Vibration Isolator Fior CHWP
Vibration Isolator Fior CHWP
■Features
As an open-spring mount, it is usually used together with the inertia
base. It is easy to install and has a static deflection that is visible to
the naked eye, which facilitates inspection after installation. It has the
same components as SMA type, but has a static deflection of 50 mm,
and therefore, it is used when operation of equipment needs to be
quieter, such as when air conditioners and fans and are installed on
the ground level within the building. The top cap is made of SS400
steel plate, and it can be welded to the bottom structure, when it is
made of steel, like the H-bean, without making an extra hole for
installation. There is a CR-type pad attached on the base plate for a
slip-resistant and high-frequency isolation.
■Usage
◆F or standing pipes
◆F or high-efficient vibration control of ventilators (ground level)
◆F or high-efficient vibration control of air conditioning units
(ground level)
◆F or high-efficient vibration control of equipment that needs to be
kept quiet
■Specification
No. Name of Components Material Standard
1 Non Skid Pad CR KS M 6617
2 Lower Housing SS400 KS D 3503
SUP9 KS B 2402
3 Coil Spring
HSW3 KS B 2403
4 Upper Spring Cap SS400 KS D 3503
5 Level Bolt SS400 KS B 1002
6 Cap Screw SS400 KS B 1002
72
Pump Performance:According to ISO9906-2012,Grade 2B
P(kW)
35
28
21
14
7
0
0 12 24 36 48 60 72 84 96 108 120
H(m) Eff(%)
60 100
54
48 80
42
36 381.00mm 60
30
24 40
318.36mm
18
12 20
241.30mm
6
0 0
0 12 24 36 48 60 72 84 96 108 120
NPSH(m) Q(l/s)
12.5
10.0
7.5
5.0
2.5
0.0
0 12 24 36 48 60 72 84 96 108 120
2023-10-9
LEGEND ACOUSTICS ENGINEERING LTD.
UNIT 12, 4/F., BLOCK A, WAH TAT IND. CENTRE, 8-10 WAH SING ST., KWAI CHUNG, N.T. Selection Guideline: Selection Criteria
TEL : (852) 2815 0928, 2815 0899 FAX : (852) 2854 0123 As the end suction water pump <30kW and width <6m, the minimum static deflection should be >19mm (By ASHRAE handbook & NSV handbook) Minimum static deflection > 19mm
The requirement of Isolation Efficiency is > 95% E > 95%
By equation E=(1-TR)x100%, Transimssion Rate TR should be < 0.05 TR < 0.05
By equation TR=1/-(1-η2), Frequency Ratio η should be > 4.58 η > 4.58
CLIENT : ATAL By equation η=fd/fn, fn should be < fd/4.58
As given by manufacturer, the lowest fd is 738 RPM. By fn < 738/4.58, fn should be < 161RPM
fn < 161RPM
PROJECT : Tai Wo As given by manufacturer, the highest fd is 1475 RPM. By fn < 1475/4.58, fn should be < 322RPM
Under such circumstance, the 161 RPM is used as the criteria for fn
TITLE : Summary Table for Vibration Isolator - Water Pump By equation fn=1/2(3.14)Sqrt((9800/ds))*60, static deflection ds should be > 34.5mm to achieve 95% isolation efficiency
Minimum static deflection > 34.5mm
Also required by the specification, minimum 50% deflection should be achieved. Minimum static deflection should be > 12.5mm
DATE : 2024/1/15 (Rev.1) By equation K=W/ds, Spring Constant K should be less than Point Load/34.5 for each point K < (Point Load/34.5)
Total weight is divided into 4 points. Point load = Total Weight/4
Selection Criteria Point Load = Total Load/4 34.5 < ds < 50 Spring > 19mm > Point Load 4 fn < 161 Given fd (by manufacturer) K < (Point Load/34.5) η > 4.58 TR < 0.05 E > 95%
Isolation Isolation
Lowest Highest Frequency Frequency
No. of Total load (Inertia Block + Deflection of Rate Rate No. of Natural Spring constant Spring TR TR Efficiency Efficiency
Point Selection of Operating Operating Ratio η Ratio η
Item Designation Water Point Pump + Motor + Fittings + Point Load Deflection Capacity Spring frequency K criteria constant K (Lowest (Highest % %
Load (kg) Spring model Frequency Frequency (Lowest (Highest
Pump Water) (kg) (mm) (mm) (kg) Isolator fn (RPM) (kg/mm) (kg/mm) fd) fd) (Lowest (Highest
fd (RPM) fd (RPM) fd) fd)
fd) fd)
1 CHWP-4 1 4 4460 1115 46.5 SMA2-B-1200 50 1200 4 139 738 1475 < 32.3 24.0 5.32 10.64 0.037 0.009 96.33 99.11