WM311 HOMM Exterior wall

created on 1.9.2023

U-Value calculation according to DIN EN ISO 6946

# Material Dicke λ R
[cm] [W/mK] [m²K/W]
Thermal contact resistance inside (Rsi) 0,130
1 KNAUF Standard 15A+AL 1,50 0,210 0,071
2 Lámina de aluminio 0,00 160,000 0,000
3 KNAUF Standard 12,5A 1,25 0,210 0,060
4 KNAUF Insulation Ultracoustic Plus 7,00 0,035 2,000
Steel (Width: 0,06 cm) 7,50 50,000 0,002
Steel (Width: 0,06 cm) 0,50 50,000 0,000
Steel (Width: 0,06 cm) 0,50 50,000 0,000
Steel (Width: 5 cm) 0,06 50,000 0,000
Steel (Width: 5 cm) 0,06 50,000 0,000
5 KNAUF Insulation Ultracoustic Plus 5,00 0,035 1,429
6 KNAUF Insulation Ultracoustic Plus 10,00 0,035 2,857
Steel (0,092%) 10,00 50,000 0,002
Steel (Width: 0,06 cm) 0,50 50,000 0,000
Steel (Width: 0,06 cm) 0,50 50,000 0,000
Steel (Width: 5 cm) 0,06 50,000 0,000
Steel (Width: 5 cm) 0,06 50,000 0,000
7 KNAUF Aquapanel Outdoor 1,25 0,350 0,036
Thermal contact resistance outside (Rse) 0,040

Thermal contact resistances have been taken from DIN 6946 Table 7.
Rsi: heat flow direction horizontally
Rse: heat flow direction horizontally, outside: Direct contact to outside air
Upper limit of thermal resistance Rtot;upper = 6,609 m²K/W.
Lower limit of thermal resistance Rtot;lower = 3,672 m²K/W.
Check applicability: Rtot;upper / Rtot;lower = 1,800 (maximum allowed: 1,5)
DIN 6946 must not be used because the ratio of the upper limit value of the thermal resistance to the lower limit value of the
thermal resistance is more than 1.5.
Heat transfer coefficient from finite-elements method U = 0,182 W/(m²K)

outside
12,5 7

100 6
260,01

50 5

70 4
12,5 3
15 1 2
inside

50 600
50

Page 1
WM311 HOMM, U=0,18 W/(m²K)

Temperature profile
Temperature profile
20 Temperature
18 1 Dew point
16 2
Temperature [°C]

3 4 5 6 7
14
12
10
outside
8
6
4
2

0 50 100 150 200 250


Inside [mm] inside
Outside
50 600
1 KNAUF Standard 15A+AL (15 mm) 4 KNAUF Insulation Ultracoustic Plu... 6 KNAUF Insulation Ultracoustic Plu...
2 Lámina de aluminio 5 KNAUF Insulation Ultracoustic Plu... 7 KNAUF Aquapanel Outdoor (12,5 mm)
3 KNAUF Standard 12,5A (12,5 mm) 4 KNAUF Montantes verticales (75x50)
4 KNAUF Montantes verticales (75x50) 5 KNAUF Insulation Ultracoustic Plu...

Left:Temperature and dew-point temperature at the place marked in the right figure. The dew-point indicates the
temperature, at which water vapour condensates. As long as the temperature of the component is everywhere above the dew
point, no condensation occurs. If the curves have contact, condensation occurs at the corresponding position.
Right: The component, drawn to scale.

Layers (from inside to outside)


# Material λ R Temperatur [°C] Weight
[W/mK] [m²K/W] min max [kg/m²]
Thermal contact resistance* 0,250 19,2 20,0
1 1,5 cmKNAUF Standard 15A+AL 0,210 0,071 18,9 19,5 9,5
2 0,001 cm Lámina de aluminio 160,000 0,000 18,9 19,3 0,0
3 1,25 cm KNAUF Standard 12,5A 0,210 0,060 18,5 19,3 7,9
4 7 cmKNAUF Insulation Ultracoustic Plus 0,035 2,000 13,4 19,2 1,1
7,5 cmSteel (Width: 0,06 cm) 50,000 0,002 17,8 18,5 0,5
0,5 cmSteel (Width: 0,06 cm) 50,000 0,000 18,7 18,7 0,0
0,5 cmSteel (Width: 0,06 cm) 50,000 0,000 17,5 17,5 0,0
0,06 cm Steel (Width: 5 cm) 50,000 0,000 17,5 17,6 0,4
0,06 cm Steel (Width: 5 cm) 50,000 0,000 18,7 18,7 0,4
5 5 cmKNAUF Insulation Ultracoustic Plus 0,035 1,429 8,1 17,8 0,8
6 10 cm KNAUF Insulation Ultracoustic Plus 0,035 2,857 6,3 13,5 1,6
10 cm Steel (0,092%) 50,000 0,002 6,8 8,1 0,7
0,5 cmSteel (Width: 0,06 cm) 50,000 0,000 8,4 8,4 0,0
0,5 cmSteel (Width: 0,06 cm) 50,000 0,000 6,6 6,6 0,0
0,06 cm Steel (Width: 5 cm) 50,000 0,000 6,6 6,8 0,4
0,06 cm Steel (Width: 5 cm) 50,000 0,000 8,1 8,4 0,4
7 1,25 cm KNAUF Aquapanel Outdoor 0,350 0,036 6,3 6,8 14,4
Thermal contact resistance* 0,040 6,2 6,5
26,001 cm Whole component 5,500 38,1
*Thermal contact resistances according to DIN 4108-3 for moisture protection and temperature profile. The values for the U-
value calculation can be found on the page 'U-value calculation'.

Page 2
WM311 HOMM, U=0,18 W/(m²K)

Surface temperature inside (min / average / max): 19,2°C 19,4°C 19,5°C


Surface temperature outside (min / average / max): 6,3°C 6,3°C 6,5°C

Page 3
WM311 HOMM, U=0,18 W/(m²K)

Moisture proofing
For the calculation of the amount of condensation water, the component was exposed to the following constant climate for
90 days: inside: 20°C und 50% Humidity; outside: 6.2°C und 71% Humidity (Climate according to user input).
This component is free of condensate under the given climate conditions.

# Material sd-value Condensate Weight


[m] [kg/m²] [Gew.-%] [kg/m²]
1 1,5 cm KNAUF Standard 15A+AL 0,06 - 9,5
2 0,001 cm Lámina de aluminio 1500 - 0,0
3 1,25 cm KNAUF Standard 12,5A 0,05 - 7,9
4 7 cm KNAUF Insulation Ultracoustic Plus 0,07 - 1,1
7,5 cm Steel (Width: 0,06 cm) 12,00 - 0,5
0,5 cm Steel (Width: 0,06 cm) 180,00 - 0,0
0,5 cm Steel (Width: 0,06 cm) 180,00 - 0,0
0,06 cm Steel (Width: 5 cm) 1500 - 0,4
0,06 cm Steel (Width: 5 cm) 1500 - 0,4
5 5 cm KNAUF Insulation Ultracoustic Plus 0,05 - 0,8
6 10 cm KNAUF Insulation Ultracoustic Plus 0,10 - 1,6
10 cm Steel (0,092%) 9,00 - 0,7
0,5 cm Steel (Width: 0,06 cm) 180,00 - 0,0
0,5 cm Steel (Width: 0,06 cm) 180,00 - 0,0
0,06 cm Steel (Width: 5 cm) 1500 - 0,4
0,06 cm Steel (Width: 5 cm) 1500 - 0,4
7 1,25 cm KNAUF Aquapanel Outdoor 0,83 - 14,4
26,001 cm Whole component 1.670,45 0 38,1

Humidity
The temperature of the inside surface is 19,2 °C leading to a relative humidity on the surface of 53%.Mould formation is not
expected under these conditions.
The following figure shows the relative humidity inside the component.

100 Relative humidity (%)


90 1 saturation point
80 2
Relative humidity (%)

3 4 5 6 7
70
60
50
outside
40
30
20
10
0
0 50 100 150 200 250
Inside [mm] inside
Outside
50 600
1 KNAUF Standard 15A+AL (15 mm) 4 KNAUF Insulation Ultracoustic Plu... 6 KNAUF Insulation Ultracoustic Plu...
2 Lámina de aluminio 5 KNAUF Insulation Ultracoustic Plu... 7 KNAUF Aquapanel Outdoor (12,5 mm)
3 KNAUF Standard 12,5A (12,5 mm) 4 KNAUF Montantes verticales (75x50)
4 KNAUF Montantes verticales (75x50) 5 KNAUF Insulation Ultracoustic Plu...

Notes: Calculation using the Ubakus 2D-FE method. Convection and the capillarity of the building materials
were not considered. The drying time may take longer under unfavorable conditions (shading, damp / cool
summers) than calculated here.

Page 4
WM311 HOMM, U=0,18 W/(m²K)

Moisture protection in accordance with DIN 4108-3:2018 Appendix A


The temperatures and / or humidities you specify are not in accordance with DIN 4108-3. The following values are given by
DIN 4108-3: 20°C / 50% humidity inside and -5°C / 80% humidity outside. Change the values in the input form to enable the
calculation according to DIN 4108-3.

Page 5
WM311 HOMM, U=0,18 W/(m²K)

Heat protection
The following results are properties of the tested component alone and do not make any statement about the heat protection
of the entire room:

Temperature profile
36 Temperature at 3pm, 11am and 7am
34 1 Temperature at 7pm, 11pm and 3am
32 2
30 3 4 5 6 7 1 KNAUF Standard 15A+AL (15 mm)
Temperature [°C]

28 2 Lámina de aluminio
26 3 KNAUF Standard 12,5A (12,5 mm)
24 4 KNAUF Insulation Ultracoustic Plus (70 mm)
22 5 KNAUF Insulation Ultracoustic Plus (50 mm)
20 6 KNAUF Insulation Ultracoustic Plus (100 mm)
18 7 KNAUF Aquapanel Outdoor (12,5 mm)
16
14
0 50 100 150 200 250
Inside [mm]
Outside

[°C] The surface temperature during the day


36 Outside
34 Inside
32
30
28
26
24
22
20
18
16
14 Phase shift: 6.7h
12 14 16 18 20 22 24 2 4 6 8 10 12
[time of day]
Top:Temperature profile within the component at different times. From top to bottom, brown lines: at 3 pm, 11 am and 7 am
and red lines at 7 pm , 11 pm and 3 am.
Bottom:Temperature on the outer ( red ) and inner ( blue ) surface in the course of a day. The arrows indicate the location of
the temperature maximum values . The maximum of the inner surface temperature should preferably occur during the
second half of the night.

Phase shift* 6,7 h Heat storage capacity (whole component): 37 kJ/m²K


Amplitude attenuation ** 8,7 Thermal capacity of inner layers: 18.9 kJ/m²K
TAV *** 0,115
* The phase shift is the time in hours after which the temperature peak of the afternoon reaches the component interior.
** The amplitude attenuation describes the attenuation of the temperature wave when passing through the component. A value of 10
means that the temperature on the outside varies 10x stronger than on the inside, e.g. outside 15-35 °C, inside 24-26 °C.
*** The temperature amplitude ratio TAV is the reciprocal of the attenuation: TAV = 1 / amplitude attenuation
Note: The heat protection of a room is influenced by several factors, but essentially by the direct solar radiation through windows and the
total amount of heat storage capacity (including floor, interior walls and furniture). A single component usually has only a very small
influence on the heat protection of the room.

The calculations presented above have been created for a 1-dimensional cross-section of the component.