FACTOR CONTROLLER
INSTRUCTION MANUAL
etaSMART
etaSMART 16R
15 16
13 14
10 11 12
8 9
6 7
4 5
2 3
1
LEAD
4R
LAG etaSMART
ALARM
AUTO
MANUAL
3 4
1 2
LLER
CONTRO LEAD
R FACTOR
TIC POWE LAG
AUTOMA ALARM
AUTO
MANUAL
LLER
CONTRO
ER FACTOR
TIC POW
AUTOMA
• Manufacturer assumes no responsibility for a hazard or • Installation, commissioning and maintenance to be
damage caused by incorrect or non-application of any of done by qualified personnel only
the instructions attached herein. • Hazards of electric shock and burning.
• Use according to the operating instructions, professional
practices, wiring rules, codes, safety regulations
applicable to the given installation.
• Packaging material can be recycled.
• Disconnect the power and isolate before proceeding with
• Poly bags can be recycled separately
any work on this equipment.
• Always use an appropriate voltage detection device to
Confirm the absence of voltage.
UNPACKING
4R
etaSMART 6-Pole 10-Pole
3 4
1 2
3-Pole 2-Pole
LEAD
LAG
ALARM
AUTO
MANUAL
CONTROLLER 4 INSTRUCTION
IC POWER
FACTOR
MANUAL
AUTOMAT
PRODUCTS TERMINAL CONNECTORS MOUNTING CLAMPS
etaSMART is available in two frame sizes and has 6 variants based on the
number of relay contact outputs and 4 variants in transistor contact
outputs. 1 2 3 4 5 6 7 8
LEAD
AUTO
MANUAL
Frame - 1
Relay contact output :
ALARM
AUTO
MANUAL
Transistor contact output :
etaSMART-8T, 8 steps APFC Relay, CAT NO:CS91614OOOO AUTOMATIC POWER FACTOR CONTROLLER
Frame - 2
etaSMART-12T, 12 steps APFC Relay, CAT NO: CS91615OOOO
05
3. INSTALLATION
3.1 PANEL CUT-OUT
etaSMART is designed for flush mounting on any control panel. Please refer to the dimensional drawing shown below for
understanding the overall & cut out dimensions for panel.
92
Panel Cutout
NOTE: All dimensions are in mm
96
etaSMART 4R
70.9
1 2 3 4
96
58.3
LEAD
LAG
ALARM
AUTO
MANUAL
06
Panel cut-out for etaSMART 12R / 14R / 16R / 8T / 12T / 15T.
138
138
Panel Cutout
NOTE: All dimensions are in mm
144
71.6
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
58.3
144
LEAD
LAG
ALARM
AUTO
MANUAL
Provide a cut-out as shown in above figure for respective model. Push the etaSMART relay through the cut out
and fix the relay to the panel by means of the two mounting clamps
07
3.2 WIRING DIAGRAM
etaSMART 4R / etaSMART 6R / etaSMART 8R
L1
MAINS
LOAD
L2
CT1
L3
N
SUPPLY FU3
AC
(8A)
C1
L3
L2
L1
S1
CURRENT
1A / 5A
INPUT
R1
1
S2
FU2 (1A)
R2
2
415 - 440 V AC
U1
VOLTAGE
SUPPLY
R3
3
U2
FU5 BANK1
FU1 (1A)
K1
R4
4
D
A
O
L
FU4
R5
5
Wire Range 30 - 12 AWG Stranded Or Solid
CAT.NO. CS90902OOOO
R6
6
RELAY OUTPUTS
Terminal Torque 0.5 N-m
etaSMART - 8R
NOTE: BANK2
R7
FU6
7
K2
1. Connect phase to phase voltage to input terminal
8
R8
U1 & U2 for voltage input.
C2
2. Ensure primary CT must be connected on remaining
phase and connect CT secondary to terminal S1 & S2.
5. All relay terminals are suitable for wire range 30 - 12 AWG stranded or solid Copper Wire.
08
etaSMART 12R / etaSMART 14R / etaSMART 16R
L1
MAINS
L2
LOAD
CT1
L3
N
FU3 (5A)
FU4
(16A)
C1
C2
R1
1
R16
16
R2
2
R3
17
3
FU5 BANK1
R4
4
SUPPLY
AC
L3
L2
L1
R5
5
Max Common Current - 16A
S1
CURRENT
1A / 5A
INPUT
RELAY OUTPUTS
R6
S2
6
FU2 (1A)
R7
415 - 440 V AC
U1
7
VOLTAGE
SUPPLY
R8
U2
8
FU6 BANK2
FU1 (1A)
R9
9
K2
NOTE:
D
A
O
L
R10
10
Wire Range 30 - 12 AWG Stranded Or Solid
1. Connect phase to phase voltage to input terminal
R11
11
415-440 V 50/60 Hz MAX 6.5 VA
CAT.NO. CS90905OOOO
Terminal Torque 0.5 N-m
etaSMART - 16R
R12
12
415 - 440 V AC
U1 & U2 for voltage input.
R13
13
R14
14
2. Ensure primary CT must be connected on remaining K1
R15
15
phase and connect CT secondary to terminal S1 & S2. FU7 BANK15
K15
4. Last relay contact output in the etaSMART relay is changeover contact ALARM
5. All relay terminals are suitable for wire range 30 - 12 AWG stranded or solid Copper Wire.
09
ALARM
T1
T2
T3
T4
T5
T6
7
T1 T2 T3 T4 T5 T6 R1
TRANSITOR OUTPUTS
Rating : 8 - 48VDC,100mA
SUPPLY
CURRENT VOLTAGE
INPUT 415 - 440 V
1A / 5A AC
etaSMART - 6T
CAT.NO. CS91613OOOO
6 Steps APFC Relay
11
FU15
C1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15
TRANSISTOR OUTPUTS
Rating : 8 - 48VDC,100mA
!
415 - 440 V AC
L1
AC L
O
SUPPLY
L2
A
L3
D
R1 etaSMART - 15T
CURRENT SUPPLY
INPUT VOLTAGE CAT.NO. CS91616OOOO
1A / 5A 415 - 440 V 15 Steps APFC Relay
AC 415-440 V 50/60 Hz MAX 6.5 VA
Wire Range 30 - 12 AWG Stranded Or Solid
C2 16 17 S1 S2 U1 U2 Terminal Torque 0.5 N-m
Common emitter Circuit
C1 T1 T2 T3 T4 T5 T6
C1 L1 L3 C3 C1 L1 L3 C3
2 Amp
- +
24 V DC
12
NOTE:
• Connect voltage input from any two phases and current from the remaining third phase.
• Capacitor duty contactor must be used for capacitor switching.
ü CT
û
CT
û
CT
Load APFC
Panel
• Recommendation – Use CT with 1 Amp secondary in case the distance between CT and Controller is more than 10 meter
13
PF: 1.000
+++!!!---XX--- - -
14
A
A
DIS SENSITVITY
60 s
15
16
SENSITIVITY: It defines the speed of capacitor bank connection. A low sensitivity provides faster connection with greater
number of capacitor switching whereas high sensitivity provides slower connection with less number of capacitor switching.
Example:
If required kVAr to reach the target PF is 80kVAr, then soft logic internally calculates number of required steps to connect and
achieve target PF.
Suppose require steps to achieve target PF is 4 & sensitivity is set as 60, then switching time between two banks will be
calculate as, Switching Time = Sensitivity / n = 60/4 =15 Sec
So, each capacitor bank will connect to the line voltage in interval of 15sec.
Sensitivity is applicable for only Relay steps connection.
17
REMARK
-
-
-
-
Applicable for contactor switching
(Recommended value is 60 s)
Applicable for contactor switching
(Recommended value is 60 s)
Applicable for thyristor switching
-
18
19
20
21
22
23
24
25
OPERATING MODE
MANUAL
+++!!!!+--------
26
SYMBOLS DESCRIPTION SYMBOLS DESCRIPTION
+ Step connected X Faulty step
- Step disconnected F Step configured as FAN
33
CUSTOMER INTERACTION CELL (CIC)
BSNL/MTNL (Toll-Free): 1800 233 5858
RELIANCE (Toll-Free): 1800 200 5858
Telephone : 022 6774 5858
email: cic@LNTEBG.com
website:www.LNTEBG.com
SP50029