unusual. By using the DynAReg and a well dimensioned LCL-line filter unit
the THD (Total Harmonic Distortion) can be typically decreased by a factor of 10.
The active input bridge offers the DynAReg possibility to raise the output voltage in relation to supply
voltage. With a 400V supply voltage for example, it is possible to create 500V output voltage to the
motor. Typically DC-bus voltage level is adjusted 10...25 % above that achieved with a diode rectifier.
Thanks to the closed loop DC voltage controller, the DynAReg is, within its current limits,
unsusceptiple for variations in the power supply line. This makes DynAReg extremely suitable for
locations with a weak power supply line.
As the DynAReg belongs to the DynA family with DynAC Vector and DynAHoist Vector, a great
number of common components minimize the spare part inventory and simplify the maintenance
procedures.
2 PROGRAMMING OF DYNAREG
DynAReg has the digital control panel including a keyboard and a display. Control panel is removable
and has full galvanic isolation from mains potential.
DISPLAY
MON PAR REF BTNS
Displays parameter values, monitoring data,
etc., six digits
PG
Status page
RUN READY FAULT
Monitoring page PG
RUN READY FAULT
Reference
value page PG
RUN READY FAULT
PG
Fault page
RUN READY FAULT
PG
2.1.3 STATUS-page
Display shows the state of the regenerative unit:
"run" - DynAReg is running
"ready" - locked to the network and waiting the run-command (DIA1)
"stop" - stopped from the panel
"shutd" - shutdown state tripped to a fault
"off" - off-state (charging)
"broken" - inverter is broken
"unloc" - unable to lock to the mains:
pressing the TAB-button changes the display mode to show the internal locking
status word: OVFCBA
A - L1- phase missing
B - L2- phase missing
C - L3- phase missing
F - line frequency out of range (active also if one phase missing)
V - DC voltage level out of range
O - other fault which is either heat sink temperature out of range or motoring
overcurrent through diodes
2.1.4 MONITOR-page
Currently, the following internal signals can be monitored:
n0: - active current in % of the nominal current of the equipment
n1: - reactive current (including the reactive current of the filter)
n2: - peak current (%)
n3: - operating frequency (Hz)
n4: - actual DC-Voltage level (%)
n5: - heatsink temperature (°C)
n6: - line voltage level (%)
n7: - converter voltage level (%)
n8: - active current limit level (%)
n9: - unbalance current (%)
n10: - sum of phase currents (%)
n11: - negative sequence current (phase unbalance %)
n12: - software version.revision
monitor signal can be selected directly with UP/DOWN button
2.1.5 REFERENCE-page
The following reference signals can be monitored:
r0: - DC-Voltage reference level
r1: - internal reactive current reference (the capacitor current reference)
r2: - switching frequency (kHz)
2.1.6 FAULT-page
Fault page can be used to display 10 last faults. The active fault is F0. The fault history can be
scrolled with UP/DOWN buttons. The fault history will be cleared after power down.
FAULT CODES:
Hardware trips:
1: Over Current
2: Over Voltage
3: Earth fault
4: Inverter fault
5: Charge switch open
10: Line Fault (not stored into history)
13: Undertemperature
14: Overtemperature/Cooling fan does not have control voltage
25: Watchdog Fault
Software trips:
101: Over Current (motoring current through antiparallel diodes)
102: Over Voltage
103: Earth fault
110: Phase disbalance
141: External fault
92: Undervoltage stop
0= 0V (Not connected)
1= +24 V (Inverter board terminal 12)
F-series K-series
0=400 V 0=575 V
1=500 V 1=690 V
The DC voltage must be programmed at least 10% higher compared to the nominal DC voltage oft
the 6-pulse diode bridge.
3 START-UP PROCEDURE
If any problems or malfunctions occur during the start-up, refer to Chapter 5 “Troubleshooting”, to
find out the reason. All problems must be solved before continuing. For further information contact
Warning! High voltages inside DynAReg. Wait for at least five minutes after the supply
voltage has been switched off before service actions. Display in operating
condition (lights on) indicates a dangerous voltage on the DC-bus. When display
turns off, the DC-bus voltage is about 100V. Note also that there is a dangerous
voltage in the DC-bus always when the DC-bus is charged.
Do not connect any voltage to the DC-bus terminals of DynAReg (DC+. DC-). Otherwise, the inverter
will be damaged.
Note! Connect power (U, V, W) to the terminals of the filter unit, and DC-bus cables to the
DynAReg terminals DC+, DC-.
The overload protection of DynAReg protects the supply cables. The fuses of the supply provide
short circuit protection. Fuses in DC-bus provide DC-bus overload and short circuit protection.
Note! Before making any isolation resistance measurements disconnect the DynAReg (U,
V, W) cables.
R U2 U1 U2 U1 U
Supply L-filter LC-filter DynAReg
S V2 V1 V2 V1 V
UER UER
T W2 xxx/xxx.01 W1 W2 xxx/xxx.02 W1 W
- Check the cabling from the filter unit and DC-bus to DynAReg.
- Check that external connections and the programming of the digital inputs are according to
application.
- Check that filtering capacitors and discharging resistors are connected according to Appendix 2.
4 SERVICE
DynAReg does not require regular maintenance. The following actions are recommended:
2. Check that there are no abnormal noises coming from the cooling fans
5 TROUBLESHOOTING
Warning! High voltages inside DynAReg. Wait for at least five minutes after the supply
voltage has been switched off before service actions. Display in operating
condition (lights on) indicates a dangerous voltage on the DC-bus. When display
turns off, the DC-bus voltage is about 100V. Note also that there is a dangerous
voltage in the DC-bus always when the DC-bus is charged.
This chapter describes how to detect DynAReg failures. The purpose is to find out which components
are damaged and how to replace them to restore proper operation. Advice is also given to find
possible external failures that affect DynAReg function.
Supply
Supply voltage F-series 380-500VAC, K-series 525-690VAC
Allowable supply voltage +/- 10%
fluctuation
Nominal supply frequency 50/60Hz +/- 5%
Control features
Control method Voltage oriented vector control
Filter LCL type or special line filter
Protections
Overload protection Fault is detected if the current momentarily exceeds 280% of rated
current
Undervoltage / blown fuse Fault is detected if AC voltage drops below 65% of nominal supply
voltage
Overvoltage protection Fault is detected if DC voltage exceeds 911V (F-), 1258V (K-series)
Momentary power loss Immediate fault stop
Inverter overtemperature Temperature sensor on the heat sink
Control voltage transformer Primary: circuit breaker, secondary: fuse
Ground fault Provided by electronic circuitry
Ambient conditions
Ambient temperature -10°C ... +55°C (+14°F ... +131°F) ED£60%
Storage temperature -40°C ... +60°C (-31°F ... +140°F) dry
Humidity <95%RH (no condensation)
Altitude Maximum 1000m at In. Above 1000m: In reduces 1% per each 100m.
Above 3000m: consult factory.
Vibration Operation: maximum displacement amplitude 3mm at 2-9Hz.
Maximum acceleration amplitude 0.5G (5m/s²) at 9-200Hz
SUPPLY
R S T
O-K1 WIRING:
A 6mm 2
A O-K1
R01
Discharging R02
resistors R03
C01
Filtering
capacitors C02
C03
Filter unit FU1
L4 L5 L6
C1
C3
C2
L1 L2 L3
K1
U V W
DC-BUS
-
SUPPLY
R S T
O-K1 WIRING:
A 6mm 2
A O-K1
R01
Discharging R02
resistors R03
C01
Filtering
capacitors C02
C03
C1 C11
C3 C13
C2 C12
K1 K11
U V W U V W
DC-BUS DC-BUS
-
12500F
0550F
0750F
0900F
1100F
1320F
1600F
2000F
2500F
3150F
4000F
5000F
6300F
8000F
Order code /
Material number Description Type Technical data
DISPLAY PANEL
450130 7-segment LED panel DAV-1L 1 1 1 1 1 1 1 1 1 1 1 1 1 1
BOARDS
DAV-B062-Fxxxx Control Board (4M) xxxx = power class 1 1 1 1 1 1 1 1 1 1 1 1 1 1
DAV-B119-F Auxiliary Control Board 1 1 1 2 2 3 3
DAV-B103-F Master Auxiliary Control Board 2 3 3 3
DAV-B119-F Slave Auxiliary Control Board 2 3 3 6
DAV-B104-F Master Repeater 1 1 1 2
DAV-B105-F Slave Repeater 1 1 1 2
DAV-B002-FxxxxS Power Board xxxx = power class 1 1 1
DAV-B020-FxxxxS Power Board 2 2 2 3 3 3
DAV-B055-FxxxxS Power Board 4 4 4 4 4
DAV-B110-FxxxxS Slave Power Board 4 4 8
DAV-B112-FxxxxS Slave Power Board 3
DAV-B080-F VRD Board 4 4 8 8 12
DAV-B008-Fxxxx Adapter Board xxxx = power class 1 1 1 2 2 2 3 3 4 4 6 8 8 12
DAV-B018-F Branching Board 1 1 1 1 1 1 1 2 2 2 3
COOLING FANS
DAV-E104-G Fan D2E133-AM47 220VAC 1 1 1 2
DAV-E110-G Fan D2E133-DM47 230VAC 1 1
DAV-E109-G Fan D2E146-CD51-09 220VAC 3 3 4 4 6 8 8 12
IGBT MODULES
DAV-S407-G IGBT SKM200GB123D 2*200A/1200V 6
DAV-S408-G IGBT SKM300GB123D 2*300A/1200V 3 3 6 9 12 24
DAV-S409-G IGBT SKM400GB123D 2*400A/1200V 3 6 9 12 18 24 36
BUSBARS
DAV-M606-F Busbars for DAV0550F-0900F 1 1 1
DAV-M608-F Busbars for DAV1100F-1600F 1 1 1
DAV-M610-F Busbars for DAV2000F-2500F 1 1 2
DAV-M612-F Busbars for DAV3150F-4000F 1 1 2 2 3
CURRENT SENSORS
DAV-E822-G Current Sensor LEM 305-S 300A 3 3 6 6 9 12 24
DAV-E823-G Current Sensor LEM 305-S/SP1 300A 3 6 9 12 18 24 36
CHEMICALS
DAV-M901-G Thermal compound Paste 12 150g tube X X X X X X X X X X X X X X
K-series
0550K
0750K
0900K
1100K
1320K
1600K
2000K
2500K
3150K
4000K
5000K
6300K
Order code /
Material number Description Type Technical data
DISPLAY PANEL
450130 7-segment LED panel DAV-1L 1 1 1 1 1 1 1 1 1 1 1 1
BOARDS
DAV-B062-Kxxxx Control Board (4M) xxxx = power class 1 1 1 1 1 1 1 1 1 1 1 1
DAV-B119-K Auxiliary Control Board 1 1 1 2 2 3 3
DAV-B103-K Master Auxiliary Control Board 2 3 3
DAV-B119-K Slave Auxiliary Control Board 2 3 3
DAV-B104-K Master Repeater 1 1 1
DAV-B105-K Slave Repeater 1 1 1
DAV-B010-KxxxxS Power Board xxxx = power class 1 1
DAV-B042-KxxxxS Power Board 2 2 2 3 3 4 4 3 4 4
DAV-B111-KxxxxS Slave Power Board 3 4 4
DAV-B080-K VRD Board 2 2 2 3 3 4 4 6 8 8
DAV-B007-Kxxxx Adapter Board xxxx = power class 1 1
DAV-B008-Kxxxx Adapter Board 2 2 2 3 3 4 4 6 8 8
DAV-B018-F Branching Board 1 1 1 1 1 1 1 2 2 2
COOLING FANS
DAV-E102-G Fan MC24B3 120mm, 24VDC 1
DAV-E103-G Fan Major JG 24 B3 150mm, 24VDC 1
DAV-E110-G Fan D2E133-DM47 230VAC 1 1
DAV-E104-G Fan D2E133-AM47 220VAC 2
DAV-E109-G Fan D2E146-CD51-09 220VAC 3 3 4 4 6 8 8
IGBT MODULES
DAV-S412-G IGBT SKM150GB173D 2*150A/1700V 6 6 9
DAV-S413-G IGBT SKM200GB173D 2*200A/1700V 3 3 6 9 12 12 18 24 24
BUSBARS
DAV-M614-K Busbars for DAV0300K-0750K 1 1
DAV-M615-K Busbars for DAV0900K-1320K 1 1 1
DAV-M616-K Busbars for DAV1600K-2000K 1 1 2
DAV-M617-K Busbars for DAV2500K-3150K 1 1 2 2
CURRENT SENSORS
DAV-E821-G Current Sensor LEM 205-S 200A 3 3
DAV-E822-G Current Sensor LEM 305-S 300A 6 6 6 9 9 12 12 18 24 24
CHEMICALS
DAV-M901-G Thermal compound Paste 12 150g tube X X X X X X X X X X X X
1250 F
110 F
132 F
160 F
200 F
250 F
315 F
400 F
500 F
630 F
800 F
55 F
75 F
90 F
Item Device Mat.no Type
A1 Inverter DAV xxxx RFL1N001 1 1 1
DAV xxxx RFL0N001 1 1 1 1 1 1 1 1 1 1 1
"xxxx" defines inverter power class
0550 equals 55F
8000 equals 800F
K-series
110 K
132 K
160 K
200 K
250 K
315 K
400 K
500 K
630 K
55 K
75 K
90 K
Item Device Mat.no Type
A1 Inverter DAV xxxx RKL1N00x 1 1
DAV xxxx RKL0N00x 1 1 1 1 1 1 1 1 1 1
"xxxx" defines inverter power class
0550 equals 55K
6300 equals 630K
Dimensions WxHxD T1
940x1187x315 mm
Weight (approx.)
55F 100 kg
75F 102 kg
90F 102 kg A1
K1 R1
K2 K01
X1
DynAReg V 110-160 F
T1
Dimensions WxHxD
910x1435x385 mm
Weight (approx.)
R1
110F 171kg
A1
132F 179kg
160F 181kg
F7 F01
K1
X1
F-series
DynAReg V 200-250 F
Dimensions WxHxD
910x1435x422 mm
Weight (approx.) T2
200F 220kg
250F 230kg
T1
K2
X1
R1
K1
DynAReg V 315-400 F
Dimensions WxHxD
1270x1540x425 mm
Weight (approx.)
315F 290kg T2
400F 300kg
T1
Requires external filter unit
F7 F01
A1
K2 K01
X1
K1
R1
F-series
DynAReg V 500 F
Dimensions WxHxD
2x910x1435x422 mm
Weight (approx.)
500F 2x230kg T2 T12
F7
A1 A11
K01
K2
X1
F17
R1
K1 K11
DynAReg V 630-800 F
T2
T1
T12
F7 F01
A1 A11
T11
K2 K01
F17
X1
K1 K11
R1
F-series
DynAReg V 1250 F
T2
T1
F2 F7 F01
A11 A1 A12
K2 K01
X1
K11 R1 R1 R1 K1 K12
K-series
DynAReg V 55-75 K
F7 F01 T1
Dimensions WxHxD
940x786x290 mm R1
K2 K01
A1
Weight (approx.)
55K 52kg
75K 52kg K1
DynAReg V 90-132 K
T1 T2
Dimensions WxHxD
910x1435x385 mm
Weight (approx.)
R1
90K 171kg
110K 179kg A1
132K 181kg
F7 F01
K1
X1
K-series
DynAReg V 160-200 K
T1
Dimensions WxHxD
910x1435x422 mm
T2
Weight (approx.)
T3
160K 220kg
200K 230kg
K2
X1
R1
K1
DynAReg V 250-315 K
T1
Dimensions WxHxD
1270x1540x425 mm T2
Weight (approx.) T3
250K 290kg
315K 300kg
F7 F01
A1
K2 K01
X1
K1
R1
K-series
DynAReg V 400 K
Dimensions WxHxD
T1
2x910x1435x422 mm
T2
Weight (approx.)
400K 2x230kg T3
T12
F7
A1 A11
K01
K2
X1
F17
R1
K1 K11
DynAReg V 500-630 K
T1
T2
T3
T12
T11
F7 F01
A1 A11
K2 K01
F17
X1
K1 K11
R1
L11
L12
L13
480 ON48 X1:15
X1:20
460 X1:21
440 2.5-4A X1:22
1 3 5
415 230V OL230 X1:23
C K01:1 X1:24
I> I> I> STOP
F7 K01:67
4 6
400
2
380
1 3
F01 ES
ON48
OL230
2 4
67 1 3 X1 :16
K01 K2
SET
ES
68 2 4
1.0 S 5
K2 S1
6
X1 :17
S1
R1 R3 1 3 5
E K01 K1
R2 R4 2 4 6
A
83
HU4.07.0063 En
K2
84
230 0 U V W
26 21
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- A1 INVERTER BOARD
OL230 53
63 73 153 163 1
K01 K2
K2 K2 K01 K01 54
64 74 154 164 2
X1:12 SET X1:18 X1:19
A X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 1.0 S
A2 A2 A2
K1 K01 K2
A1 A1 A1
ON48
DYNAREG V 55-90 F
X1:1 :2 :3 T1 OL48
L1 L2 L3 PE
500 48V 2-3.15A X1 :14
D
L11
L12
L13
480 ON48 X1:15
X1:20
460 X1:21
440 2.5-4A X1:22
1 3 5
415 230V OL230 X1:23
C K01:1 X1:24
I> I> I> STOP
F7 K01:67
4 6
400
2
380
1 3
F01 ES
ON48
OL230
2 4
67 1 3 X1 :16
K01 K2
SET
ES
68 2 4
1.0 S 5
K2 S1
6
X1 :17
S1
R1 R3 1 3 5
E K01 K1
R2 R4 2 4 6
A
83
HU4.07.0063 En
K2
84
U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
230 0
26 21
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- A1 :25 :22
A1 INVERTER BOARD
OL230 53
63 73 153 163 1
K01 K2
K2 K2 K01 K01 54
64 74 154 164 2
X1:12 SET X1:18 X1:19
A X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 1.0 S
A2 A2 A2
K1 K01 K2
A1 A1 A1
ON48
DYNAREG V 110-160 F
X1:1 :2 :3 T1 OL48
L1 L2 L3 PE
500 48V 2-3.15A X1 :14
D
L11
L12
L13
480 ON48 X1:15
X1:20
460 X1:21
440 2.5-4A X1:22
1 3 5
415 230V OL230 X1:23
C K01:1 X1:24
I> I> I> STOP
F7 K01:67
E
4 6
400
2
380
1 3
F01 ES
ON48
OL230
2 4
T2
67 1 3 500 48V 2-3.15A X1 :16
K01 K2 480
SET
ES
68 2 4
1.0 S 460 5
440 2.5-4A K2 S1
E 6
415 230V
K01:67 X1 :17
S1
R1 R3 2 4 6 400
E K01 K1 380
R2 R4 1 3 5
A
83
HU4.07.0063 En
K2
84
U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
230 0
26 21
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- A1 :25 :22
A1 INVERTER BOARD
OL230 53
63 73 153 163 1
K01 K2
K2 K2 K01 K01 54
64 74 154 164 2
X1:12 SET X1:18 X1:19
A X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 1.0 S
A2 A2 A2
K1 K01 K2
A1 A1 A1
ON48
DYNAREG V 200-400 F
PE L1 L2 L3 T11 X1:1 :2 :3 L1 L2 L3 PE T1 OL48
E 500 500 X1 :14
48V 2-3.15A 48V 2-3.15A
480 ON48
L11
L12
L13
ON48 D 480 X1:15
X1:20 X1:20
460 460 X1:21
2.5-4A 440 440
1 3 5 1 3 5 2.5-4A X1:22
OL230 230 415 230 OL230 X1:23
C 415
K01:3 K01:1 X1:24
I> I> I> I> I> I>
F17 F7 STOP
400 E
2 4 6 2 4 6 400
380 1 3 380
33
F01 33
F7
34 F17
34 ES
2 4
ON48
OL230
1 3
T12 T2
48V 2-3.15A 500 K2 500
2 4 48V 2-3.15A X1 :16
480 67 480 ES
460 K01 5
SET 460
440 68
2.5-4A 1.0 S 440 2.5-4A E K2 S1
6
230 415 415 230
K01:67 K01:67 X1 :17
2 4 6 2 4 6 S1
E
K11 400 R1 R3 K1 400
1 3 5 380 K01 1 3 5 380
R2 R4 55
53
K1 K01
D
E
R1
R1
A A
83
HU4.07.0063 En
E K2
84
U V W 230 0 230 0 U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
12
X11 X2
10 26 21
H1-H10 H1-H10
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
18 IOUT
11 CDIA
17 CDIB
A11 A1 25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- L+ L- A1 INVERTER BOARD
A1 :25 :22
B
OL230 K01:1 K01:3 OL230 53
3 1
K01 K01 K2
4 2 54
X1:13 63 73 153 163 X1:12 SET X1:18 X1:19
A A
1.0 S
K2 K2 K01 K01
A2 64 74 154 164 A2 A2 A2
K11 K1 K01 K2
X1 :4 :5 :6 :7 X1 :8 :9 :10 :11
A1 A1 A1 A1
ON48 ON48
DYNAREG V 500-800 F
E
L1 L2 L3 PE L1 L2 L3 PE L1 L2 L3 PE X1:1 :2 :3 500 T1 OL48
480 48V 2-3.15A X1 :14
ON48
L11
L12
L13
D X1:15
460 X1:20
440 X1:21 STOP
1 3 5 X1:22
415
X1:23
C ES
X1:24
I> I> I>
F7 400
2 4 6 380
1 3 X1 :16
F01 ES
E 5
K2 S1
2 4
6
C E X1 :17
D S1
ON48
OL230
1 3
T2
500
K2
2 4 230V D 55
53
1 K1 K01
F2 54 SET 56
2 4 6 2 4 6 67 2 4 6 C 2 1.0 S
K12 K11 K01 K1 D 53
1 3 5 1 3 5 SET 68 1 3 5 OL230
1.0 S K01:67 K11
D
54
A A A
R1 R3 1 53
K01 K01
2 E K12
R2 R4
E 54
63 73 153 163
A2 A2 A2
D K2 K2 K01 K01 K1 K11 K12
Page 34
C 64 74 154 164
A1 A1 A1
X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 ON48
R1
10
12
83
HU4.07.0063 En
10 K2
12 84
X12 H1- U V W X11 H1- U V W X2 H1- U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
H10 H10 H10 26 21
7 0V
0 0 0
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
A12 L+ L- A11 L+ L- A1 L+ L- A1 :25 :22
A1 INVERTER BOARD
53
K2
54
B B SET X1:18 X1:19
A A A
1.0 S
A2 A2
K01 K2
A1 A1
ON48
DYNAREG V 1250 F
X1:1 :2 :3 OL48 K01:1
L1 L2 L3 PE T1
690 X1 :14
D 48V 2.5-4A
L11
L12
L13
660 ON48 X1:15
600 X1:20
575 X1:21
1 3 5 X1:22
525 X1:23
C X1:24
F7 STOP
2 4 6
1 3
F01 ES
2 4
1 3 X1 :16
K2 ES
2 4
5
K2 S1
6
X1 :17
S1
R1 R3 1 3 5
K01 K1
R2 R4 2 4 6
A
83
HU4.07.0063 En
K2
84
U V W
26 21
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
18 IOUT
11 CDIA
17 CDIB
25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- A1 INVERTER BOARD
OL48 53
63 73 153 163 1
K01 K2
K2 K2 K01 K01 54
64 74 154 164 2
X1:12 SET X1:18 X1:19
A X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 1.0 S
A2 A2 A2
K1 K01 K2
A1 A1 A1
ON48
DYNAREG V 55-75 K
X1:1 :2 :3 T1 OL48
L1 L2 L3 PE 690 X1 :14
D 48V 2.5-4A
L11
L12
L13
660 ON48 X1:15
600 X1:20
575 X1:21
1 3 5 X1:22
525 X1:23
C X1:24
F7 STOP
2 4 6
1 3
F01 T2 ES
690 K01:1
ON48
230V 2-3.15A
OL230
660 K01:67
2 4
600
575
67 525
1 3 X1 :16
K01 K2
SET
ES
68 2 4
1.0 S 5
K2 S1
6
X1 :17
S1
R1 R3 1 3 5
E K01 K1
R2 R4 2 4 6
A
83
HU4.07.0063 En
K2
84
U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
230 0
26 21
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- A1 :25 :22
A1 INVERTER BOARD
OL230 53
63 73 153 163 1
K01 K2
K2 K2 K01 K01 54
64 74 154 164 2
X1:12 SET X1:18 X1:19
A X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 1.0 S
A2 A2 A2
K1 K01 K2
A1 A1 A1
ON48
DYNAREG V 90-132 K
X1:1 :2 :3 T1 OL48
L1 L2 L3 PE 690 X1 :14
D 48V 2.5-4A
L11
L12
L13
660 ON48 X1:15
600 X1:20
575 X1:21
1 3 5 X1:22
525 X1:23
C X1:24
F7 STOP
2 4 6
1 3
F01 T2 ES
690 K01:1
ON48
230V 2-3.15A
OL230
660 K01:67
E
2 4
600
575
67 525
1 3 X1 :16
K01 K2
SET
ES
68 2 4
1.0 S 5
K2 S1
6
E
X1 :17
T3
690 K01:67 S1
R1 R3 2 4 6 230V 2-3.15A
660
E K01 K1
R2 R4 1 3 5 600
575
R1
Page 37
A
83
HU4.07.0063 En
K2
84
U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
230 0
26 21
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- A1 :25 :22
A1 INVERTER BOARD
OL230 53
63 73 153 163 1
K01 K2
K2 K2 K01 K01 54
64 74 154 164 2
X1:12 SET X1:18 X1:19
A X1 :4 :5 :6 :7 X1 :8 :9 :10 :11 1.0 S
A2 A2 A2
K1 K01 K2
A1 A1 A1
ON48
DYNAREG V 160-315 K
PE L1 L2 L3 X1:1 :2 :3 L1 L2 L3 PE OL48
T1
E 690 X1 :14
660 48V 2.5-4A
L11
L12
L13
K01:3 T11 D ON48 X1:15
690 X1:20
230V 2-3.15A 600
660 X1:21
X1:20 575
600 1 3 5 1 3 5 X1:22
575 525 X1:23
C
X1:24
525 F17 F7 STOP
2 4 6 2 4 6
1 3
33
F01 33
F7
34 F17
34 T2 ES
690 K01:1
E 2 4 230V 2-3.15A
660 E
T12
ON48
OL230
690 600
K01:67 230V 2-3.15A 660 575
1 3
600 525
575 K2 X1 :16
67 2 4 ES
525 K01 5
SET 68
1.0 S K2 S1
E 6
T3 X1 :17
2 4 6 2 4 6 690 K01:67 S1
660 230V 2-3.15A
K11 R1 R3 K1
1 3 5 K01 1 3 5
R2 R4 600 55
53
575
K01
D
E
R1
R1
A A
83
HU4.07.0063 En
E K2
84
U V W 230 0 230 0 U V W A1 :26 :21 :7 :8 :9 :10 :11 :12 :14 :15 :16 :17 :18 :20
12
X11 X2
10 26 21
H1-H10 H1-H10
7 0V
12 +24
20 DO1
8 DIA1
9 DIA2
10 DIA3
14 DIB4
15 DIB5
16 DIB6
11 CDIA
18 IOUT
17 CDIB
A11 A1 25 22 X10
Konecranes Components Corporation reserves the right to alter or amend the above information without notice
L+ L- L+ L- A1 INVERTER BOARD
A1 :25 :22
OL230 K01:1 B
K01:3 OL230 53
3 1
K01 K01 K2
4 2 54
X1:13 63 73 153 163 X1:12 SET X1:18 X1:19
A A
1.0 S
K2 K2 K01 K01
A2 64 74 154 164 A2 A2 A2
K11 K1 K01 K2
X1 :4 :5 :6 :7 X1 :8 :9 :10 :11
A1 A1 A1 A1
ON48 ON48
DYNAREG V 400-630 K
HU4.07.0063 En Owner's Manual
Page 39
DC-bus cabling
DC-voltage selection
Protective devices
Filter Type:
Filter connections
and cabling
L1 U2 U1 U2 U1 U
Supply L-filter LC-filter DynAReg
L2 V2 V1 V2 V1 V
UER UER
L3 W2 xxx/xxx.01 W1 W2 xxx/xxx.02 W1 W
Filtering capacitors
connections and cabling
Remarks
Date Checked by