Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Application Guide Volume IV AG2000-04

Applying the SEL-352 Relay


for Automatic Throw-Over Control
of a Bus Tie and Incoming Circuit Breakers
Shaojun Chen and Scott Anderson

INTRODUCTION
The SEL-352 Relay is an extremely flexible device. Two voltage source inputs and enhanced
SELOGIC® control equations allow the SEL-352 Relay to implement throw-over control functions
in addition to its pre-designed tasks. Automatic throw-over control of a bus tie and incoming
circuit breakers reduces the time that load is disconnected from a power source after a power
system disturbance. This application guide describes how to use the SEL-352 Relay to
automatically restore power to either 110 kV bus tie sections or 10 kV double bus sections as
shown in Figure 1, in the event that the respective source is removed.

Line 1 Line 2

PT1 PT2

352

CB 1 CB 2
CB 3
110 kV 110 kV

T1 T2

CB 4 CB 5

10 kV Bus 1 CB 6 10 kV Bus 2

PT3 PT4

352

DWG: AG2000.04.001

Figure 1: SEL-352 Placement for Automatic Throw-Over Control

SCHWEITZER ENGINEERING LABORATORIES


2350 NE Hopkins Court $ Pullman, WA $ 99163-5603 $ USA
Phone: (509) 332-1890 $ Fax: (509) 332-7990
E-mail: info@selinc.com $ Internet: www.selinc.com
In the 110 kV section of Figure 1, the SEL-352 Relay opens or closes circuit breakers CB1 and
CB2 to provide consistent power to as many as two 110/10 kV transformers connected to an
alternate power source. In the 10 kV bus section of Figure 1, when either of two 10 kV buses is
deenergized, the SEL-352 Relay detects a live bus and closes the bus-tie Breaker 6 (CB6) to
quickly restore power to the bus. The restoration schemes use line potential transformer inputs to
distinguish dead line or live line for 110 kV incoming feeders and use 10 kV bus potential
transformer inputs to specify which 10 kV bus is dead.
We present four cases based on the pre-disturbance bus arrangement and the desired
post-disturbance arrangement. Undervoltage elements, overcurrent elements, programmable
SELOGIC control equations, and intermediate timers provide a fast and orderly restoration of load.

THROW-OVER CONTROL CASE:


The automatic throw-over logic described here assumes the following:
• All outgoing loads connected to 10 kV buses are radially connected.
• Circuit breakers CB1, CB2, CB3, CB4, CB5, and CB6 have fault current interruption
capability.
• Both 110 kV incoming lines have sufficient capacity to serve both 10 kV Buses 1 and 2
simultaneously.
• External inputs (bus protection trip inputs in particular) are externally latched.
Throw-over control is provided for the following cases:
• Throw-over Control Case 1: Breaker 1 and Breaker 3 normally are closed. When Breaker
1 is removed from service, Breaker 2 automatically is closed to provide an alternate source
for both distribution transformers.
• Throw-over Control Case 2: Breaker 2 and Breaker 3 normally are closed. When Breaker
2 is removed from service, Breaker 1 automatically is closed to provide an alternate source
for both distribution transformers.
• Throw-over Control Case 3: Breaker 4 and Breaker 5 normally are closed. When Breaker
4 is removed from service, Breaker 6 automatically is closed to provide an alternate source
for Bus Section 1.
• Throw-over Control Case 4: Breaker 4 and Breaker 5 normally are closed. When Breaker
5 is removed from service, Breaker 6 automatically is closed to provide an alternate source
for Bus Section 2.
Table 1, Table 2, Table 3, and Table 4 summarize the desired breaker operations for faults on the
various sections.

Table 1: Throw-Over Control Case 1

Faulted Line Section Breaker 1 Breaker 2 Breaker 3


Line 1 (pre-fault) close open close
Line 1 (post-fault) open close close

2 SEL Application Guide 2000-04 Date Code 20000616


Table 2: Throw-Over Control Case 2

Faulted Line Section Breaker 1 Breaker 2 Breaker 3


Line 2 (pre-fault) open close close
Line 2 (post-fault) close open close

Table 3: Throw-Over Control Case 3

Faulted Line Section Breaker 4 Breaker 5 Breaker 6


Transformer 1 (pre-fault) close close open
Transformer 1 (post-fault) open close close

Table 4: Throw-Over Control Case 4

Faulted Line Section Breaker 4 Breaker 5 Breaker 6


Transformer 2 (pre-fault) close close open
Transformer 2 (post-fault) close open close

AC/DC CONNECTIONS:

110 kV section:
Connect the inputs VAX, VBX, and VCX of the SEL-352 Relay to the A-phase, B-phase, and
C-phase of the Line 1 potential transformer (PT1) and the inputs VAY, VBY, and VCY to the
A-phase, B-phase, and C-phase of the Line 2 potential transformer (PT2), as shown in Figure 1.
Connect the inputs IA, IB, and IC of the relay to the current transformer (CT) associated with
either Circuit Breaker 1 for Case 1 or Circuit Breaker 2 for Case 2.
OUT102 through OUT104 of the SEL-352 Relay are asserted to close Circuit Breakers 1
through 3, and OUT105 through OUT107 are asserted to trip Circuit Breakers 1 through 3,
respectively. A summary of general closing and tripping settings for bus-tie breakers CB1, CB2,
and CB3 follows:
SBLOG = CUSTOM
Relay inputs:
52AA = IN101 (Circuit Breaker 1 status, B contact)
52AB = IN102 (Circuit Breaker 2 status, B contact)
52AC = IN103 (Circuit Breaker 3 status, B contact)
Relay outputs:
OUT102 = CCA (close Circuit Breaker 1)
OUT103 = CCB (close Circuit Breaker 2)
OUT104 = CCC (close Circuit Breaker 3)

Date Code 20000616 SEL Application Guide 2000-04 3


OUT105 = RTA (trip Circuit Breaker 1)
OUT106 = RTB (trip Circuit Breaker 2)
OUT107 = RTC (trip Circuit Breaker 3)

10 kV section:
Connect the inputs VAX, VBX, and VCX of the SEL-352 Relay to the A-phase, B-phase and
C-phase of the Bus 1 potential transformer (PT3) and the inputs VAY, VBY, and VCY to the
A-phase, B-phase, and C-phase of the Bus 2 potential transformer (PT4), as shown in Figure 1.
Connect the inputs IA, IB, and IC of the relay to the current transformer (CT) associated with
bus-tie CB6.
OUT102 through OUT104 of the SEL-352 Relay are asserted to close Circuit Breakers 4 through
6, and OUT105 through OUT107 are asserted to trip Circuit Breakers 4 through 6, respectively.
A summary of general closing and tripping settings for breakers CB4, CB5, and CB6 follows:
SALOG = CUSTOM
SBLOG = CUSTOM
Relay inputs:
52AA = IN101 (Circuit Breaker 4 status, b contact)
52AB = IN102 (Circuit Breaker 5 status, b contact)
52AC = IN103 (Circuit Breaker 6 status, b contact)
Relay outputs:
OUT102 = CCA (close Circuit Breaker 4)
OUT103 = CCB (close Circuit Breaker 5)
OUT104 = CCC (close Circuit Breaker 6)
OUT105 = RTA (trip Circuit Breaker 4)
OUT106 = RTB (trip Circuit Breaker 5)
OUT107 = RTC (trip Circuit Breaker 6)

THROW-OVER CONTROL CASE 1: AUTOMATIC CONTROL OF CIRCUIT BREAKER 2


Use SELOGIC control equations to program the SEL-352 Relay to effect the automatic throw-
over. Timer T2A is set once the pre-fault condition (see Table 1) is true for the timer pickup
time. T2B supervises external trip inputs and CB2 status. Conditions for the throw-over
initiation are the collapse of Line 1 voltage and the disappearance of load current. Should these
conditions persist for longer than the T3A time setting, CB1 is tripped via T3B followed by the
closing of CB2 via T3C.

4 SEL Application Guide 2000-04 Date Code 20000616


T2A
52AA T3B
52AB 500
52AA 5
52AC RTA CB1
X59L3 500 3
Y59L3

T3A
X27D3 100
Y59L3
50LD 30

T2B T3C
IN105 5 10
52AB CCB CB2
0 52AA 3

DWG: AG2000.04.002

Figure 2: Throw-Over Control Case 1 Logic for Closing CB2

SELOGIC control equations:


X27D3 = dead line voltage on Line 1
X59L3 = live line voltage on Line 1
Y27D3 = dead line voltage on Line 2 (not used)
Y59L3 = live line voltage on Line 2
T2A = !52AA*52AB*!52AC*X59L3*Y59L3 (Breakers 1 and 3 closed, Breaker 2
opened)
T2B = IN105 + !52AB + T3C (block throw-over)
where:
IN105 = external blocking input
50LD = load current of Line 1
T3A = T2AD*(X27D3 *Y59L3)*!50LD*!T2BD (Line 1 dead following Case 1
operation condition, no blocking)
T3B = T3AD*!52AA (set longer than the longest auto-reclose dead time)
RTA = T3BD (trip Circuit Breaker 1 after T3Apu delay)
T3C = T3AD*52AA
CCB = T3CD (close Circuit Breaker 2 right after CB1 opens)
If voltage on the incoming Line 1 is restored before CB2 closes, X27D3 deasserts thus aborting
the closing of CB2. If the voltage collapse is due to a permanent fault on Line 1, the Line 1
protection trips CB1 and the SEL-352 Relay closes CB2. Tripping of CB1 is reinforced via T3B
to ensure that CB2 is not energized onto a permanent fault.

Date Code 20000616 SEL Application Guide 2000-04 5


Throw-Over Case 1 RTA CB1
Fault on Line 1
Condition Trip

T2Apu T3Apu

Trip

Time

Close

CCB CB2
X27D3*Y59L3*!50LD
Close
DWG: AG2000.04.003

Figure 3: Timing Diagram for Throw-Over Control Case 1

THROW-OVER CONTROL CASE 2: AUTOMATIC CONTROL OF CIRCUIT BREAKER 1


Figure 4 shows the logic for tripping CB2 and closing CB1. Should Line 2 lose its voltage, CB2
trips sequentially via the SEL-352 Relay. CB1 then automatically closes after a T3Cpu time
delay. If voltage returns to Line 2 before CB1 closes, the logic aborts the closing of CB1.
T2A T3B
52AA
52AB 500 5
52AB
52AC RTB CB2
X59L3 3
500
Y59L3

T3A
X59L3 100
Y27D3
50LD 30

T2B
T3C
IN105 5
10
52AA
CCA CB1
0 52AB 3

DWG: AG2000.04.004

Figure 4: Throw-Over Control Case 2 Logic for Closing CB1

SELOGIC control equations:


X27D3 = dead line voltage on Line 1 (not used)
X59L3 = live line voltage on Line 1
Y27D3 = dead line voltage on Line 2
Y59L3 = live line voltage on Line 2

6 SEL Application Guide 2000-04 Date Code 20000616


T2A = 52AA*!52AB*!52AC*X59L3*Y59L3 (Breakers 2 and 3 closed, Breaker 1
opened)
T2B = IN105 + !52AA + T3C (block tripping)
where:
IN105 = external block input
50LD = load current of Line 2
T3A = T2AD*(Y27D3*X59L3)*!50LD*!T2BD (Line 2 dead following Case 2
operation condition, no blocking)
T3B = T3AD*!52AB
RTB = T3BD (trip Circuit Breaker 2 after T3Bpu delay)
T3C = T3AD*52AB
CCA = T3CD (close Circuit Breaker 1 after T3Cpu delay and after CB2 opens)
If voltage on the incoming Line 2 is restored before CB1 closes, Y27L3 deasserts thus aborting
the closing of CB1. If the voltage collapse is due to a permanent fault on Line 2, the Line 2
protection trips CB2 and the SEL-352 Relay closes CB1. Tripping of CB2 is reinforced via T3B
to ensure that CB1 is not energized onto a permanent fault.
Throw-Over Case 2 RTB CB2
Fault on Line 2
Condition Trip

T2Apu T3Apu

Trip

Time

Close

CCA CB1
Y27D3*X59L3*!50LD
Close
DWG: AG2000.04.005

Figure 5: Throw-Over Control Case 2 Logic for Closing CB1

THROW-OVER CONTROL CASE 3 AND 4: AUTOMATIC CONTROL OF CIRCUIT


BREAKER 6
Figure 6 shows the logic for tripping either CB4 or CB5 and then closing CB6. When the Throw-
over Case 3 and 4 condition exists for T2Apu (e.g., 10 seconds), the automatic throw-over control
of CB6 is enabled. Should the Bus 1 lose its bus voltage because of internal faults on
Transformer 1, CB4 trips sequentially after a T3Apu time delay via the SEL-352 Relay. CB6
closes automatically after CB4 opens.
Date Code 20000616 SEL Application Guide 2000-04 7
T3C
52AB 5 RTB CB5
3
T2A T3B
52AA
52AB 500 5
52AC 52AA RTA CB4
X59L3 500 3
Y59L3 T3A
X27D3 100
Y59L3 3

T2C
Y27D3 100
X59L3 3

IN105
52AC T2B 52AA T1A
5 10 CCC CB6
X59L3
Y59L3 3
0
50LD
52AB

DWG: AG2000.04.006

Figure 6: Throw-Over Control Case 3 and 4 Logic for Closing CB6

Close CB6 for loss of voltage on Bus 1 but for full voltage on Bus 2. Set the T3Apu time delay
greater than the tripping time of CB4. This ensures that CB4 has time to open before the relay
attempts to close CB6.
SELOGIC control equations:
X27D3 = dead bus voltage on Bus 1
X59L3 = live bus voltage on Bus 1
Y27D3 = dead bus voltage on Bus 2
Y59L3 = live bus voltage on Bus 2
T2A = !52AA*!52AB*52AC*X59L3*Y59L3 (Breakers 4 and 5 closed, Breaker 6
opened)
T2B = IN105 + !52AC + (X59L3*Y59L3) + T1A +50LD
T2C = T2AD*(Y27D3*X59L3)*!T2BD
T3A = T2AD*(X27D3*Y59L3)*!T2BD
T3B = T3AD*!52AA
T3C = T2CD*!52AB
T1A = (T3AD*52AA) + (T2CD*52AB)
RTA = T3BD (trip Circuit Breaker 4)
RTB = T3CD (trip Circuit Breaker 5)
CCC = T1AD (close Circuit Breaker 6)
IN105 = Throw-over block (87T and all other external protection)

8 SEL Application Guide 2000-04 Date Code 20000616


If a permanent fault occurs on Transformer 1 (T1), the transformer protection of T1 trips CB4.
Close CB6 after verifying that Bus 1 loses its source to restore power on Bus 1. If a permanent
fault occurs on Transformer 2 (T2), Breaker 5 trips, and the above throw-over control logic closes
CB6 to restore power to Bus 2.
Throw-Over Case 3 RTA CB4
Fault on XFMR 1
Condition Trip

T2Apu T3Apu

Trip

Time

Close

CCC CB6
X27D3*Y59L3*!T2BD
Close
DWG: AG2000.04.007

Figure 7: Timing Diagram for Throw-Over Control Case 3

Throw-Over Case 4
Fault on XFMR 2 RTB CB5
Condition

T2Apu T3Apu

Trip

Time

Close

CCC CB6
X59L3*Y27D3*!T2BD
Close
DWG: AG2000.04.008

Figure 8: Timing Diagram for Throw-Over Control Case 4

Throw-over control at the 10 kv side is blocked when the transformer protection, 87T, picks up.
Use IN105 for this function and also for all other external blocking inputs.

Date Code 20000616 SEL Application Guide 2000-04 9


FACTORY ASSISTANCE
The employee-owners of Schweitzer Engineering Laboratories are dedicated to making electric
power safer, more reliable, and more economical.
We appreciate your interest in SEL products, and we are committed to making sure you are
satisfied. If you have any questions, please contact us at:
Schweitzer Engineering Laboratories
2350 NE Hopkins Court
Pullman, WA USA 99163-5603
Tel: (509) 332-1890
Fax: (509) 332-7990
We guarantee prompt, courteous, and professional service.
We appreciate receiving any comments and suggestions about new products or product
improvements that would help us make your job easier.

All brand or product names appearing in this document are the trademark or registered trademark of their respective holders.

Schweitzer Engineering Laboratories, SELOGIC, Connectorized, and are registered trademarks of Schweitzer Engineering Laboratories.

Copyright © SEL 2000 (All rights reserved) Printed in USA.

Applying the SEL-352 Relay


for Automatic Throw-Over Control
of a Bus Tie and Incoming Circuit Breakers SEL Application Guide 2000-04 Date Code 20000616

You might also like