0.6/1.0 KV Copper Xlpe Power Cable (Unarmoured) : CU/X-HF-110/HFS-110-TP

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 3

0.6/1.

0 kV COPPER XLPE POWER CABLE (UNARMOURED)


CU/X-HF-110/HFS-110-TP

Compliant with GEN. TO AS/NZS 5000.1:2005

BEFORE YOU START

1. The current ratings indicated in this Specification Sheet have been based on the calculation procedures as
recommended in IEC 60287and the following assumptions. Rating factors should be
a. Max continuous conductor temp = 90 °C
b. Ambient air temperature = 40°C
c. Ambient ground temperature =25°C
d. Depth of laying =0.5m
e. Thermal resistivity of soil =1.2 K.m/W
2. The particulars given above are nominal & are subject to normal manufacturing tolerances.
3. Sequential length marking shall be provided at every one meter on outer sheath by hot foil indenting/Printing.
4. All the drums shall be packed by PP sheet over the outermost cable layer.

PARAMETER SPECIFICATION
Annealed Plain Copper - Stranded Circular Class-2
Conductor Material & Shape (Phase and Earth)
(As Per AS/NZS 1125)
CONSTRUCTION

Insulation Material (Phase and Earth) X-HF-110


Separator Tape N/A
Core Identification By Red , Black & Green/Yellow Coloured Insulation
Insulated Cores Laid-Up With Suitable Non-Hygroscopic
Laid-Up
Filler If Applicable
Inner Sheath -
Black, HFS-110-TP , UV Protect
Outer sheath
(As Per AS/NZS 3808)

Australasian Cables (A Division of EESA Pty Ltd) 604/89, High Street, Kew 3101 Ph: 0437720513, 0420 598 900
www.eesa.net.au / sales@eesa.net.au
Std. Packing Length As Per Schedule
Type of Drum Wooden Drum
Non - Standard Length Not Less Than 100 Mtrs. Up To 5%
Non - Standard Length
PACKING

Of Order Qty.
Overall Quantity Tolerance + 0%/- 1%
Non Standard Length N/A
AUSTRALASIAN "APAR FIRE-PROTEKT" INDIA 0.6/1
Embossing/Printing kV X-HF-110 ELECTRIC CABLE "Cu" 'CABLE SIZE'
‘CABLE DESIGNATION’ 'YEAR OF MFG'

PARAMETER SPECIFICATION
Max. Conductor Temperature at Rated Current 90°C
CARRYING

Ambient Air Temperature 40°C


CAPACITY
CURRENT

Ambient Soil Temperature 25°C


Soil Thermal Resistivity 1.2K.m/W
Depth Of Laying 0.5m

Voltage Grade 0.6/1 KV


Permissible Voltage Variation ± 10%
PROPERTIES
ELECTRICAL

Permissible Frequency Variation ± 5%


Combined Voltage & Frequency Variation ± 10%
Max. Conductor Temperature at Rated Current 90°C
Max. Conductor Temp. at the End of Short Circuit 250°C
PROPERTIES

Min. Oxygen Index As Per ASTMD-2863 30%


LSZH

Max. Smoke Density Rating As Per AS/NZS 61034-2 N/A

Fire Rated Test RHE-2 of AS/NZS 4507 ( Table -1)

DIMENSIONS

No./Nom. Cross No. Of Wire / Wire Size (Before Insulation(Nom./Min. Thickness) in


Sectional Area of Nom. Conductor Diameter in mm
Stranding) in Nos. X mm mm
Conductor in
Sq.mm
Phase Core Earth Core Phase Core Earth Core Phase Core Earth Core

2 x 2.5 + 2.5 (E) 7 / 0.68 7 / 0.68 1.98 1.98 0.7/0.53 0.7/0.53

2 x 6 + 2.5 (E) 7 / 1.035 7 / 0.68 3.08 1.98 0.7/0.53 0.7/0.53

DIMENSIONS

Australasian Cables (A Division of EESA Pty Ltd) 604/89, High Street, Kew 3101 Ph: 0437720513, 0420 598 900
www.eesa.net.au / sales@eesa.net.au
No./Nom. Cross
Outer Sheath
Sectional Area of Approx. Overall Dia. of Approx. Net Weight of Std. Packing Length In
(Nom./Min. Thickness)
Conductor in Cable in mm Cable in Kg/Km Mtrs
in mm
Sq.mm
2 x 2.5 + 2.5 (E) 1.8 / 1.43 12 175 680
2 x 6 + 2.5 (E) 1.8 / 1.43 14 270 500

ELECTRICAL PROPERTIES
Max. D.C
Max. A.C Short Circuit
Resistance Of Zero Sequence
No./Nom. Cross Resistance at Conductor Zero Sequence Rating
Conductor At Resistance at
Sectional Area of 90°C in Inductance @ Reactance At Conductor
20°C in 20°C in
Conductor in Sq.mm Ohm/Km 50hz And 90°C 50 Hz Ohm/Km (Duration 1
Ohm/Km Ohm/Km
Phase/Earth Sec.) in KA
Phase/Earth
2 x 2.5 + 2.5 (E) 7.41 / 7.41 9.48 / 9.48 N/A N/A N/A 0.36

2 x 6 + 2.5 (E) 3.08 / 7.41 3.94 / 9.48 N/A N/A N/A 0.86

CURRENT CARRYING CAPACITY


Unenclosed Enclosed - Wiring Underground
Buried direct
Enclosure In Air wiring enclosure
No./Nom. Cross Spaced Touching
Sectional Area of
Conductor in Sq.mm

2 x 2.5 + 2.5 (E) 41 Amps 39 Amps 33 Amps 39 Amps 39 Amps


2 x 6 + 2.5 (E) 69 Amps 65 Amps 56 Amps 64 Amps 64 Amps

INSTALLATION
No./Nom. Cross Sectional Area Min. Safe Bending Radius of Cable in mm
of Conductor in Sq.mm During Installation Installed
2 x 2.5 + 2.5 (E) 216 144
2 x 6 + 2.5 (E) 252 168

MECHANICAL PROPERTIES
No./Nom. Cross Sectional Area
of Conductor in Sq.mm Maximum Pulling Tension On Conductor in kN

2 x 2.5 + 2.5 (E) 0.53


2 x 6 + 2.5 (E) 1.02

Notes

1. The particulars given above are nominal & are subject to normal manufacturing tolerances.
2. Sequential length marking shall be provided at every one meter on outer sheath by hot foil indenting/Printing.
3. Earth Core insulation thickness chooses suitable to get earth core diameter equal to phase core.
4. All the drums shall be packed by PP sheet over the outermost cable layer.
5. Materials & properties of Insulation & Sheath are as per AS/ NZS 3808.