Professional Documents
Culture Documents
Pesgm2022 003489
Pesgm2022 003489
in Inverter-Interfaced Microgrids
Kwasi Opoku, Subash Pokharel, and Aleksandar Dimitrovski
Department of Electrical & Computer Engineering
University of Central Florida
Orlando, Florida 32826
Email: opokukwasi@knights.ucf.edu, pokharelsbs@ieee.org, adimitrovski@ucf.edu
Abstract—Directional protection has been employed for many The rapid development of communication infrastructure
years in transmission and distribution networks to achieve the has indeed motivated other similar schemes such as wide-
required secure and selective protection. It also offers great area protection and traveling waves-based schemes [10], [11].
potential for dealing with the unique problems introduced in
inverter-interfaced microgrids. The control methods used in Generally, the outlined solutions that require extensive com-
inverter-based distributed generation (IBDGs), introduce further munication infrastructure result in increased costs, rendering
challenges that affect fault detection in microgrids. This paper them uneconomical in some cases. Directional relays, however,
reviews the influence of inverter control on fault conditions and provide a non-communication-assisted approach to increase
proposes a directional method for detecting unbalanced faults in the selectivity and security of microgrid protection systems.
a microgrid, using negative sequence admittance. This approach
provides a sensitive and selective option for the protection system. By comparing the voltage and current phasor magnitude and
The method is compared with the existing negative sequence- angle, faults can be determined to be forward or backward.
based directional protection methods. Results from simulation The drawback of traditional directional overcurrent, however,
studies are used to verify its effectiveness. is the reduced sensitivity to current magnitudes in microgrids
Index Terms—negative sequence, inverter-interfaced micro- [12]. By modifying the reference and polarizing quantities, to
grds, directional overcurrent, microgrid protection, distributed
generation, superimposed quantities include symmetrical or superimposed sequence quantities, the
sensitivity of such directional elements can be improved in
I. I NTRODUCTION microprocessor relays [12], [13].
A significant area of focus in microgrid development is the It is well known that the frequency of asymmetrical fault
protection challenges introduced by such active distribution incidents (single-phase-to-ground, phase-to-phase, and double-
networks. These, together with the new protection consider- phase-to-ground) constitute about 95 percent of all faults in the
ations, have been well-documented in existing literature [1], power system [14]. This implies that the negative sequence
[2]. quantities present in significant levels during such unbalanced
Researchers have proposed several approaches to deal with faults offer the potential to identify and discriminate the
the microgrid protection challenges, and these new solutions overwhelming majority of faults. This paper reviews the fault
are continuously evolving. Such solutions combine conven- response of constant-current (CC) controlled, PQ-controlled,
tional protection methods with the flexibility offered by en- and Voltage-Frequency (V/F) controlled inverters in a grid-
hanced communication in the distribution network. A com- connected microgrid and their influence on the negative se-
mon approach employed is adaptive protection, where the quence. Furthermore, it introduces an admittance-based neg-
protection configuration is adapted to make the best protection ative sequence element that effectively detects asymmetrical
decision based on prevailing system values and operation faults under these conditions. This method is compared with
mode or topology. This method may be centralized as in [3], the traditional torque-based negative sequence directional re-
using a central controller, or decentralized as proposed in [4]. lay, a negative sequence impedance element employed in [15]
Differential protection schemes have also been proposed to and a superimposed negative sequence directional element
solve the sensitivity and selectivity problems of microgrid pro- proposed in [12].
tection [5]–[7]. These include line current differential methods, The fault responses of IBDGs are reviewed in Section
as extensively deployed in transmission networks, and other II, and the different negative sequence directional elements
novel differential protection approaches. Data transmission are discussed in Sections III. Sections IV and V introduce
bandwidth and synchronization considerations are critical for the proposed admittance approach and present simulations of
this method. A large number of load nodes in distribution various scenarios in a test system.
networks also poses a challenge to the implementation of II. FAULT R ESPONSE OF I NVERTER -BASED D ISTRIBUTED
differential protection [8]. In a similar vein, distance protection G ENERATION (IBDG)
methods have been considered to improve sensitivity issues in
microgrids [9]. It has the advantage of not being dependent The response of IBDGs during faults is determined by the
only on the limited fault current magnitudes. Communication- control strategy employed, along with other factors. Control
assisted schemes may, in this case, be used as a backup to methods may be categorized as current control or voltage
eliminate the impact of infeed and outfeed currents of DGs. control. Current control modes are widely used in grid-
connected IBDGs, and they directly control the output current
This material is based upon work supported by the U.S. Department of of the inverter to track the output complex power. Voltage
Energy’s Office of Energy Efficiency and Renewable Energy (EERE) under control methods are modeled as ideal voltage sources and
the Solar Energy Technologies Office Award Number DE-EE0002243-2144.
The views expressed herein do not necessarily represent the views of the U.S. do not directly regulate the output current of the DG. They
Department of Energy or the United States Government. are applicable for grid-forming inverters. This paper considers
∗
P∗
id 1 vd vq
i∗q = v 2 + vq2 vq −vd Q∗ (2)
d
three types of control modes: for current control, the Constant- C. V/F Control of IBDGs
Current (CC) Control and the PQ Control, and for voltage This method is widely used in grid-forming inverters, and
control, the Voltage-Frequency (V/F) control. Detailed descrip- it supports the voltage and frequency of the microgrid to
tions of the control types and structures are discussed in [16]. maintain stability. It is common in stored-energy DGs [17]. It
A. Constant-Current Control of IBDGs is also implemented in the dq frame, providing an outer voltage
control loop to regulate the voltage and also determine the
The constant-current (CC) control method is implemented current reference. The V/F control does not directly regulate
in the natural frequency frame (abc frame) and it delivers the output current. Instead, the current reference is used in
a constant output current iabc . A current reference i∗abc is an inner current loop to generate voltage modulation in the
determined by the current control loop, and this reference PWM used for switching of the semiconductor devices to
does not change in magnitude, angle, or frequency even maintain stability. The transfer function of this control can
under variations in voltage. Hence, during an unbalanced fault, be generically represented as
the constant reference results in a constant balanced output.
The transfer function of a CC controlled inverter could be ∗
Vdq = Gv (s)Vdq − Z(s)i0dq (3)
generically represented as
∗
where Vdq and Vdq represent the reference voltage and output
iabc = Gi (s)i∗abc (1) voltage (in dq frame) respectively, and Gv (s) and Z(s)
where Gi (s) represents the closed-loop gain of the control. A represent the closed loop gain of the outer voltage loop and
proportional-integral (PI) controller can be used to achieve the the inner current loop, respectively. Gv (s) and Z(s) depend
desired control action. on the time constant, τi , of the inner current loop.
Fig. 2 illustrates the response of the CC controlled inverter When subjected to an asymmetrical fault, the imbalance
when the test system in Fig. 1 [16] is subjected to a double- will be realized, both in output voltage and current, due to
phase-to-ground (B-C-G) fault at F1 at t = 0.08s. It can be the control action of the V/F control described. Fig. 4 shows
observed that, while significant imbalance is realized in the the fault response to a B-C-G fault at F1 . It should be noted
output voltage due to the imbalances in the grid-side voltage, that the simulation model is presented to illustrate how the
the output current remains constant and balanced. V/F control mimics the response of synchronous generators
to support voltage and frequency stability. In practical appli-
B. PQ Control of IBDGs cations, a current limiter is used to reduce the fault current to
This method determines the current reference limits by acceptable levels [18].
using an outer power loop. Unlike the CC method, the current The responses of the different inverter control methods
reference is adjusted based on variations in the grid voltage. described reveal differences and limitations in the negative
It is implemented in the synchronous reference (dq) frame. sequence contribution under asymmetrical faults. Nonethe-
The current reference in dq frame (i∗d and i∗q ) are obtained less, these unique negative sequence characteristics can be
given a preset active and reactive power reference (P ∗ and employed to obtain a secure, selective, and sensitive fault
Q∗ ) as given in (2). detection method.
TABLE I
Start R ESPONSE TO F1 , F2 AND F3 WITH IBDG IN CC C ONTROL M ODE
F1 F2 F3
Relay |∆Y2 | arg(∆Y2 ) Det |∆Y2 | arg(∆Y2 ) Det |∆Y2 | arg(∆Y2 ) Det
A 50.64 153.4◦ F 50.64 153.4◦ F 0.85 −13.7◦ R
No |I2/I1|>0.1 B 50.62 153.4◦ F 0.83 −13.3◦ R 0.83 −13.6◦ R
Or
0.7<|I0/I2|<1.4 C 2.3e-2 −6.6◦ R 2.3e-2 −6.4◦ R 2.3e-2 −6.6◦ R
Yes
No Yes
Calculate
Y2>Yset
arg{ Y2}
No
(180+ )<arg{!Y2} (0+!)<arg{ Y2}<
<(360+ ) (180+!)
Yes Yes
Fig. 7: ∆Y2 for fault at F4 with PQ controlled IBDG
Reverse Forward
Fault Fault TABLE II
R ESPONSE TO F1 , F2 AND F3 WITH IBDG IN PQ C ONTROL M ODE
F1 F2 F3
Stop Relay |∆Y2 | arg(∆Y2 ) Det |∆Y2 | arg(∆Y2 ) Det |∆Y2 | arg(∆Y2 ) Det
A 50.64 153.7◦ F 50.65 153.5◦ F 0.85 −13.7◦ R
B 50.66 153.5◦ F 0.82 −13.6◦ R 0.82 −13.6◦ R
Fig. 5: Proposed algorithm C 6.5e-3 −4.4◦ R 6.8e-3 −6.1◦ R 6.8e-3 −6.1◦ R
V. S IMULATION R ESULTS
51 and phase angle of about 153◦ at a steady state during
Several simulation studies are carried out on the network in a forward fault. Relay B also correctly detects the fault as
Fig. 1 to evaluate the performance of the proposed method in reverse with lower magnitude of 0.82 and a phase angle of
Section IV. A 10/0.4kV transformer connects the microgrid −14◦ . The results for similar faults at F1 , F2 and F3 are
to the main grid. A 13.2 + j3.14Ω load is connected to presented in Table I. A relatively smaller change is observed
the microgrid. The DG is rated at 0.01 + j0.01MVA and is for the reverse faults, but a phase angle clearly discriminates
simulated under CC, PQ, and V/F control modes, and the fault from forward faults. It should be noted that the plots do not
response of the DGs are as described in [16]. Relays A, B, show the relay response until half-cycle before the fault. This
and C are positioned at bus B1, load feeder, and DG feeder, is because the ∆Y2 computation has a zero denominator. The
respectively. Settings guide provided in [13] for determining pre-fault value can be considered to be zero by the relay.
Z2 is applied to the system to determine admittance values With the DG in PQ control mode, similar results to the same
under normal condition and Yset is set at 30, which allows for B-C-G faults are observed, as shown in Fig. 7. DGs in both
a significant margin. Also, due to the protected line, ϕ is set CC and PQ control modes have a similar negative sequence
at 14◦ , 26.6◦ and 27.6◦ for relay A, B and C respectively. It current response. The results for the faults at F1 , F2 and F3
must be noted that this test system is obtained from the system are presented in Table II.
used in [16] to analyse response of inverters under various Fig. 8 shows some variation in the simulation results for the
control schemes. The line angles used here fall below typical ∆Y2 when the DG is in V/F control mode. The increase in
distribution line angles of 45◦ to 60◦ . Tests conducted using |∆Y2 | values is due to the negative sequence current support
angles in this range proved even more secure performance of provided in this mode during faults. Fault responses at F1 , F2
the protection. and F3 are presented in Table III.
Fig. 6 shows the operating response of relays A, B and Results for high impedance fault (HIF) simulation are
C for B-C-G bolted faults at F4 at t = 0.08s during CC presented in Table IV. It is important to note that the |I2 /I1 |
control of the DG. The results for both relays A and C show starting criterion falls below the required 0.1 setting under
a significant increase in the ∆Y2 magnitude from 0 to about these conditions. The high impedance fault ratio factor of