Manual
13 14 15 16
P1 P2 P3 P4
-SUP +SUP ZERO-C ZERO-F SPAN-C SPAN-F
SGM 424
STRAIN GAUGE TO 4-20mA CONVERTER
LOADCELL 4-20mA
+E +S -E -S +IN -IN Sh CAL Sh -I +I
1 2 3 4 5 6 7 8 9 10 11 12
S424-MAN
INDUSTRIAL INSTRUMENTATION
SGM424
ADJUSTMENT OF THE STRAIN GAUGE CONVERTER
Power supply TYPE SGM420-2.
24Vdc
1. First mount the loadcell(s) mechanical
(-20% to +30%)
without any friction under the weigher. The
GND + loadcell cable has to be connected to the
12-pole connector:
+ loadcell supply (+excitation) at clamp-1 +E.
- loadcell supply (-excitation) at clamp-3 -E.
+ sense at clamp-2 +S.
+ sense at clamp-4 -S.
+ signal (input) at clamp-5 +IN.
13 14 15 16
- signal (input) at clamp-6 -IN.
Screen of the cable (shield) at clamp Sh.
13 14 15 16
P1 P2 P3 P4
2. Connect the power supply 24Vdc (-20% to
ZERO-C ZERO-F SPAN-C SPAN-F
+30%) to the 4-pole connector.
-SUP +SUP
19,2-31,2V ZERO/SPAN ADJUST
SGM 424
STRAIN GAUGE TO 4-20mA CONVERTER
LOADCELL 4-20mA
+E +S -E -S +IN -IN Sh CAL Sh -I +I
1 2 3 4 5 6 7 8 9 10 11 12
LOWPASS FILTER
DIP3 & 4 = OFF = 2,5Hz (default)
1 2 3 4 5 6 7 8 9 10 11 12
DIP3 & 4 = ON = 25Hz
Default is all dipswitches off
- Signal
+ Excitation - Sense Z-COARSE Z-FINE S-COARSE S-FINE
+ Sense - Excitation
+Signal
BB
13 14 15 16
5. With an unloaded weigher the current must be adjusted to
P1 P2 P3 P4 4mA. First use potentiometer-1 for COARSE and then
ZERO-C ZERO-F SPAN-C SPAN-F
potentiometer-2 for the FINE-adjusting.
-SUP +SUP
19,2-31,2V ZERO/SPAN ADJUST
6. Place the maximum load at the weigher. Adjust the mA-
SGM 424 signal to 20mA with potentiometer-3 for COARSE and then
STRAIN GAUGE TO 4-20mA CONVERTER potentiometer-4 for FINE-adjusting.
LOADCELL 4-20mA It’s also possible to load the weigher with a smaller load ( at
+E +S -E -S +IN -IN Sh CAL Sh -I +I least 10%). Because the load cell signal is linear to the load,
the output signal must also adjusted to 10% => 5.6mA.
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 12
- +
R-Load
750 Ohm max
I-Load 4-20mA
BB
SGM 424
STRAIN GAUGE TO 4-20mA CONVERTER
LOADCELL 4-20mA
+E +S -E -S +IN -IN Sh CAL Sh -I +I
1 2 3 4 5 6 7 8 9 10 11 12
Specifications: