Boq 90 TR
Boq 90 TR
(This BOQ
Sl. template must not be modified/replaced
Item Description by the bidder and the same should be uploaded
Quantity
No.
1 PART 'A' - HIGH SIDE EQUIPMENTS
2 CHILLERS
3 Supply, installation, testing & commissioning of screw type water
cooled water chilling machines having actual capacity of 90 TR with VFD
starter at chilled water inlet/ outlet temperature of 12.22 deg. C /
6.67 deg. C having evaporator fouling factor of 0.0005 FPS and condenser
water inlet / outlet temperature of 32.2 deg. C/ 36.4 deg. C having
condenser fouling factor of 0.001 FPS suitable for operation on refrigerant
R-134a comprising of the following complete as per specifications and as
required.
4 Minimum COP should be 5.9 for water cooled screw chillers. The IPLV
of VFD chiller should not be more than 0.4 KW/TR as per CPWD norm.
The IKW/TR should not be more than 0.64 KW/TR.