Professional Documents
Culture Documents
Ag 200004
Ag 200004
INTRODUCTION
The SEL-352 Relay is an extremely flexible device. Two voltage source inputs and enhanced
SELOGIC® control equations allow the SEL-352 Relay to implement throw-over control functions
in addition to its pre-designed tasks. Automatic throw-over control of a bus tie and incoming
circuit breakers reduces the time that load is disconnected from a power source after a power
system disturbance. This application guide describes how to use the SEL-352 Relay to
automatically restore power to either 110 kV bus tie sections or 10 kV double bus sections as
shown in Figure 1, in the event that the respective source is removed.
Line 1 Line 2
PT1 PT2
352
CB 1 CB 2
CB 3
110 kV 110 kV
T1 T2
CB 4 CB 5
10 kV Bus 1 CB 6 10 kV Bus 2
PT3 PT4
352
DWG: AG2000.04.001
AC/DC CONNECTIONS:
110 kV section:
Connect the inputs VAX, VBX, and VCX of the SEL-352 Relay to the A-phase, B-phase, and
C-phase of the Line 1 potential transformer (PT1) and the inputs VAY, VBY, and VCY to the
A-phase, B-phase, and C-phase of the Line 2 potential transformer (PT2), as shown in Figure 1.
Connect the inputs IA, IB, and IC of the relay to the current transformer (CT) associated with
either Circuit Breaker 1 for Case 1 or Circuit Breaker 2 for Case 2.
OUT102 through OUT104 of the SEL-352 Relay are asserted to close Circuit Breakers 1
through 3, and OUT105 through OUT107 are asserted to trip Circuit Breakers 1 through 3,
respectively. A summary of general closing and tripping settings for bus-tie breakers CB1, CB2,
and CB3 follows:
SBLOG = CUSTOM
Relay inputs:
52AA = IN101 (Circuit Breaker 1 status, B contact)
52AB = IN102 (Circuit Breaker 2 status, B contact)
52AC = IN103 (Circuit Breaker 3 status, B contact)
Relay outputs:
OUT102 = CCA (close Circuit Breaker 1)
OUT103 = CCB (close Circuit Breaker 2)
OUT104 = CCC (close Circuit Breaker 3)
10 kV section:
Connect the inputs VAX, VBX, and VCX of the SEL-352 Relay to the A-phase, B-phase and
C-phase of the Bus 1 potential transformer (PT3) and the inputs VAY, VBY, and VCY to the
A-phase, B-phase, and C-phase of the Bus 2 potential transformer (PT4), as shown in Figure 1.
Connect the inputs IA, IB, and IC of the relay to the current transformer (CT) associated with
bus-tie CB6.
OUT102 through OUT104 of the SEL-352 Relay are asserted to close Circuit Breakers 4 through
6, and OUT105 through OUT107 are asserted to trip Circuit Breakers 4 through 6, respectively.
A summary of general closing and tripping settings for breakers CB4, CB5, and CB6 follows:
SALOG = CUSTOM
SBLOG = CUSTOM
Relay inputs:
52AA = IN101 (Circuit Breaker 4 status, b contact)
52AB = IN102 (Circuit Breaker 5 status, b contact)
52AC = IN103 (Circuit Breaker 6 status, b contact)
Relay outputs:
OUT102 = CCA (close Circuit Breaker 4)
OUT103 = CCB (close Circuit Breaker 5)
OUT104 = CCC (close Circuit Breaker 6)
OUT105 = RTA (trip Circuit Breaker 4)
OUT106 = RTB (trip Circuit Breaker 5)
OUT107 = RTC (trip Circuit Breaker 6)
T3A
X27D3 100
Y59L3
50LD 30
T2B T3C
IN105 5 10
52AB CCB CB2
0 52AA 3
DWG: AG2000.04.002
T2Apu T3Apu
Trip
Time
Close
CCB CB2
X27D3*Y59L3*!50LD
Close
DWG: AG2000.04.003
T3A
X59L3 100
Y27D3
50LD 30
T2B
T3C
IN105 5
10
52AA
CCA CB1
0 52AB 3
DWG: AG2000.04.004
T2Apu T3Apu
Trip
Time
Close
CCA CB1
Y27D3*X59L3*!50LD
Close
DWG: AG2000.04.005
T2C
Y27D3 100
X59L3 3
IN105
52AC T2B 52AA T1A
5 10 CCC CB6
X59L3
Y59L3 3
0
50LD
52AB
DWG: AG2000.04.006
Close CB6 for loss of voltage on Bus 1 but for full voltage on Bus 2. Set the T3Apu time delay
greater than the tripping time of CB4. This ensures that CB4 has time to open before the relay
attempts to close CB6.
SELOGIC control equations:
X27D3 = dead bus voltage on Bus 1
X59L3 = live bus voltage on Bus 1
Y27D3 = dead bus voltage on Bus 2
Y59L3 = live bus voltage on Bus 2
T2A = !52AA*!52AB*52AC*X59L3*Y59L3 (Breakers 4 and 5 closed, Breaker 6
opened)
T2B = IN105 + !52AC + (X59L3*Y59L3) + T1A +50LD
T2C = T2AD*(Y27D3*X59L3)*!T2BD
T3A = T2AD*(X27D3*Y59L3)*!T2BD
T3B = T3AD*!52AA
T3C = T2CD*!52AB
T1A = (T3AD*52AA) + (T2CD*52AB)
RTA = T3BD (trip Circuit Breaker 4)
RTB = T3CD (trip Circuit Breaker 5)
CCC = T1AD (close Circuit Breaker 6)
IN105 = Throw-over block (87T and all other external protection)
T2Apu T3Apu
Trip
Time
Close
CCC CB6
X27D3*Y59L3*!T2BD
Close
DWG: AG2000.04.007
Throw-Over Case 4
Fault on XFMR 2 RTB CB5
Condition
T2Apu T3Apu
Trip
Time
Close
CCC CB6
X59L3*Y27D3*!T2BD
Close
DWG: AG2000.04.008
Throw-over control at the 10 kv side is blocked when the transformer protection, 87T, picks up.
Use IN105 for this function and also for all other external blocking inputs.
All brand or product names appearing in this document are the trademark or registered trademark of their respective holders.
Schweitzer Engineering Laboratories, SELOGIC, Connectorized, and are registered trademarks of Schweitzer Engineering Laboratories.