UPS Technical

Revision 9
Contents

Sentryum – S3M/S3T 2
Multipower – MPW/MPX 8
Multipower – MP2/M2S 13
Multisentry - MST 19
Central Supply System CSS 24
Nextenergy - NXE 31
MasterPlus - MHT 35
MasterPlus - MHE 38
MasterPlus - MPS 42
Sentinel Dual - SDU 48
Sentinel Tower - STW 50
Sentinel Dual (Low Power)- SDH 52
Sentinel Pro - SEP 53
Sentinel Rack - SER 54
Vision Dual/Rack/Tower – VSD/VSR/VST 55

Power Cable Part Numbers 56


Power Connector Part Numbers 57
Cable Assembly Part Numbers 58

1
Sentryum – S3T
Technical Data
AC/AC Efficiency %
Power Power Dissipated Power Dissipated DC/AC Efficiency Bypass i2t
S3T KA Rating Battery Qty
Factor 0% Load 100% Load 25% 50% 75% 100% % (A2s)

10 100W 410W 94.30 95.60 96.00 96.10 95.90 11250 6KA


15+15 (75% nominal power)

15 119W 590W 95.20 96.20 96.30 96.20 96.40 11250 6KA


16+16 (80% nominal power)

20 119W 840W 95.60 96.20 96.30 96.20 96.40 11250 6KA


17+17 (85% nominal power)

30 165W 1210W 96.00 96.40 96.30 96.10 96.50 20000 6KA


18+18 (90% nominal power)

40 1 226W 1610W 95.20 96.60 96.30 96.10 96.50 20000 6KA


19+19 (95% nominal power)

60 341W 2570W 96.09 96.43 96.15 95.90 96.68 20000 10kA


20+20 (full nominal power)

80 350W 4040W 95.00 95.42 95.33 95.20 94.15 18000 10kA


21+21 (full nominal power)

100 360W 5060W 95.50 95.80 95.55 95.17 95.37 18000 10kA
22+22 (full nominal power)

120 405W 6130W 96.21 96.10 95.63 95.16 94.07 18000 10kA

Inverter Short Circuit (Ph-N) Inverter Overload Bypass Overload

>103% - ≤120% - 60 min. ≤110% - Infinite


>120% - ≤125% - 10 min >110% - ≤125% - 60 min.
2.7 x In for 200ms +
>133% - ≤ 150% >125% - ≤ 150% - 10 min.
1.5 x In for 300ms
>150% - ≤ 200% >150% - ≤ 200% - 60 sec
>200% >150% - 20 sec

2
Sentryum – S3T
Electrical Data

Input AC Output AC DC
Battery
Max AC Max AC Input Battery
SWBATT Fuse Recharge Max UPS
S3T Input Output Protection Recharge Max Typical Max Typical Max Typical
Rating Current DC Current
Current Current Rating Current (ER) Terminal Cable Earth Terminal Cable Terminal Cable
(Standard)
Size Size Size Size Size Size

32A gG 10mm2 10mm2 10mm2


10 21A 16A 32A 6A 12A* 27.5A Terminal
4mm2 M6
Terminal
4mm2
Terminal
6mm2
(10x38)

50A gG 16mm2 16mm2 16mm2


15 31.5A 24A 50A 6A 20A* 41A 6mm2 M6 6mm2 10mm2
(14x51) Terminal Terminal Terminal

50A gG 16mm2 16mm2 16mm2


20 40A 32A 50A 6A 20A* 55A 10mm2 M6 10mm2 16mm2
(14x51) Terminal Terminal Terminal

80A gR 35mm2 35mm2 35mm2


30 63A 48A 80A 10A 30A* 82A 10mm2 M6 10mm2 16mm2
(22x58) Terminal Terminal Terminal

100A gR 35mm2 35mm2 35mm2


40 80A 64A 100A 10A 30A* 110A Terminal
16mm2 M6
Terminal
16mm2
Terminal
16mm2
(22x58)

125A gR 500v 50mm2 50mm2 50mm2


60 120A 87A 125A 10A 30A 165A 25mm2 25mm2 35mm2
(22x58) Terminal M6 Terminal Terminal

80 153A 133A 160A N/A 12A 30A 230A M8 50mm2 M8 M8 50mm2 M8 70mm2

100 191A 167A 200A N/A 12A 30A 285A M8 70mm2 M8 M8 70mm2 M8 95mm2

120 230A 200A 250A N/A 30A** N/A 340A M8 95mm2 M8 M8 95mm2 M8 120mm2

*Output load less than 65%

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

3
Sentryum – S3M
Technical Data

AC/AC Efficiency %
DC/AC
Power Power Dissipated Power Dissipated Bypass i2t Fan Capacity
S3M Efficiency KA Rating Battery Qty DC Voltage
Factor 0% Load 100% Load (A2s) M3/h
25% 50% 75% 100% %

10 100W 375W 94.6 95.8 96.0 95.8 95.9 20000 6KA 20+20 480V 235

15 1 120W 530W 94.9 96.1 96.2 96.0 95.9 35000 10KA 20+20 480V 330

20 120W 765W 95.6 96.1 96.0 95.7 95.9 35000 10KA 20+20 480V 475

Inverter Short Circuit (Ph-N) Inverter Overload Bypass Overload

>103% - ≤120% - 60 min. ≤110% - Infinite


>120% - ≤125% - 10 min >110% - ≤125% - 60 min.
2.7 x In for 200ms +
>133% - ≤ 150% >125% - ≤ 150% - 10 min.
1.5 x In for 300ms
>150% - ≤ 200% >150% - ≤ 200% - 60 sec
>200% >150% - 20 sec

4
Sentryum – S3M
Electrical Data

Input AC Output AC DC
Max AC Max AC Battery Battery
Max AC Input Max UPS
Input Input SWBATT Fuse Recharge Recharge
S3M Output Protection DC Max Typical Max Typical Max Typical
Current Current Rating Current Current
Current Rating Current Terminal Cable Earth Terminal Cable Terminal Cable
L1 L2/L3 (Standard) (ER)
Size Size Size Size Size Size

32A gG 16mm2 16mm2 10mm2


10 63A 21A 48A 80A 6A 12A* 27.5 10mm2 M6 10mm2 6mm2
(10x38) Terminal Terminal Terminal

50A gG 35mm2 35mm2 16mm2


15 94.5A 31.5A 72A 100A 6A 20A* 41 16mm2 M6 16mm2 10mm2
(14x51) Terminal Terminal Terminal

50A gG 35mm2 35mm2 16mm2


20 120A 40A 96A 125A 6A 20A* 55 25mm2 M6 25mm2 16mm2
(14x51) Terminal Terminal Terminal

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

5
Sentryum
Mechanical Data

Compact - CPT Active - ACT Xtend - XTD

10 15 20 10 15 20 30 40 10 15 20 30 40 60
Weight (Unpopulated) kg 48 50 52 72 74 76 78 82 103 105 107 112 116 130
Weight (Populated)
151 153 155 278 280 282 284 288 412 414 416 421 425 439
kg
Fan Flow Rate
235 330 475 235 330 475 645 860 235 330 475 645 860 1370
(m3/h)

Cable Entry Bottom - Rear Bottom - Front Bottom - Front

Noise Level (Full Load) (dBA) <55 <60 <55 <60 <60 <62 <55 <60 <60 <62 <68

IP Rating IP20 IP20 (IP21, IP30, IP31 are available on request)

Battery 1 x (20+20) 7Ah/9Ah 2 x (20+20) 7Ah/9Ah 3 x (20+20) 7Ah/9Ah 3 x (20+20)

Width (mm) • 280mm 380mm 440mm


Height (mm) • 700mm 1025mm 1320mm
Depth (mm) • 840mm 850mm 840mm

6
Sentryum
Mechanical Data

Sentryum 80-120kVA Sentryum Rack

80 100 120 Cabinet SRT/M PWC 60 Power Module SRM/T 20

Weight (kg) 172 180 198 165 (Empty) 41

Fan Flow Rate (m3/h) 2400 3000 3600

Cable Entry Bottom - Front Top & Bottom

Noise Level (Full


<62 <63 <68 N/A <62
Load) dBA
- IP20 (either with the cabinet doors open or closed)
IP Rating IP20
IP21/31 optional
Width (mm) 500 700 445
Height (mm) 830 2060 397
Depth (mm) 1600 750 664

7
Multipower
Technical Data

Power Power AC/AC Efficiency % DC/AC Efficiency


Power Power Max Battery
Dissipated Dissipated 0% Battery Qty DC Voltage
Modules Factor Recharge Current
100% Load Load 25% 50% 75% 100% 25%-50% 50%-80% 80%-100%

MPW PM25
1 1.18kW 202W 94.7% 96.20% 96.30% 96.20% 95.30% 95.50% 95.30% 8A 20+20 480V
(4U)
MPW PM42
1 1.62kW 220W 95.7% 96.20% 96.10% 95.80% 95.30% 95.50% 95.30% 8A 20+20 480V
(4U)
MPW PM15X
1 0.625kW 154W 94.30% 95.70% 96.00% 96.00% 94.30% 95.20% 95.70% 6A 20+20 480V
(2U)
MPW PM25X
1 1.042kW 205W 95.00% 96.10% 96.10% 96.00% 95.10% 95.60% 95.70% 8A 20+20 480V
(2U)

Max Short Auto Inverter Short Circuit (Ph-N)


Ka
Cabinet Module Type Bypass A2t circuit Consumption
Rating MPW PM25 MPW PM42 MPW PM15X MPW PM25X
Current 20mS No Load
MPW PM25 (4U) 145000 5400A 10KA 702W 2.5 x In 200ms + 1.5 x In for 300ms 2.5 x In 100ms + 1.5 x In for 400ms
MPW CBC
130 MPW PM42 (4U) 145000 5400A 10KA 752W Inverter Overload
MPW PM25 MPW PM42 MPW PM15X MPW PM25X
MPW PM25 (4U) 1620000 19000A 10KA 1598W
MPW PWC
300 >101% - ≤125% 10 min.
MPW PM42 (4U) 1805000 19000A 10KA 1715W
>125% - ≤150% 1 min.
MPX PM15 (2U) 145000 5400A 10KA 570W
MPX CBC >150% - ≤ 180% 0.5 sec
75X MPX PM25 (2U) 145000 5400A 10KA 730W
>180% 0.2 sec
MPX PM15 (2U) 145000 5400A 10KA 920W
MPW PWC Bypass Overload
130X MPX PM25 (2U) 145000 5400A 10KA 1190W
MPW 130BM MPW 300 BM
MPX PM15 (2U) 145000 5400A 10KA 730W >101% - ≤125% 10 min.
MPX CBC
100X MPX PM25 (2U) 145000 5400A 10KA 950W > 125% 1 min

8
Multipower - MPX
Electrical Data
Max Module Max Output Max AC Input Max AC Output Input Protection DC Fuse Max DC AC DC
MPX
QTY Power Current Current Rating Rating Current Input Output Bypass +N-
MPW PM15X (15kVA/kW)
1 Module 15kVA 31A 22A 32A 50A 39A
2 Modules 30kVA 62A 44A 63A 80A 78A
3 Modules 45kVA 5 75kW 93A 66A 100A 125A 117A M8 – 50mm2 M8 – 50mm2 M8 – 50mm2 M8 – 70mm2
MPW PWC 130X

4 Modules 60kVA 124A 88A 125A 160A 156A


5 Modules 75kVA 155A 110A 160A 200A 195A
MPW PM25X (25kVA/kW)
1 Module 25kVA 49A 37A 63A 80A 66A
2 Modules 50kVA 98A 74A 100A 160A 132A
3 Modules 75kVA 5 125kW 147A 111A 160A 200A 198A M8 – 95mm2 M8 – 95mm2 M8 – 95mm2 M8 – 120mm2
4 Modules 100kVA 196A 148A 200A 315A 264A
5 Modules 125kVA 245A 185A 250A 350A 330A
MPW PM15X (15kVA/kW)
1 Module 15kVA 31A 22A 32A 50A 39A
2 Modules 30kVA 62A 44A 63A 80A 78A
4 60kW M8 – 35mm2 M8 – 35mm2 M8 – 35mm2 M8 – 50mm2
MPW CBC 100X

3 Modules 45kVA 93A 66A 100A 125A 117A


4 Modules 60kVA 124A 88A 125A 160A 156A
MPW PM25X (25kVA/kW)
1 Module 25kVA 49A 37A 63A 80A 66A
2 Modules 50kVA 98A 74A 100A 160A 132A
4 100kW M8 – 70mm2 M8 – 70mm2 M8 – 70mm2 M8 – 95mm2
3 Modules 75kVA 147A 111A 160A 200A 198A
4 Modules 100kVA 196A 148A 200A 315A 264A
MPW PM15X (15kVA/kW)
1 Module 15kVA 31A 22A 32A 50A 39A
MPW CBC 75X

2 Modules 30kVA 3 45kW 62A 44A 63A 80A 78A M8 – 35mm2 M8 – 35mm2 M8 – 35mm2 M8 – 50mm2
3 Modules 45kVA 93A 66A 100A 125A 117A
MPW PM25X (25kVA/kW)
1 Module 25kVA 49A 37A 63A 80A 66A
2 Modules 50kVA 3 75kW 98A 74A 100A 160A 132A M8 – 50mm2 M8 – 50mm2 M8 – 50mm2 M8 – 70mm2
3 Modules 75kVA 147A 111A 160A 200A 198A

9
Multipower - MPW
Electrical Data
Max Module Max Output Max AC Input Max AC Output Input Protection DC Fuse Max DC AC DC
MPW
QTY Power Current Current Rating Rating Current Input Output Bypass +N-
MPW PM42 (42kVA/kW)
1 Module 42kVA 80A 62A 100A 125A 110A
2 Modules 84kVA 160A 124A 200A 250A 220A
3 Modules 126kVA 239A 187A 250A 350A 330A
M8 M8 M8 M8
4 Modules 168kVA 7 252kW 319A 249A 350A 500A 440A
2 2 2
2 X 95mm 2 X 95mm 2 X 95mm 2 X 120mm2
5 Modules 210kVA 399A 311A 400A 600A 550A
MPW PWC 300

6 Modules 252kVA 478A 373A 500A 700A 660A


7 Modules 294kVA 558A 436A 600A 800A 770A
MPW PM25 (25kVA/kW) Discontinued
1 Module 25kVA 50A 37A 50A 80A 66A
2 Modules 50kVA 100A 74A 100A 160A 131A
3 Modules 75kVA 150A 111A 160A 200A 196A
M8 M8 M8 M8
4 Modules 100kVA 7 175kVA 200A 148A 200A 300A 261A
2 X 50mm2 2 X 50mm2 2 X 50mm2 2 X 70mm2
5 Modules 125kVA 250A 185A 250A 350A 326A
6 Modules 150kVA 300A 222A 300A 400A 392A
7 Modules 175kVA 350A 259A 350A 500A 458A
MPW PM42 (42kVA/kW)
1 Module 42kVA 80A 62A 100A 125A 110A
MPW CBC 130

2 Modules 84kVA 3 126kW 160A 124A 200A 250A 220A M8 – 95mm2 M8 – 95mm2 M8 – 95mm2 M8 – 120mm2
3 Modules 126kVA 239A 187A 250A 350A 330A
MPW PM25 (25kVA/kW) Discontinued
1 Module 25kVA 50A 37A 50A 80A 66A
2 Modules 50kVA 3 75kW 100A 74A 100A 160A 131A M8 – 50mm2 M8 – 50mm2 M8 – 50mm2 M8 – 70mm2
3 Modules 75kVA 150A 111A 160A 200A 196A

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres . These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

10
Multipower - MPW
Mechanical Data
Power Cabinet Power Cabinet Combo Cabinet Combo Cabinet Combo Cabinet
MPW PWC 130X MPW PWC 300 MPW CBC 75X MPW CBC 100X MPW CBC 130

Cabinets

15kVA – 75kVA 15kVA – 45kVA 15kVA – 60kVA


Nominal Power or 42kVA – 294kVA or or 42kVA – 126kVA
25kVA – 125kVA 25kVA – 75kVA 25kVA – 100kVA

Bypass Power 126kW 252kW 126kW 126kW 126kW

5x MPW PM15X 3x MPW PM15X +12xBU 4x MPW PM15X +24xBU


Module Capacity or 7x MPW PM42 or or 3x MPW PM42 +20xBU
5x MPW PM25X 3x MPW PM25X +12xBU 4x MPW PM25X +24xBU

Weight (Unpopulated) 145kg 300kg 190kg 350kg 340kg

Cable Input Bottom Top & Bottom Bottom Top & Bottom Top & Bottom

Noise Level (Full Load) <65dBA <68dBA <63dBA <64dBA <64dBA

Dimensions
• Width • 600mm • 600mm • 600mm • 600mm • 600mm
• Height • 1050mm • 1050mm • 1050mm • 1050mm • 1050mm
• Depth • 1200mm • 2000mm • 1600mm • 2000mm • 2000mm

11
Multipower - MPW
Mechanical Data
Power Module Power Module Bypass Module Bypass Module
Battery Module
MPW PM25/PM42 MPW PM15X/PM25X MPW BM 300 MPW BM 130

Power Components

Nominal Power 25kW / 42kW 15kW / 25kW 300kW 130kW 10 x 12V 9AH

Weight 36kg / 40kg 25kg 42kg 23kg 32kg

Ventilation Forced Forced Forced Forced Passive

Fan Flow Rate 3800m3/h 2580m3/h N/A N/A N/A

IP Class IP20

Dimensions
• Width • 448mm • 448mm • 448mm • 305mm • 109mm
• Height • 177mm • 88mm • 228mm • 202mm • 158mm
• Depth • 703mm • 703mm • 652mm • 635mm • 749mm

Multicom Multicom Multicom Multicom Multicom Multicom Multicom UGS


Netman 208 Multi Panel Multi I/O Alarm Card Synchro Kit
302 352 411 421 372 384 392 Kit

PWC 130X

12
Multipower – MP2/M2S
Technical Data

Power Power AC/AC Efficiency % DC/AC Efficiency Max Battery


Power Power
Dissipated Dissipated Recharge Battery Qty
Modules Factor
100% Load 0% Load 25% 50% 75% 100% 25%-50% 50%-80% 80%-100% Current

30 (75% nominal power)


PM 67kW 1 2.94kW TBC 96.2% 96.5% 96.2% 95.8% 95.3% 95.5% 95.3% 30A 32 (80% nominal power)
34 (85% nominal power)
36 (90% nominal power)
38 (95% nominal power)
40 (full nominal power)
PM 67kW BLUE 1 1.93kW TBC 98.1% 98.1% 97.7% 97.2% 97.3% 97.2% 96.7% 30A 42 (full nominal power)
44 (full nominal power)

Inverter Short Circuit (Ph-N)


Max Short circuit Current
Cabinet Bypass A2t ICC Ka Rating
20mS 2.5 x In for 100ms + 1.5 x In for 400ms
MP2 500 1805k 8000A 50KA
Inverter Overload
MS2 1000 12300k 18000A 100KA 103% - 125% - 10 Minutes .

M2S 1250 12300k 18000A 100KA 125% - 150% - 1 Minute

M2S 1600 24500k 18000A 100KA 150% - 180% - 0.5 seconds

Bypass Overload
100% - 110% - Continuous.

110% - 125% - 10 Minutes

125% - 150% - 60 Seconds

13
Multipower – MP2/M2S
Electrical Data
Nominal Input AC DC
Max AC Input Max AC Output DC Fuse Max DC
MP2/M2S Output Protection PE
Current Current Rating Current Input Output Bypass +N-
Power Rating

1 Module 67kVA 127A 97A TBC TBC 175A


2 Modules 134kVA 253A 193A TBC TBC 351A
MP2 500 PCM

3 Modules 201kVA 380A 290A TBC TBC 526A

4 Modules 268kVA 507A 387A TBC TBC 702A 2 x M8 2 x M8 2 x M8 2 x M8 2 x M8


500kW
5 Modules 335kVA 633A 484A TBC TBC 877A 2 X 300mm2 2 X 240mm2 2 X 240mm2 2 X 240mm2 2 X 240mm2
6 Modules 402kVA 760A 580A TBC TBC 1052A
7 Modules 469kVA 886A 677A TBC TBC 1228A
8 Modules 500kVA 945A 722A TBC TBC 1309A

9 Modules 603kVA 1139A 870A TBC TBC 1579A


10 Modules 670kVA 1266A 967A TBC TBC 1754A
M2S 1000

11 Modules 737kVA 393A 1064A TBC TBC 1929A


7 x M12 7 x M12 7 x M12 7 x M12 3 x M12
12 Modules 804kVA 1000kW 1519A 1160A TBC TBC 2105A
2 2 2 2
4 x 240mm 3 x 240mm 3 x 240mm 3 x 240mm 6 x 185mm2
13 Module 871kVA 1646A 1257A TBC TBC 2280A
14 Modules 938kVA 1772A 1354A TBC TBC 2455A
15 Modules 1000kVA 1890A 1443A TBC TBC 2618A

16 Modules 1072kVA
M2S 1250

2026A 1547A TBC TBC 2806A


17 Modules 1139kVA 2152A 1644A TBC TBC 2982A 7 x M12 7 x M12 7 x M12 7 x M12 3 x M12
1250kW
18 Modules 1206kVA 2279A 1741A TBC TBC 3157A 5 x 240mm2 4 x 240mm2 4 x 240mm2 4 x 240mm2 6 x 240mm2
19 Modules 1250kVA 2362A 1804A TBC TBC 3272A

20 Modules 1340kVA 2532A 1934A TBC TBC 3508A


M2S 1600

21 Modules 1407kVA 2658A 2031A TBC TBC 3683A


7 x M12 7 x M12 7 x M12 7 x M12 3 x M12
22 Modules 1474kVA 1600kW 2750A 2128A TBC TBC 3859A
6 x 240mm2 5 x 240mm2 5 x 240mm2 5 x 240mm2 9 x 240mm2
23 Modules 1541kVA TBC 2224A TBC TBC 4034A
24 Modules 1600kVA TBC 2309A TBC TBC 4188A

14
Multipower – MP2/M2S
Mechanical Data

MP2 500 M2S 1000 PC0 M2S 1000 PCS

Cabinets

Nominal Power 500kW 1000kW 1000kW

Bypass Power 500kW 1000kW 1000kW

8 x PM 67kW 15 x PM 67kW 15 x PM 67kW


Module Capacity or or or
8 x PM 67kW BLUE 15 x PM 67kW BLUE 15 x PM 67kW BLUE

Weight (Unpopulated) 344kg 1311kg 1661kg

Cable Input Top (Bottom optional) Top or Bottom Top or Bottom

Noise Level (Full Load) <69dBA <75dBA <75dBA

Dimensions
• Width • 600mm • 2400mm • 3000mm
• Height • 1997mm • 2000mm • 2000mm
• Depth • 870mm • 1025mm • 1025mm

15
Multipower – MP2/M2S
Mechanical Data

M2S 1250 PC0 M2S 1250 PCS

Cabinets

Nominal Power 1250kW 1250kW

Bypass Power 1250kW 1250kW

19 x PM 67kW 19 x PM 67kW
Module Capacity or or
19 x PM 67kW BLUE 19 x PM 67kW BLUE

Weight (Unpopulated) 1311kg 1661kg

Cable Input Top or Bottom Top or Bottom

Noise Level (Full Load) <75dBA <75dBA

Dimensions
• Width • 2400mm • 3000mm
• Height • 2000mm • 2000mm
• Depth • 1025mm • 1025mm

16
Multipower – MP2/M2S
Mechanical Data

M2S 1600 PC0 M2S 1600 PCS

Cabinets

Nominal Power 1600kW 1600kW

Bypass Power 1600kW 1600kW

24 x PM 67kW 24 x PM 67kW
Module Capacity or or
24 x PM 67kW BLUE 24 x PM 67kW BLUE

Weight (Unpopulated) 1577kg 1927kg

Cable Input Top or Bottom Top or Bottom

Noise Level (Full Load) <75dBA <75dBA

Dimensions
• Width • 3400mm • 4000mm
• Height • 2000mm • 2000mm
• Depth • 1025mm • 1025mm

17
Multipower – MP2/M2S
Mechanical Data
Power Module Power Module Bypass Module
PM 67kW PM 67kW BLUE MP2 500

Power Components

Nominal Power 67kVA / 67kW 67kVA / 67kW 500kW

Weight 37kg 37kg TBCkg

Ventilation Forced Forced Forced

Fan Flow Rate TBCm3/h TBCm3/h TBCm3/h

IP Class IP20

Dimensions
• Width 450mm 450mm TBCmm
• Height 135mm (3U) 135mm (3U) TBCmm
• Depth 630mm 630mm TBCmm

Multicom Multicom Multicom Multicom Multicom Multicom Multicom UGS


Netman 208 Multi Panel Multi I/O Alarm Card Synchro Kit
302 352 411 421 372 384 392 Kit

MP2/M2S

18
Multisentry – MST/MCT
Technical Data
Power AC/AC Efficiency
Inverter Short Circuit (Ph-N)
Power Auto DC/AC Bypass KA Battery DC
MST Dissipated
Factor Consumption 25% 50% 75% 100% Efficiency i2t (A2s) Rating Qty voltage
in kW MST 10 - 100 MST 125 - 200

10kVA
0.9 630W 220W 89.3% 91.8% 93.0% 93.5% 92.5% 11250 6KA 20+20 480V 2.7 x In 200ms + 1.5 x In for
9kW 1.5 x In 500ms
300ms
12kVA
0.9 750W 220W 89.8% 92.4% 93.3% 93.6% 92.5% 11250 6KA 20+20 480V
10.8kW
Inverter Overload
15kVA
0.9 860W 240W 91.6% 93.0% 93.8% 94.0% 93.5% 11250 6KA 20+20 480V
13.5kW MST 10 - 125 MST 160 - 200

20kVA >101% - ≤103% >101% - ≤103%


0.9 1.15kW 240W 91.6% 93.8% 94.0% 94.0% 93.5% 11250 6KA 20+20 480V Infinite Infinite
18kW
>103% - ≤110% >103% - ≤110%
30kVA 10 min. 60 min.
0.9 1.28kW 240W 95.0% 96.1% 96.2% 96.1% 95.3% 20000 6KA 20+20 480V
27kW
>110% - ≤133% >110% - ≤125%
40kVA 60 Sec. 10 min.
0.9 1.50kW 240W 95.7% 96.2% 96.2% 96.0% 95.3% 25000 6KA 20+20 480V
36kW >133% - ≤ 150% >125% - ≤ 150%
5 sec 60 sec
60kVA
0.9 2.92kW 455W 94.6% 95.5% 95.5% 95.4% 95.0% 25000 10KA 20+20 480V >150% - ≤ 200% >150% - ≤ 200%
54kW
0.5 sec 0.5 sec
80kVA
0.9 3.95kW 455W 94.9% 95.6% 95.6% 95.2% 95.0% 110000 10KA 20+20 480V >200% >200%
72kW 0.2 sec 0.2 sec

100kVA Bypass Overload


0.9 5.05kW 470W 95.3% 95.7% 95.5% 95.0% 95.0% 145000 10KA 20+20 480V
90kW
MST 10 - 125 MST 160 - 200
125kVA
0.9 6.03kW 580W 95.6% 96.1% 96.0% 95.6% 95.5% 145000 10KA 20+20 480V ≤110% ≤110%
112.5kW Infinite Infinite

160kVA >110% - ≤133% >110% - ≤125%


1 7.5kW 1.5kW 95.1% 95.5% 95.8% 95.4% 95.5% 432000 10KA 20+20 480V
160kW 60 min. 60 min.

>133% - ≤ 150% >125% - ≤ 150%


200kVA 10 min. 10 min
1 9.9kW 1.5kW 95.6% 96.2% 96.1% 95.8% 95.5% 432000 10KA 20+20 480V
200kW
>150% >150%
60 sec 60 sec

19
Multisentry – MST/MCT
Electrical Data
Input AC Output AC DC
Max AC Max AC Input Battery
SWBAT fuse Max UPS Max Max Max
MST Input Output Protection Recharge Typical AC Typical AC Typical DC
Rating DC current Terminal Earth / N Terminal Terminal
Current Current Rating Current Cable Size Cable Size Cable Size
Size Size Size

32A gG 16mm2 16mm2 16mm2


10kVA 20A 15A 32A
(10x38)
25A 6A Terminal 10mm2 10mm2 M6 Terminal 10mm2 Terminal 4mm2

32A gG 16mm2 16mm2 16mm2


12kVA 24A 17A 32A
(10x38)
30A 6A Terminal 10mm2 10mm2 M6 Terminal 10mm2 Terminal 6mm2

50A gG 16mm2 16mm2 16mm2


15kVA 29A 22A 32A
(14x51)
38A 6A Terminal 10mm2 16mm2 M6 Terminal 10mm2 Terminal 6mm2

50A gG 16mm2 16mm2 16mm2


20kVA 38A 29A 63A
(14x51)
51A 6A Terminal 10mm2 25mm2 M6 Terminal 10mm2 Terminal 10mm2

80A gG 35mm2 35mm2 35mm2


30kVA 54A 46A 63A
(14x51)
74A 10A Terminal 16mm2 25mm2 M6 Terminal 16mm2 Terminal 16mm2

100A gG 35mm2 35mm2 35mm2


40kVA 70A 61A 80A
(14x51)
99A 10A Terminal 25mm2 25mm2 M6 Terminal 25mm2 Terminal 25mm2

50mm2 50mm2 50mm2 50mm2


60kVA 104A 87A 125A N/A 150A 10A Terminal 50mm2
M6 / M8 Terminal 50mm2 Terminal 50mm2

95mm2 95mm2 95mm2 95mm2


80kVA 138A 116A 160A N/A 200A 10A Terminal 50mm2
M6 / M8 Terminal 50mm2 Terminal 70mm2

95mm2 95mm2 95mm2 150mm2


100kVA 172A 145A 200A N/A 250A 10A Terminal 70mm2
M6 / M8 Terminal 70mm2 Terminal 120mm2

125kVA 211A 181A 250A N/A 300A 25A M8 95mm2 M6 / M8 M8 95mm2 M8 150mm2

160kVA 316A 232A 320A N/A 456A 25A M10 150mm2 M8 / M10 M10 150mm2 M10 150mm2

200kVA 385A 290A 400A N/A 567A 25A M10 150mm2 M8 / M10 M10 150mm2 M10 240mm2

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

20
Multisentry – MSM/MCM
Technical Data

Power AC/AC Efficiency


Power UPS Auto DC/AC Bypass i2t
MSM Dissipated in KA Rating Battery Qty DC voltage
Factor Consumption 25% 50% 75% 100% Efficiency (A2s)
kW

10kVA
0.9 630W 220W 87.6% 91.7% 92.7% 93.3% 92.5% 25000 6KA 20+20 480V
9kW

12kVA
0.9 750W 220W 90.2% 92.2% 92.9% 93.5% 92.5% 25000 6KA 20+20 480V
10.8kW

15kVA
0.9 860W 240W 89.8% 92.6% 93.2% 93.8% 93.5% 25000 10KA 20+20 480V
13.5kW

20kVA
0.9 1.15kW 240W 91.0% 92.8% 93.3% 94.0% 93.5% 25000 10KA 20+20 480V
18kW

Inverter Short Circuit (Ph-N) Inverter Overload Bypass Overload

>103% - ≤110% - 10 min. ≤110% - Infinite

>110% - ≤133% - 60 Sec. >110% - ≤133% - 60 min.

1.5 x In 500ms >133% - ≤ 150% - 5 sec >133% - ≤ 150% - 10 min.

>150% - ≤ 200% - 0.5 sec >150% - 60 sec

>200% - 0.2 sec

21
Multisentry – MSM/MCM
Electrical Data

3P+N AC Input AC Output DC


1P+N
Max AC Input SWBAT Max UPS Battery
Max AC Max AC
MSM Max AC Output Protection fuse DC Recharge Min AC Min AC
Input Input L1 L2 L3 Min DC
Input Current Rating Rating current Current Cable E L1 N Cable +N -
Current Current N Cable Size
Current L1 Size Size
L2/L3

32A gG 35mm2 35mm2 16mm2


10kVA 49A 18A 55A 45A 63A 25A 6A Terminal 10mm2 10mm2 Terminal 10mm2 Terminal 4mm2
(10x38)

32A gG
35mm2 35mm2 16mm2
12kVA 59A 21A 64A 55A 80A 31A 6A Terminal 16mm2 16mm2 Terminal 16mm2 Terminal 6mm2
(10X38)

50A gG 35mm2 35mm2 16mm2


15kVA 72A 25A 76A 68A 100A 38A 6A Terminal 16mm2 16mm2 Terminal 16mm2 Terminal 6mm2
(14x51)

50A gG 35mm2 35mm2 16mm2


20kVA 95A 33A 98A 91A 125A 51A 6A Terminal 25mm2 25mm2 Terminal 25mm2 Terminal 10mm2
(14x51)

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres . These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

22
Multisentry
Mechanical Data
Compact MCM / MCT MST/MSM 10-40 MST 60-125 MST 160-200

10 12 15 20 10 12 15 20 30 40 60 80 100 125 160 200


Weight (Unpopulated) 80kg 82kg 90kg 95kg 105kg 110kg 115kg 120kg 135kg 145kg
190kg 200kg 220kg 250kg 450kg 460kg
Weight (Populated) 185kg 187kg 195kg 200kg 315kg 320kg 325kg 330kg 345kg 355kg

Fan Flow Rate 300m3/h 545m3/h 510m3/h 626m3/h 510m3/h 2100m3/h 3500m3/h

Cable Entry Bottom - Rear Bottom - Front Bottom - Front Top & Bottom - Rear

Noise Level (Full Load) <55dBA <55dBA <50dBA <63dBA <68dBA <70dBA

IP Rating IP20
• Width • 320mm • 440mm • 500mm • 780mm • 600mm
• Height • 930mm • 1320mm • 1600mm • 1745mm • 1050mm
• Depth • 840mm • 850mm • 850mm • 945mm • 2000mm

Netman Multicom Multicom Multicom Multicom Multicom Multicom Multicom Multi Alarm Synchro UGS
Multi I/O
208 302 352 411 421 372 384 392 Panel Card Kit Kit

MST/MSM

23
CSS – C1M / C1T
Technical Data

Power AC/AC Efficiency Short Battery


Power DC/AC Bypass KA Battery Inverter Overload
CSS Dissipated Circuit DC voltage Recharge
Factor 25% 50% 75% 100% Efficiency i2t (A2s) Rating Qty
in kW Current Current >103% - ≤120%
Infinite
C1M6
0.9 470W 87.6% 91.7% 92.7% 93.3% 92.5% 2.5 x In 25000 6KA 20+20 480V 6A >120% - ≤132%
5400W 10 min.

C1M10 >132% - ≤160%


0.9 630W 90.2% 92.2% 92.9% 93.5% 92.5% 1.8 x In 25000 6KA 20+20 480V 6A 60 Sec.
9000W
>160% - ≤ 180%
C1M15 5 sec
0.9 860W 91.0% 92.8% 93.3% 94.0% 93.5% 2 x In 25000 10KA 20+20 480V 6A
13500W
>180%
0.5 sec
C1T10
0.9 630W 89.3% 91.8% 93.0% 93.5% 92.5% 1.8 x In 11250 6KA 20+20 480V 6A
9000W Bypass Overload

C1T15 ≤110%
0.9 860W 89.8% 92.4% 93.3% 93.6% 93.5% 2 x In 11250 6KA 20+20 480V 6A Infinite
13.5kW
>110% - ≤133%
C1T20 60 min.
0.9 1.15kW 91.6% 93.0% 93.8% 94.0% 95.0% 2.25 x In 20000 6KA 20+20 480V 10A
18kW
>133% - ≤ 150%
10 min.
C1T30
0.9 1.28kW 95.7% 96.2% 96.2% 96.0% 95.0% 2 x In 25000 6KA 20+20 480V 10A
27kW >150%
60 sec
C1T40
0.9 1.50kW 94.6% 95.5% 95.5% 95.4% 95.0% 2.25 x In 25000 6KA 20+20 480V 10A
36kW

C1T60
0.9 2.61kW 94.9% 95.6% 95.6% 95.2% 95.0% 2 x In 110000 10KA 20+20 480V 20A
54kW

C1T80
0.9 3.65kW 95.3% 95.7% 95.5% 95.0% 95.0% 1.85 x In 145000 10KA 20+20 480V 20A
72kW

C1T100
0.9 4.25kW 95.6% 96.1% 96.0% 95.6% 95.5% 1.8 x In 145000 10KA 20+20 480V 25A
90kW

24
CSS – C1M / C1T
Electrical Data
AC Input AC Output DC
Max AC Input Max AC Input Max AC Output Input Protection SWBAT fuse Max UPS DC
CSS Minimum DC Cable
Current L1 Current L2 / L3 Current Rating Rating current L1 L2 L3 N E L1 N +N-
size

1P-63A 35mm2 35mm2 35mm2 16mm2


C1M6 49A 16A 26A 32A gG (10x38) 15A Terminal Terminal Terminal Terminal 4mm2
3P-16A

1P-100A 35mm2 35mm2 35mm2 16mm2


C1M10 69A 23A 43A 32A gG (10x38) 25A Terminal Terminal Terminal Terminal 6mm2
3P-32A

1P-125A 35mm2 35mm2 35mm2 16mm2


C1M15 96A 32A 65A 50A gG (14x51) 38A Terminal Terminal Terminal Terminal 10mm2
3P-40A

Max AC Input Max AC Output DC


Max AC Input Max AC Output Input Protection SWBAT fuse Max UPS DC
CSS
Current Current Rating Rating current Minimum DC Cable
L1 / L2 / L3 E L1 / L2 / L3 +N -
Size

16mm2 16mm2 16mm2 16mm2


C1T10 23A 15A 32A 32A gG (10x38) 25A Terminal Terminal Terminal Terminal 6mm2

16mm2 16mm2 16mm2 16mm2


C1T15 32A 22A 40A 50A gG (14x51) 38A Terminal Terminal Terminal Terminal 10mm2

50mm2 50mm2 50mm2 50mm2


C1T20 43A 29A 63A 80A gG (22x58) 51A Terminal Terminal Terminal Terminal 16mm2

50mm2 50mm2 50mm2 50mm2


C1T30 60A 43A 80A 100A gG (22x58) 74A Terminal Terminal Terminal Terminal 25mm2

50mm2 50mm2 50mm2 50mm2


C1T40 77A 58A 125A 100A gG (14x51) 70A Terminal Terminal Terminal Terminal 25mm2

95mm2 95mm2 95mm2 95mm2


C1T60 121A 87A 160A N/A 150A Terminal Terminal Terminal Terminal 35mm2

95mm2 95mm2 95mm2 150mm2


C1T80 155A 116A 200A N/A 200A Terminal Terminal Terminal Terminal 50mm2

C1T100 197A 152A 250A N/A 254A M8 M8 M8 M8 70mm2

25
CSS – C1M / C1T
Mechanical Data
CSS C1M/T 6-30 CSS C1T 40-80 CSS C1T 100

6 10 15 20 30 40 60 80 100
Weight (Unpopulated) 107kg 112kg 122kg 135kg 145kg 190kg 200kg 220kg 250kg
Fan Flow Rate 510m3/h 2100m3/h
Cable Entry Bottom - Front Bottom - Front Bottom - Front
IP Rating IP20
Noise Level (Full Load) <50dBA <63dBA
Dimensions
• 440mm • 500mm • 650mm
• Width
• 1320mm • 1600mm • 1600mm
• Height
• Depth • 850mm • 850mm • 830mm

UGS
Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O Alarm Card Synchro Kit
Kit

CSS

26
CSS – CBM / CBT
Technical Data

Power AC/AC Efficiency Short Battery


Power DC/AC Bypass KA Battery Inverter Overload
CBM CBT Dissipated Circuit DC voltage Recharge
Factor 25% 50% 75% 100% Efficiency i2t (A2s) Rating Qty
in kW Current Current >103% - ≤110%
60Min
CBM 6
1 250W 93.0% 94.87% 95.8% 95.95% 95.9% 20000 6KA 20+20 480V 6A >110% - ≤125%
6kW 10 min.

CBM 8 >125% - ≤150%


1 330W 93.8% 95.39% 95.89% 95.90% 95.9% 20000 6KA 20+20 480V 8A 60 Sec.
6kW
>150% - ≤ 200%
CBM 10 0.5 sec
1 440W 94.62% 95.81% 96.0% 95.83% 95.9% 20000 6KA 20+20 480V 9A
8kW
>200%
0.2 sec
CBM 15
1 620W 94.95% 96.13% 96.29% 96.06% 95.9% 35000 10KA 20+20 480V 15A Inverter Overload capacity
12kW
referred to power
according to EN 50171
CBM 20 2.7 x In for
1 890W 95.67% 96.19% 96.05% 95.75% 95.9% 35000 10KA 20+20 480V 15A
16kW 200ms

+ 120% - Infinite
CBT 10
1 410W 94.3% 95.6% 96.0% 96.1% 95.9% 11250 6KA 20+20 480V 12A
8kW
1.5 x In for
300ms Bypass Overload
CBT 15
1 590W 95.2% 96.2% 96.3% 96.2% 96.4% 11250 6KA 20+20 480V 20A
12kW
≤110%
Infinite
CBT20
1 840W 95.6% 96.2% 96.3% 95.9% 96.4% 11250 6KA 20+20 480V 20A >110% - ≤125%
16kW
60 min.

CBT 30 >125% - ≤ 150%


1 1.21kW 96.0% 96.4% 96.3% 96.1% 96.5% 20000 10KA 20+20 480V 30A
24kW 10 min.

>150 - ≤ 200%
60 sec
CBT40
1 1.61kW 95.2% 96.6% 96.3% 96.1% 96.5% 20000 10KA 20+20 480V 30A
32kW >200%
0.2 sec

27
CSS – CBM / CBT
Electrical Data
AC Input AC Output DC
Max AC Input Max AC Input Max AC Output Input Protection SWBAT fuse Max UPS DC
CBM Minimum DC Cable
Current L1 Current L2 / L3 Current Rating Rating current L1 L2 L3 N E L1 N +N-
size
1P - 63A Type C
16mm2 16mm2 10mm2
CBM 6 43A 14A 29A 32A gR (10x38) 16.5A Terminal M6 Terminal Terminal 6mm2
3P - 20A Type C

1P - 80A Type C
16mm2 16mm2 10mm2
CBM 8 53A 17.5A 38A 32A gR (10x38) 22A Terminal M6 Terminal Terminal 6mm2
3P - 25A Type C

1P - 80A Type C
16mm2 16mm2 10mm2
CBM 10 63A 21A 48A 32A gR (14x51) 27.5A Terminal M6 Terminal Terminal 6mm2
3P - 40A Type C

1P - 100A Type C
35mm2 35mm2 16mm2
CBM15 94.5A 31.5A 72A 50A gR (14x51) 41A Terminal M6 Terminal Terminal 10mm2
3P - 50A Type D

1P - 125A Type C
35mm2 35mm2 16mm2
CBM 20 120A 40A 96A 50A gR (14x51) 55A Terminal M6 Terminal Terminal 16mm2
3P – 50A Type D

AC Input AC Output DC
Max AC Input Max AC Output Input Protection SWBAT fuse Max UPS DC
CBT
Current Current Rating Rating current Minimum DC Cable
L1 / L2 / L3 E L1 / L2 / L3 +N -
Size

10mm2 10mm2 10mm2


CBT 10 21A 14.5A 40A Type C 32A gR (10x38) 27.5A Terminal M6 Terminal Terminal 6mm2

16mm2 16mm2 16mm2


CBT 15 31.5A 22A 50A Type D 50A gR (14x51) 41A Terminal M6 Terminal Terminal 10mm2

16mm2 16mm2 16mm2


CBT 20 40A 29A 50A Type D 50A gR (14x51) 55A Terminal M6 Terminal Terminal 16mm2

35mm2 35mm2 35mm2


CBT 30 63A 43.5A 80A Type C 80A gR (22x58) 82A Terminal M6 Terminal Terminal 16mm2

35mm2 35mm2 35mm2


CBT 40 80A 58A 100A Type C 100A gR (22x58) 110A Terminal M6 Terminal Terminal 16mm2

RCD Protection Please Note!


Differential current adjusted to the sum of CSS + Load; we The typical DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with a
recommend keeping a suitable margin to prevent nuisance tripping maximum length of 10 metres . These cable sizes are guidance only and the correct cable cross sectional area will be dependent
• 100mA min. - 300mA recommended on the installation and should be verified by the electrical installer or design engineer. Single PE connections must have a cable
• Type B section of at least 10mm2
• Delay of at least 0.1s Typical Cable size is per pole.

28
CSS – CBM / CBT
Mechanical Data
CSS CBM / CBT

CBM 6 CBM 8 CBM 10 CBM 15 CBM 20 CBT 10 CBT 15 CBT 20 CBT 30 CBT 40

Weight (Populated) 102kg 102kg 103kg 105kg 107kg 112kg 105kg 107kg 112kg 116kg

Fan Flow Rate 860m3/h

Cable Entry Bottom - Front

Noise Level (Full Load) <52dBA <56dBA <50dBA <52dBA <56dBA


• Width • 440mm
• Height • 1320mm
• Depth
• 840mm

Multicom Multicom Multicom Multicom Multicom Multicom Multicom UGS


Netman 208 Multi Panel Multi I/O Alarm Card Synchro Kit
302 352 411 421 372 384 392 Kit

CSS

29
CSS – CAM

Efficiency
UPS AC
I2t Max AC Max AC Max DC Max DC
Input / Power Terminals Input Battery DC SWBATT DC Expansion
CAM UPS Auto Max Input Output Charge Discharge
Output ECO Dissipated AC/AC Input / Breaker Qty Voltage Fuse Rating Connection
Consumption DC/AC A2S Current Current Current Current
Mode 100% 100% Output
(W)
Load

CAM 3 1P+N/ 20A


36W 67W 170W 94.60% 92.45% 6115 15A 11A 10mm2 15 180V 6A 18A 80A aR
2500W 1P+N B/C
XCONU001A
CAM 5 1P+N/ 32A
36W 67W 290W 94.35% 92.55% 6115 25A 18A 10mm2 15 180V 6A 30A 80A aR
4000W 1P+N B/C

Inverter Overload CAM CAM 3 CAM 5


<103% - Infinite
Weight 24kg 25kg
>103% - ≤110% - 10 min.
Fan Flow Rate 500m3/h
>110% - ≤133% - 60 Sec.
Cable Entry Bottom Rear
>133% - ≤ 150% - 5 sec
Noise Level (Full Load) 48dBA
>150% - 0.5 sec IP Protection IP20
Bypass Overload • Width 250mm
≤110% - Infinite • Height 500mm
• Depth 698mm
>110% - ≤130% - 60 min.

>130% - ≤ 150% - 10 min.

>150% - 3 sec

Inverter overload capacity referred to power


according to EN 50171 (@ 40 °C)
RCD Protection
Differential current adjusted to the sum of CSS + Load; we
<120% - Infinite recommend keeping a suitable margin to prevent nuisance tripping
• Only a RCD Type B is allowed.

30
Nextenergy – NXE
Technical Data
AC/AC Efficiency
2 Power Power
Bypass i t DC/AC Battery DC Max Recharge
NXE Power Factor KA Rating Dissipated Dissipated 25% 100%
(A2s) 50% Load 75% Load Efficiency Qty voltage Current
100% Load 0% Load Load Load

250kVA
1 10KA 86 12.1kW 1.25 kW 96.10% 96.30% 96.00% 95.40% 96.00% 160A
250kW

300kVA
1 50KA 180 13.5kW 1.5 kW 96.00% 96.60% 96.40% 95.70% 96.00% 225A
300kW

400kVA
1 50KA 180 18kW 1.80 kW 96.00% 96.50% 96.20% 95.70% 96.00% 300A
400kW
40 480V
500kVA
1 40KA 290 23.6kW 2.1kW 96.20% 96.50% 96.00% 95.50% 96.00% 280A
500kW

600kVA
1 100KA 370 27kW 2.9kW 96.20% 96.40% 96.20% 95.70% 96.00% 440A
600kW

800kVA
1 65KA 370 35.9kW 4.0kW 96.00% 96.50% 96.10% 95.70% 96.00% 500A
800kW

Current Overload capacity (x rated current)


Inverter Overload Inverter Short Circuit Current (I/Irated)
kVA 250 300 400 500 600 800 Bypass Overload

1 Sec 10 10 7.5 9 7 5.5 250/500 300/400/600/800 250/500 300/400/600/800

500 ms 12 12 9 10 7.5 6.5 110% 110% 110%


60 Minutes 60 Minutes 2.5x per 100ms 2.7x per 100ms 60 Minutes
200 ms 13 13 9.5 11 8 7
125% 125% 125%
2 Minutes 10 Minutes 10 Minutes
100 ms 14 14 10.5 12 9.5 7.5

150% 125% 2x per 900ms 2x per 900ms 150 %


10 ms 15 15 11.5 13 11 8.5 20 Seconds 1 Minutes 60 Seconds

31
Nextenergy – NXE
Electrical Data
AC -Input AC-Output DC
Max AC Max AC Input Max UPS
L1 / L2 / L3 N/E L1 / L2 / L3 N/E +/-
NXE Input Output Protection DC
Current Current Rating current Min Cable Min Cable Min Cable Min Cable
Type Type Type Type Type Min Cable size
size size size size

250kVA 400A 361A 400A 595A 2 x 70mm2 2 x 70mm2 2 x 70mm2 2 x 70mm2 2 x 95mm2

300 kVA 500A 433A 500A 710A 2 x 95mm2 2 x 95mm2 2 x 95mm2 2 x 95mm2 2 x 120mm2

400 kVA 681A 577A 800A 945A M10 2 x 150mm2 M10 2 x 150mm2 M10 2 x 150mm2 M10 2 x 150mm2 M10 2 x 150mm2

500 kVA 844A 722A 1000A 1250A 3 x 185mm2 2 x 185mm2 2 x 185mm2 2 x 185mm2 3 x 150mm2

600kVA 1000A 866A 1000A 1500A 3 x 185mm2 3 x 185mm2 3 x 185mm2 3 x 185mm2 3 x 185mm2

800kVA 1360A 1155A 1400A 1850A M12 3 x 240mm2 M12 3 x 240mm2 M12 3 x 240mm2 M12 3 x 240mm2 M12 3 x 240mm2

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

32
Nextenergy – NXE
Mechanical Data

NXE 250 NXE 300 NXE 400 NXE 500

Weight 634kg 880kg 1100kg 1300kg

Fan Flow Rate 5500m3/h 9500m3/h

Cable Entry Bottom (TCE Available)

Noise Level (Full Load) <70dBA <73dBA

IP Rating IP20 (Higher levels of protection available upon request)


• Width • 800mm • 800mm • 800mm • 800mm
• Height
• 1900mm • 1900mm • 1900mm • 1900mm
• Depth
• 850mm • 850mm • 850mm • 850mm

33
Nextenergy – NXE
Mechanical Data

NXE 600 NXE 800 NXE 800 SB

Weight 1600kg 1800kg 1985kg

Fan Flow Rate 300m3/h 12000m3/h 12000m3/h

Cable Entry Bottom (TCE Available)

Noise Level
<73dBA <74dBA <74dBA
(Full Load)
IP Rating IP20 (Higher levels of protection available upon request)
• Width 2100mm 2100mm 2400mm
• Height 1900mm 1900mm 1900mm
• Depth 850mm 850mm 850mm

UGS
Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O Alarm Card Synchro Kit
Kit

NXE

34
Masterplus - MHT
Technical Data
AC/AC Efficiency
Power Power
Power Bypass i2t DC/AC Battery Max DC Recharge
MHT KA Rating Dissipated Dissipated 0% 25% 50% 75% 100% DC voltage
Factor (A2s) Efficiency Qty Current
100% Load Load
Load Load Load Load

100kVA
0.9 10KA 20K 6.8kW 1.7kW 92% 93.5% 93.5% 93% 94.00% 70A
90kW

120kVA
0.9 10KA 145K 8.1kW 1.8kW 92% 93.5% 93.5% 93% 94.00% 85A
108kW

160kVA
0.9 10KA 145K 10.8kW 2.1kW 93% 94% 94% 93% 94.00% 110A
144kW

200kVA
0.9 10KA 405K 13.5kW 2.2kW 93% 94% 94% 93% 94.00% 130A
180kW

250kVA
0.9 10KA 405K 16.9kW 2.6kW 93% 94% 94% 93% 94.00% 40 480V 165A
225kW

300kVA
0.9 40KA 1805K 20.3kW 3.7kW 93% 94% 94% 93% 94.00% 200A
270kW

400kVA
0.9 40KA 1805K 27.1kW 4.5kW 93% 94% 94% 93% 94.00% 260A
360kW

500kVA
0.9 50KA 1805K 30.3kW 6.2kW 93% 94.3% 94.3% 93.7% 94.00% 330A
450kW

600kVA
0.9 50KA 1805K 36.3kW 7.0kW 93% 94.3% 94.3% 93.7% 94.00% 390A
540kW

Short Circuit Capacity of Bypass Line (x nominal Voltage) I/in Inverter Overload Inverter Overload
kVA 100 120 160 200 250 300 400 500 600
110% 60 Minutes Phase / Phase
1 Sec 4.5 10 7.5 9.5 7.5 12 9 7 12
125% 10 Minutes 180% for 1 Second
500 ms 5 11 8 10.5 8.5 13 10 8 14
200 ms 6 13 9.5 12.5 10 15 11 9 16 150 % 60 Seconds Phase / Neutral
100 ms 6.5 14 10.5 13.5 10.5 17 13 10 18
200% 6 Seconds 300% for 1 Second
10 ms 9.5 20 15 19.5 15.5 25 18 15 25

35
Masterplus - MHT
Electrical Data
AC -Input AC-Output DC
Max AC Max AC Input Max UPS
MHT Input Output Protection DC L1 / L2 / L3 N/E L1 / L2 / L3 N/E +/-
Current Current Rating current
Type Min Cable size Type Min Cable size Type Min Cable size Type Min Cable size Type Min Cable size

100kVA 159A 144A 160A 200A 1 x 50mm2 1 x 50mm2 1 x 50mm2 1 x 50mm2 1 x 95mm2

120 kVA 190A 173A 200A 240A 1 x 70mm2 1 x 70mm2 1 x 70mm2 1 x 70mm2 1 x 95mm2

160 kVA 250A 231A 250A 320A 1 x 95mm2 1 x 95mm2 1 x 95mm2 1 x 95mm2 1 x 95mm2

200 kVA 317A 289A 350A 400A 1 x 95mm2 1 x 95mm2 1 x 95mm2 1 x 95mm2 1 x 120mm2

M10 M10 M10 M10 M10


250kVA 397A 361A 400A 495A 1 x 120mm2 1 x 120mm2 1 x 120mm2 1 x 120mm2 2 x 70mm2

300 kVA 476A 433A 500A 675A 1 x 185mm2 1 x 185mm2 1 x 150mm2 1 x 150mm2 2 x 95mm2

400 kVA 635A 577A 700A 900A 2 x 120mm2 2 x 120mm2 2 x 120mm2 2 x 120mm2 2 x 150mm2

500 kVA 794A 722A 800A 1150A 2 x 120mm2 2 x 120mm2 2 x 120mm2 2 x 120mm2 2 x 240mm2

600 kVA 953A 866A 1000A 1300A 2 x 185mm2 2 x 185mm2 2 x 185mm2 2 x 185mm2 2 x 240mm2

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres . These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

36
Masterplus - MHT
Mechanical Data

MHT100 - 120 MHT 160-250 MHT 300-400 MHT 500-600

100 120 160 200 250 300 400 500 600


Weight 730kg 785kg 865kg 1000kg 1095kg 1550kg 1720kg 2500kg 2700kg

Fan Flow Rate 1700m3/h 1700m3/h 3500m3/h 8100m3/h 9800m3/h

Cable Entry Bottom (TCE Available)

Noise Level (Full Load) 65dBA 65dBA 68dBA 68dBA 68dBA 72dBA 72dBA 72dBA 72dBA

IP Rating IP20 ( Other levels of protection are available upon request)

• Width • 800mm • 1000mm • 1500mm • 2100mm


• Height • 1900mm • 1900mm • 1900mm • 1900mm
• Depth • 850mm • 850mm • 850mm • 1000mm

Multicom Multicom Multicom Multicom Multicom Multicom Multicom UGS


Netman 208 Multi Panel Multi I/O Alarm Card Synchro Kit
302 352 411 421 372 384 392 Kit

MHT

37
Masterplus - MHE
Technical Data
AC/AC Efficiency
Power Power
Power Bypass i2t DC/AC Battery Max DC Recharge
MHE KA Rating Dissipated Dissipated 0% 25% 50% 75% 100% DC voltage
Factor (A2s) Efficiency Qty Current
100% Load Load Load Load Load Load

100kVA
1 10KA 145K 5.2kW 1.5kW 92.5% 94.8% 95.2% 95.1% 95.0% 66A
100kW

120kVA
1 10KA 145K 7.0kW 1.5kW 93.5% 95.2% 95.2% 94.5% 95.0% 80A
120kW

160kVA
1 10KA 405K 8.1kW 2.1kW 94% 95.3% 95.5% 95.2% 95.0% 105A
160kW

200kVA
1 10KA 405K 11.6kW 2.1kW 94.5% 95.5% 95.3% 94.5% 95.0% 130A
200kW
250kVA
1 10KA 405K 14.6kW 2.5kW 94.5% 95.5% 95.3% 94.5% 95.0% 130A
250kW
40 480V
300kVA
1 40KA 1805K 17.5kW 3.7kW 94.5% 95.5% 95.3% 94.5% 95.0% 200A
300kW

400kVA
1 40KA 1805K 23.3kW 4.5kW 94.5% 95.5% 95.3% 94.5% 95.0% 260A
400kW

500kVA
1 50KA 1805K 29.1kW 6.2kW 94.0% 95.1% 95.1% 94.5% 95.0% 330A
500kW

600kVA
1 50KA 6485K 34.9kW 7.0kW 94.0% 95.1% 95.1% 94.5% 95.0% 390A
600kW
800kVA
1 50KA 6485K 46.6kW 8.5kW 94.0% 95.1% 95.1% 94.5% 95.0% 520A
600kW

Short Circuit Capacity of Bypass Line (x nominal Voltage) I/in Inverter Overload Inverter Overload
kVA 100 120 160 200 250 300 400 500 600 800
110% 60 Minutes Phase / Phase
1 Sec 12 10 12 9.5 7.5 12 9 7 12 9
500 ms 13 11 13 10.5 8.5 13 10 8 14 10 125% 10 Minutes 180% for 1 Second

200 ms 15 13 15 12.5 10 15 11 9 16 12 150 % 60 Seconds


Phase / Neutral
100 ms 17 14 17 13.5 10.5 17 13 10 18 13 300% for 1 Second
200% 6 Seconds
10 ms 24 20 24 19.5 15.5 25 18 15 25 18

38
Masterplus - MHE
Electrical Data
AC -Input AC-Output DC
Max AC Max AC Input Max UPS
L1 / L2 / L3 N/E L1 / L2 / L3 N/E +/-
MHE Input Output Protection DC
Current Current Rating current Min Cable Min Cable
Type Min Cable size Type Type Min Cable size Type Type Min Cable size
size size

100 kVA 170A 144A 200A 250A 1 x 70mm2 1 x 70mm2 1 x 70mm2 1 x 70mm2 1 x 70mm2

120 kVA 204A 173A 250A 300A 1 x 95mm2 1 x 95mm2 1 x 95mm2 1 x 95mm2 1 x 95mm2

160 kVA 273A 231A 315A 400A 2 x 50mm2 2 x 50mm2 2 x 50mm2 2 x 50mm2 1 x 120mm2

200 kVA 341A 289A 400A 495A 2 x 70mm2 2 x 70mm2 2 x 70mm2 2 x 70mm2 1 x 150mm2

250kVA 426A 361A 500A 620A M10 2 x 95mm2 M10 2 x 95mm2 M10 2 x 95mm2 M10 2 x 95mm2 M10 2 x 95mm2

300 kVA 511A 433A 630A 750A 2 x 150mm2 2 x 150mm2 2 x 150mm2 2 x 150mm2 2 x 120mm2

400 kVA 681A 578A 800A 1000A 2 x 185mm2 2 x 185mm2 2 x 185mm2 2 x 185mm2 2 x 185mm2

500 kVA 852A 722A 1000A 1250A 3 x 185mm2 2 x 185mm2 2 x 185mm2 2 x 185mm2 3 x 150mm2

600 kVA 1000A 867A 1000A 1500A 3 x 185mm2 3 x 185mm2 3 x 185mm2 3 x 185mm2 3 x 185mm2

800 kVA 1363A 1155A 1400A 1850A M12 3 x 240mm2 M12 3 x 240mm2 M12 3 x 240mm2 M12 3 x 240mm2 M12 3 x 240mm2

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

39
Masterplus - MHE
Mechanical Data
MHE100 - 120 MHE 160-250 MHE 300-400 MHE 500-600

100 120 160 200 250 300 400 500 600

Weight 850kg 900kg 1015kg 1070kg 1300kg 1680kg 2020kg 2790kg 3031kg

Fan Flow Rate 1700m3/h 1700m3/h 3500m3/h 8100m3/h 9800m3/h

Cable Entry Bottom (TCE Available)

Noise Level (Full Load) 65dBA 65dBA 68dBA 68dBA 68dBA 72dBA 72dBA 72dBA 72dBA

IP Rating IP20 ( Other levels of protection are available upon request)


• Width 800mm 1000mm 1500mm 2100mm
• Height 1900mm 1900mm 1900mm 1900mm
• Depth 850mm 850mm 1000mm 1000mm

UGS
Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O Alarm Card Synchro Kit
Kit

MHE

40
Masterplus - MHE
Mechanical Data

MHE 800

800

Weight 3950kg

Fan Flow Rate 15500m3/h

Cable Entry Bottom

Noise Level (Full Load) 75dBA

IP Rating IP20 (Higher protection levels available upon request)

• Width 3200mm
• Height 1900mm
• Depth 1000mm

41
Masterplus - MPM
Technical Data

Power AC/AC Efficiency


Power Bypass i2t Auto DC/AC Battery DC Max Recharge
MPM KA Rating Dissipated
Factor (A2s) Consumption 25% 50% 75% 100% Efficiency Qty voltage Current
100% Load
Load Load Load Load

10kVA
0.9 10KA 11 780W 220W 89.0% 91.5% 91.5% 92.0% 95.00% 15A
9kW

15kVA
0.9 10KA 11 1.17kW 320W 89.0% 91.5% 91.5% 92.0% 95.00% 18A
13.5kW

20kVA
0.9 10KA 11 1.56kW 430W 89.0% 91.5% 91.5% 92.0% 95.00% 29A
18kW

30kVA
0.9 10KA 20 2.35kW 650W 92.0% 92.0% 92.0% 92.0% 95.00% 37A
27kW
32 384V
40kVA
0.9 10KA 20 3.13kW 860W 89.0% 92.0% 92.0% 92.0% 95.00% 37A
36kW

60kVA
0.9 10KA 405 4.70kW 1290W 89.0% 92.0% 92.0% 92.0% 95.00% 75A
54kW

80kVA
0.9 10KA 405 5.84kW 1720W 89.0% 92.0% 92.0% 92.5% 95.00% 75A
72kW

100kVA
0.9 10KA 1805 7.30kW 2150W 89.0% 92.0% 92.0% 92.5% 95.00% 110A
90kW

Short Circuit Capacity of Bypass Line (x nominal Voltage) I/in Inverter Overload Short Circuit Current

kVA 10 15 20 30 40 60 80 100 110% for 60 Minutes


1 Sec 12 8 6 5 4 8 9 15
125% for 10 Minutes 300% for 1 Second
100 ms 16 10 8 8 6 11 14 21

10 ms 24 16 12 10 8 16 20 31 150% for 1 Minute

42
Masterplus - MPM
Electrical Data
AC DC

Max AC Max AC Input L1 L2/L3 N/E +/-


Max AC Input Max UPS
MPM Input Output Protection
Current L2/L3 DC current
Current L1 Current Rating Min Cable Min Cable Min Cable Min Cable
Type Type Type Type
size size size size

10kVA 25mm2 25mm2 25mm2 25mm2


43A 22A 43A 50A 25A Terminal 6mm2 Terminal 6mm2 Terminal 6mm2 Terminal 10mm2
9kW

15kVA 50mm2 50mm2 25mm2 25mm2


65A 34A 65A 80A 38A Terminal 10mm2 Terminal 10mm2 Terminal 10mm2 Terminal 10mm2
13.5kW

20kVA 50mm2 50mm2 25mm2 25mm2


87A 45A 87A 100A 50A Terminal 16mm2 Terminal 16mm2 Terminal 16mm2 Terminal 10mm2
18kW

30kVA 50mm2 50mm2 50mm2 50mm2


130A 65A 130A 160A 80A Terminal 50mm2 Terminal 50mm2 Terminal 50mm2 Terminal 25mm2
27kW

40kVA 70mm2 50mm2 70mm2 70mm2


174A 87A 174A 200A 109A Terminal 70mm2 Terminal 70mm2 Terminal 70mm2 Terminal 35mm2
36kW

60kVA 70mm2 70mm2 2x 16mm2 70mm2


260A 131A 260A 315A 168A Terminal 2 x 35mm2 Terminal 2 x 35mm2 70mm2
54kW 35mm2 Terminal Terminal

80kVA 70mm2 70mm2 2x 70mm2 95mm2


348A 175A 348A 400A 225A Terminal 2 x 70mm2 Terminal 2 x 70mm2 95mm2
72kW 70mm2 Terminal Terminal

100kVA 95mm2 95mm2 2x 95mm2 120mm2


435A 218A 435A 500A 294A Terminal 2 x 35mm2 Terminal 2 x 95mm2 120mm2
90kW 95mm2 Terminal Terminal

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

43
Masterplus - MPM
Mechanical Data
MPM 10-40 MPM 60-80 MPM 100

10 15 20 30 40 60 80

Weight 200kg 220kg 230kg 290kg 340kg 440kg 520kg 650kg

Fan Flow Rate 320m3/h 480m3/h 640m3/h 640m3/h 960m3/h 2000m3/h 2000m3/h 2600m3/h

Cable Entry Bottom (TCE Available)

Noise Level (Full Load) 60dBA 62dBA 63dBA


IP Rating IP20
• Width 555mm 800mm 800mm
• Height 1400mm 1400mm 1900mm
• Depth 740mm 740mm 800mm

UGS
Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O Alarm Card Synchro Kit
Kit

MPM

44
Masterplus - MPT
Technical Data
AC/AC Efficiency
Power
Power KA Bypass i2t Auto DC/AC Battery DC Max Recharge
MPT Dissipated
Factor Rating (A2s) Consumption Efficiency Qty voltage Current
100% Load 25% Load 50% Load 75% Load 100% Load

10kVA
0.9 10KA 11K 780W 220W 80.0% 87.0% 89.0% 90.5% 94.0% 15A
9kW
15kVA
0.9 10KA 11K 1.17kW 320W 80.0% 87.0% 89.0% 90.5% 94.0% 18A
13.5kW
20kVA
0.9 10KA 11K 1.56kW 430W 81.0% 88.0% 90.0% 91.0% 94.0% 29A
18kW
30kVA
0.9 10KA 11K 2.35kW 650W 86.0% 91.0% 92.0% 92.0% 94.0% 37A
27kW
40kVA
0.9 10KA 11K 3.13kW 860W 86.5% 91.0% 92.0% 92.0% 94.0% 37A
36kW
60kVA
0.9 10KA 20K 4.70kW 1290W 86.5% 92.0% 92.0% 92.0% 94.0% 32 384V 75A
54kW
80kVA
0.9 10KA 20K 5.84kW 1720W 86.5% 92.0% 92.0% 92.0% 94.0% 75A
72kW
100kVA
0.9 10KA 145K 7.30kW 2150W 92.0% 93.0% 93.0% 92.5% 95.0% 80A
90kW
120kVA
0.9 10KA 145K 8.8kW 2160W 92.0% 9.0% 93.0% 92.5% 95.0% 95A
108kW
160kVA
0.9 10KA 145K 10.8kW 2880W 93.0% 93.5% 93.5% 93.0% 95.0% 125A
144kW

200kVA
0.9 10KA 405K 13.5kW 3600W 93.0% 93.5% 93.5% 93.0% 95.0% 155A
180kW

Short Circuit Capacity of Bypass Line (x nominal Voltage) I/in Inverter Overload Short Circuit Current
kVA 10 15 20 30 40 60 80 100 120 160 200
110% for 60 Minutes Phase / Phase
1 Sec 7 4.6 3.5 5 7 7 7.5 12 10 7.5 9.5
180% for 1 Second
500 ms - - - - - - - 13 11 8 10.5
125% for 10 Minutes
200 ms - - - - - - - 14 13 9.5 12.5
Phase / Neutral
100 ms 8 5 4 7 9 9 9 16 14 10.5 13.5 300% for 1 Second
150% for 1 Minute
10 ms 12 8 6 8 12 12 14 22 20 15 19.5

45
Masterplus - MPT
Electrical Data
AC DC
Max AC Input Max AC Output Input Protection Max UPS DC L1 / L2 / L3 N E +/-
MPT
Current Current Rating current
Type Min Cable size Type Min Cable size Type Min Cable size Type Min Cable size

10kVA 22A 14.5A 32A 25A 6mm2 6mm2 6mm2 6mm2

15kVA 34A 22A 63A 38A 25mm2 10mm2 25mm2 10mm2 25mm2 10mm2 25mm2 10mm2
Terminal Terminal Terminal Terminal

20kVA 45A 29A 63A 50A 10mm2 10mm2 10mm2 10mm2

30kVA 65A 43A 80A 80A 16mm2 16mm2 16mm2 16mm2

40kVA 87A 59A 100A 109A 50mm2 25mm2 50mm2 25mm2 50mm2 25mm2 50mm2 25mm2
Terminal Terminal Terminal Terminal

60kVA 131A 87A 160A 168A 50mm2 50mm2 50mm2 70mm2


M8 M8 M8 M8
80kVA 175A 116A 200A 225A 70mm2 70mm2 70mm2 95mm2

100kVA 220A 145A 250A 294A 70mm2 70mm2 70mm2 120mm2

120kVA 262A 174A 315A 327A 95mm2 95mm2 95mm2 2 x70mm2


M12 M12 M10 M12
160kVA 348A 232A 400A 436A 2 x 70mm2 2 x 70mm2 2 x 70mm2 2 x 95mm2

200kVA 436A 290A 450A 540A 2 x 70mm2 2 x 70mm2 2 x 70mm2 2 x 120mm2

Please Note!
The typical AC & DC Cable sizes above are for general guidance only based on 90°C cable at an ambient temperature of 90°C with
a maximum length of 10 metres. These cable sizes are guidance only and the correct cable cross sectional area will be dependent
on the installation and should be verified by the electrical installer or design engineer.
Typical Cable size is per pole.

46
Masterplus - MPT
Mechanical Data
MPT 10-40 MPT 60-80 MPT 100 – 200

10 20 30 40 60 80 100 120 160 200


Weight 200kg 220kg 315kg 335kg 460kg 520kg 620kg 650kg 730kg 830kg
Fan Flow Rate 320m3/h 480m3/h 640m3/h 640m3/h 2000m3/h 2600m3/h 3700m3/h
Cable Entry Bottom (TCE available)
Noise Level (Full Load) <60dBA <62dBA <65dBA <68dBA
IP Rating IP20
• Width 555mm 800mm 800mm
• Height 1400mm 1400mm 1900mm
• Depth 740mm 740mm 800mm

Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O Alarm Card Synchro Kit UGS Kit

MPT

47
Sentinel Dual
SDU (High Power)
Efficiency UPS AC
Maximum Maximum Max DC Max DC SWBATT
Input / Power Terminals Input Battery DC DC Expansion
SDU UPS Auto Power AC/AC AC Input AC Output Charge Discharge Fuse
Output Factor ECO DC/AC Input / Breaker Qty Voltage Connection
Consumption Dissipated Efficiency Current Current Current Current Rating
Mode Efficiency Output
(W) 100% Load 100%
4000 1P+N/ 25A
0.9 36W 67W 290W 94.24% 91.38% 23.6A 16A 4mm2 8 x 9Ah 96V 0.8A 49A 50A gR
3600W 1P+N B/C
5000 1P+N/ 40A 15 x
1 36W 67W 290W 94.65% 92.60% 30A 22A 6mm2 180V 0.8A 36A 50A gR
5000W 1P+N B/C 5Ah
6000 1P+N/ 40A 15 x
1 36W 67W 350W 94.50% 92.60% 36A 27A 6mm2 180V 0.8A 42A 50A gR
6000W 1P+N B/C 5Ah
6000ER 1P+N/ 40A
1 36W 67W 350W 94.50% 92.60% 36A 27A 6mm2 0 180V 6A 42A 50A gR
6000W 1P+N B/C

XCONU001A
8000 1P+N/ 63A 20 x
1 26W 84W 420W 95.00% 93.60% 49A 36A 16mm2 240V 0.8A 42A 50A gR
8000W 1P+N B/C 7Ah
10000 1P+N/ 63A 20 x
1 26W 84W 560W 95.20% 93.30% 60A 45A 16mm2 240V 0.8A 52A 50A gR
10000W 1P+N B/C 9Ah
10000
1P+N/ 63A 20 x
ER/DI 1 26W 84W 560W 95.20% 93.30% 60A 45A 16mm2 240V 6A 52A 50A gR
1P+N B/C 9Ah
10000W
8000TM 3P+N/ 63A 20 x
1 26W 84W 420W 95.00% 93.60% 49A / 16.5 36A 16mm2 240V 1A 42A 50A gR
8000W 1P+N B/C 7Ah

10000 TM 3P+N/ 63A 20 x


1 26W 84W 560W 95.20% 93.30% 60A / 20.2 45A 16mm2 240V 1A 52A 50A gR
10000W 1P+N B/C 9Ah

Overload: Bypass line available: Activates the bypass after 10 minutes - Continues to run on Bypass
100% < 110% Bypass line not available: Shutdown after 10 Minutes
Overload: Bypass line available: Activates the bypass after 60 seconds - Shutdown after 60 Min
110% < 133% Bypass line not available: Shutdown after 60 Seconds
Overload: Bypass line available: Activates the bypass after 5 seconds - Shutdown after 10 Min
133% < 150% Bypass line not available: Shutdown after 5 Seconds
Overload Bypass line available: Activates the bypass instantly Shutdown after 3 seconds if load>150% Shutdown after 2s if load >200%
load > 150% Bypass line not available: Shutdown after 0.5 seconds
Inverter short-circuit
Icc = 2.5 In for 200ms + 1.5In x 300ms (Where In = Power(VA)/220V)
(No Bypass Available)

48
Sentinel Dual
SDU (High Power)
SDU

Model 4000 5000 6000/6000ER 8000 8000 TM 10000 10000ER 10000TM 10000 TM ER

Weight 40kg 45kg 46kg 20kg 19kg + 53kg 19kg+52kg 20kg + 62kg 21kg 20kg + 62kg 21kg

Noise Level (Full Load) <48dBA <50dBA

IP Rating IP20

• Width 131mm 131mm 131mm 131mm 131mm 131mm 131mm 131mm 131mm
• Height 448mm 448mm 448mm 448mm x2 448mm x2 448mm x2 448mm 448mm x2 448mm
• Depth 640mm 640mm 640mm 640mm 640mm 640mm 640mm 640mm 640mm

Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O

SDU

49
Sentinel Tower
STW
Efficiency
UPS AC
Max AC Max AC Max DC Max DC DC
Input / Power Power I2t Terminals Input Battery DC SWBATT Fuse
STW UPS Auto Input Output Charge Discharge Expansion
Output Factor ECO Dissipated AC/AC Max Input / Breaker Qty Voltage Rating
Consumption DC/AC Current Current Current Current Connection
Mode 100% 100% Output
(W)
Load

5000 1P+N/ 4325 40A 15 x


1 36W 67W 290W 94.65% 92.60% 30A 22A 6mm2 180V 0.8A 35A 50A gR
5000W 1P+N A2S B/C 7Ah

6000 1P+N/ 4325 40A 15 x


1 36W 67W 350W 94.50% 92.60% 36A 27A 6mm2 180V 0.8A 42A 50A gR
6000W 1P+N A2S B/C 7Ah

3P or
8000 11250 49A 63A 20 x

XCONU001A
1P+N/ 1 26W 84W 420W 95.00% 93.60% 36A 16mm2 240V 0.8A 42A 50A gR
8000W A2S 16.5A B/C 7Ah
1P+N
3P or
10000 11250 60A 63A 20 x
1P+N/ 1 26W 84W 560W 95.20% 93.30% 45A 16mm2 240V 0.8A 42A 50A gR
10000W A2S 20.2A B/C 9Ah
1P+N

6000 ER 1P+N/ 4325 40A


1 36W 67W 350W 94.50% 92.60% 36A 27A 6mm2 - 180V 6A 27A 50A gR
6000W 1P+N A2S B/C

3P or
10000 ER 11250 63A
1P+N/ 1 26W 84W 560W 95.20% 93.30% 60A 45A 16mm2 - 240V 6A 52A 50A gR
10000W A2S B/C
1P+N

Overload: Bypass line available: Activates the bypass after 10 minutes - Continues to run on Bypass
100% < 110% Bypass line not available: Shutdown after 10 Minutes
Overload: Bypass line available: Activates the bypass after 60 seconds - Shutdown after 60 Min
110% < 133% Bypass line not available: Shutdown after 60 Seconds
Overload: Bypass line available: Activates the bypass after 5 seconds - Shutdown after 10 Min
133% < 150% Bypass line not available: Shutdown after 5 Seconds
Overload Bypass line available: Activates the bypass instantly Shutdown after 3 seconds if load>150% Shutdown after 2s if load >200%
load > 150% Bypass line not available: Shutdown after 0.5 seconds
Inverter short-circuit
Icc = 2.5 In for 200ms + 1.5In x 300ms (Where In = Power(VA)/220V)
(No Bypass Available)

50
Sentinel Tower
STW
Sentinel Tower

Model 5000 6000 6000ER 8000 10000 10000ER

Weight 62kg 63kg 25kg 78kg 84kg 28kg

Noise Level (Full Load) <48dBA <50dBA

IP Rating IP20

• Width 250mm
• Height 500mm
• Depth 698mm

Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O

STW

51
Sentinel Dual
SDH (Low Power)
Efficiency
UPS AC
Max AC Max AC Max DC Max SWBATT DC
Input / Power Terminals Input Battery DC
SDH UPS Auto Power AC/AC Input Output Charge DC Fuse Expansion
Output Factor ECO DC/AC Input / Breaker Qty Voltage
Consumption Dissipated Efficiency Current Current Current Current Rating Connection
Mode Efficiency Output
(W) 100% Load 100%

10A
1000 1P+N/ 32A
0.9 19.0W 49.2W 100W 89.00% 85.00% 5A 4A IEC 10A TYPE 3 x 7Ah 36V 1A 34.6A
900w 1P+N (GL)
B/C
10A
1500 1P+N/ 32A
0.9 17.1W 48.6W 130W 90.50% 86.20% 7A 6A IEC 10A TYPE 3 x 9Ah 36V 1A 51A
1350W 1P+N (GL)
B/C
16A
2200 1P+N/ IEC 16A/ 32A
0.9 24.3W 59.3W 164W 91.70% 86.40% 10.5A 9A TYPE 6 x 7Ah 72V 1A 37.4A
1980W 1P+N IEC 10A (GL)
B/C XCONU001
16A A
3000 1P+N/ IEC 16A/ 32A
0.9 28.0W 58.5W 200W 92.65% 86.60% 14A 13A TYPE 6 x 9Ah 72V 1A 51A
2700w 1P+N IEC 10A (GL)
B/C
16A
2200 ER 1P+N/ IEC 16A/ 50A
0.9 24.3W 59.3W 164W 91.70% 86.40% 11.5A 9A TYPE 0 72V* 1A 33.2A
1760W 1P+N IEC 10A (14X51)
B/C
16A
3000 ER 1P+N/ IEC 16A/ 50A
0.9 28.0W 58.5W 200W 92.65% 86.60% 15A 13A TYPE 0 72V* 1A 45.3A
2400W 1P+N IEC 10A (14X51)
B/C

Bypass line available: Activates the bypass after 2 seconds - locks after 120 seconds 1000 1500 2200 2200ER 3000 3000ER
Overload:
100% < 110% Weight 29.5kg 14.5kg 31.5kg 15kg
Bypass line not available: Locks after 60 seconds 17kg 18kg

Noise Level (Full Load) <40dBA


Bypass line available: Activates the bypass after 2 second - locks after 4 seconds
Overload:
IP Rating IP20
110% < 150% Bypass line not available: Locks after 4 seconds
• Width 87mm 87mm
Bypass line available: Activates the bypass instantly locks after 1 second • Height 450mm 450mm
Overload load
• Depth 425mm 625mm
> 150%
Bypass line not available: Locks after 0.5 second

Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O
Please Note! Fitting an additional battery
SDH box will down rate the UPS output power
factor to 0.8

52
Sentinel Pro
SEP
Efficiency Maximum UPS AC
Maximum Max DC Max DC SWBATT DC
Input / Power UPS Auto Power AC/AC AC Terminals Input Battery DC
SEP ECO DC/AC AC Input Charge Discharge Fuse Expansion
Output Factor Consumption Dissipated Efficiency Output Input / Breaker Qty Voltage
Mode Efficiency Current Current Current Rating Connection
(W) 100% Load 100% Current Output
700VA 1P+N/ 10A
0.9 10.5W 42W 80W 88.40% 86.30% 4A 3A IEC 10A 2 x 7Ah 24V 1A 36A -
630W 1P+N B/C
1000VA 1P+N/ 10A
0.9 10.5W 29W 107W 89.20% 88.00% 5A 4A IEC 10A 3 x 7Ah 36V 1A 33A -
900W 1P+N B/C
1500VA 1P+N/ 10A
0.9 10.5W 38W 121W 91.70% 88.30% 7A 6.5A IEC 10A 3 x 9Ah 36V 1A 50A -
1350W 1P+N B/C
2200VA 1P+N/ IEC 16A/ 16A

XCONU001A
0.9 12W 44W 161W 92.40% 90.00% 11A 9.5A 6 x 7Ah 72V 1A 36A -
1980W 1P+N IEC 10A B/C
3000VA 1P+N/ IEC 16A/ 16A
0.9 12W 58W 202W 93.20% 90.40% 14A 13A 6 x 9Ah 72V 1A 49A -
2700W 1P+N IEC 10A B/C
1000ER 1P+N/ 10A
0.9 10.5W 29W 107W 89.20% 88.00% 6A 4A IEC 10A 0 36V 6A 33A 50A
900W 1P+N B/C
2200ER 1P+N/ IEC 16A/ 16A
0.9 12W 44W 161W 92.40% 90.00% 12A 9.5A 0 72V 6A 36A 50A
1980W 1P+N IEC 10A B/C
IEC 16A/
3000ER 1P+N/ 16A
0.9 12W 58W 202W 93.20% 90.40% 16A 13A IEC 0 72V 6A 49A 50A
2700w 1P+N B/C
10+16A

Bypass line available: Activates the bypass after 2 seconds - locks after 120 seconds 700 1000 1000ER 1500 2200 2200ER 3000 3000ER
Overload:
100% < 110% Bypass line not
Locks after 60 seconds Weight 11kg 13kg 7kg 14kg 26kg 14kg 28kg 15kg
available:
Bypass line available: Activates the bypass after 2 second - locks after 4 seconds Noise Level (Full Load) <40dBA
Overload:
110% < 150% Bypass line not
Locks after 4 seconds IP Rating IP20
available:

Bypass line available: Activates the bypass instantly locks after 1 second • Width 158mm 190mm
Overload load >
150% • Height 235mm 333mm
Bypass line not
Locks after 0.5 second • Depth 422mm 446mm
available:

Netman 208 Multicom 302 Multicom 352 Multicom 411 Multicom 421 Multicom 372 Multicom 384 Multicom 392 Multi Panel Multi I/O

SEP

53
Sentinel Rack
SER

Efficiency
Maximum UPS AC
Maximum Max DC Max DC SWBATT
Input / Power AC Terminals Input Battery DC DC Expansion
SER UPS Auto Power AC/AC AC Input Charge Discharge Fuse
Output Factor ECO DC/AC Output Input / Breaker Qty Voltage Connection
Consumption Dissipated Efficiency Current Current Current Rating
Mode Efficiency Current Output
(W) 100% Load 100%

1500VA 1P+N/ 10A


0.9 10.5W 29W 121W 91.70% 88.40% 7A 6.5A IEC 10A 3 x 9Ah 36V 1A 50A -
1350W 1P+N B/C
IEC 16A/ XCONU001A
3000ER 1P+N/ 16A
0.9 12W 44W 202W 93.10% 90.50% 15.5A 13A IEC 0 72V 6A 49A 50A
2700w 1P+N B/C
10A+16A

Bypass line available: Activates the bypass after 2 seconds - locks after 120 seconds
Overload:
100% < 110%
Bypass line not available: Locks after 60 seconds

Bypass line available: Activates the bypass after 2 second - locks after 4 seconds
Overload:
110% < 150%
Bypass line not available: Locks after 4 seconds

Bypass line available: Activates the bypass instantly locks after 1 second
Overload load >
150%
Bypass line not available: Locks after 0.5 second

54
Vision Tower / Rack / Dual
VST VSR VSD
Efficiency
UPS AC
Maximum Maximum Max DC Max DC SWBATT
Input / Power Terminals Input Battery DC DC Expansion
VSD UPS Auto Power AC/AC AC Input AC Output Charge Discharge Fuse
Output Factor DC/AC Input / Breaker Qty Voltage Connection
Consumption Dissipated Efficiency Current Current Current Current Rating
Efficiency Output
(W) 100% Load 100%

10A
1100 1P+N/
0.9 35W 26W 97.40% 84.00% 5.3A 4.8A IEC 10A Type 3 36V 1A 35A -
990W 1P+N
B/C
10A
1500 1P+N/
0.9 49W 37W 97.20% 88.00% 7.2A 6.5A IEC 10A Type 3 36V 1A 50A -
1350W 1P+N
B/C
IEC 16A / 16A
2200 1P+N/

XCONU001A
0.9 60W 53W 97.30% 88.70% 10.6A 9.5A IEC Type 6 72V 1A 36A 50A
1980W 1P+N
16A/10A B/C
IEC 16A / 16A
3000 1P+N/
0.9 92W 78W 97.10% 91.10% 14.2A 13A IEC Type 6 72V 1A 49A 50A
2700W 1P+N
16A/10A B/C
IEC 16A / 16A
2200ER 1P+N/
0.8 68W 53W 95.50% 88.70% 12.1A 8A IEC Type 0 72V 6A 32A 50A
1760W 1P+N
16A/10A B/C
IEC 16A / 16A
3000ER 1P+N/
0.8 92W 78W 95.60% 91.10% 15.8A 11A IEC Type 0 72V 6A 43A 50A
2400W 1P+N
16A/10A B/C

Efficiency
UPS AC
Maximum Maximum AC Max DC Max DC
Input / Power UPS Auto Power AC/AC Terminals Input Battery
VST / VSR DC/AC AC Input Output DC Voltage Charge Discharge
Output Factor Consumption Dissipated Efficiency Input / Breaker Qty
Efficiency Current Current Current Current
(W) 100% Load 100% Output

800 1P+N/ 10A VST 2 / VST 24V / VST 36A /


0.8 32.5W 18w 97.00% 87.00% 3.9A 2.8A IEC 10A 1A
640W 1P+N TYPE C VSR 4 VSR 48V VSR 18A
1100 1P+N/ 10A VST 2 / VST 24V / VST 49A /
0.8 31.5W 26W 97.00% 88.00% 5.3A 3.8A IEC 10A 1A
880W 1P+N TYPE C VSR 4 VSR 48V VSR 25A
1500 1P+N/ 10A
0.8 27W 37W 97.00% 89.00% 7.4A 5.2A IEC 10A 4 48V 1A 33A
1200W 1P+N TYPE C
2000 1P+N/ 16A
0.8 19W 53W 97.00% 88.00% 9.7A 7A IEC 10A 4 48V 1A 45A
1600W 1P+N TYPE C

55
Power Cable
Part Numbers

Cable Size Part Number

H07 - Single Core

25mm2 2809

35mm2 2444

50mm2 2794

70mm2 1865
2
95mm 3171 Crimp Lug Riello Part Number Crimp Lug Part Number
2
120mm 2623

150mm2 1832 10mm² x M6 77187 50mm² x M6 71818

185mm2 1859 10mm² x M8 1305 50mm² x M8 72599

H07 - Multicore 10mm² x M10 2581 50mm² x M10 2372

10mm² x M12 2231 70mm² x M6 71819


4mm2 (3-core) 4178
16mm² x M6 2377 70mm² x M8 77901
4mm2 (5-core) 4044
16mm² x M8 72597 70mm² x M10 2640
6mm2 (4-core) 4040
16mm² x M10 2243 70mm² x M12 1879
10mm2 (4-core) 4041
25mm² x M6 71322 95mm² x M6 1866
16mm2 (4-core) 4042
25mm² x M8 1848 95mm² x M8 1867
PVC 3 Core
25mm² x M10 1430 95mm² x M10 1678
1.5mm (15A) BLACK 98426
25mm² x M12 90406 95mm² x M12 2572
1.5mm (15A) WHITE 93955
35mm² x M6 71817 120mm² x M8 3685
2.5mm (20A) BLACK 1435
35mm² x M8 72598 120mm² x M10 3435
2.5mm (20A) WHITE 79193
35mm² x M10 2197 120mm² x M12 3264
4.0mm (32A) BLACK 1769 35mm² x M12 3359 120mm² x M16 3265

56
Power Connector
Part Numbers

Connector Type Part Number Connector Type Part Number

Commando 16A PLUG 230V 76142


UK PLUG 10AMP (BS1363) 1152

Commando 32A PLUG 230V 1497


UK PLUG 13AMP (BS1363) 1151

Commando 16A SOCKET 230V 1752

IEC 10A PLUG (C14) 98293


Commando 32A SOCKET 230V 1498

Commando 63A PLUG 400V (3P) 2525

IEC 10A SOCKET (C13) 1141

Commando 63A SOCKET 400V (3P) 2527

IEC 16A PLUG (C20) 1162

Connector Type Part Number

DC Connector SDL <6K 0611010693

DC Connector SDL >6K 0CBCU0325E


IEC 16A SOCKET (C19) 1163
DC Connector
XCONU001A
SDH/SDU/STW/SEP/SPH/VST/VSD

57
Cable Assembly
Part Numbers

Connector Type Part Number Connector Type Part Number

10A IEC PLUG to 10A IEC SOCKET 2M 3379 13A UK PLUG to 10A IEC SOCKET 2M 79963

10A IEC PLUG to 13A UK SOCKET 2M 2584 13A UK PLUG to 16A IEC SOCKET 2M 1359

16A Commando PLUG to 16A IEC SOCKET


10A IEC PLUG to 16A IEC SOCKET 2M 3595 3378
2M

16A Commando SOCKET to 16A IEC PLUG


3309
16A IEC PLUG to 10A IEC SOCKET 2M 3594 2M

16A IEC PLUG to 16A IEC SOCKET 2.5M 1490

58