ITRP Program Management Team

REQUEST FOR INFORMATION (RFI) HOI ISTON


AIRPORTS
RFI No.: RFI 2266
Company Name:
Hensel Phelps Aconex No.

TITLE: CBIS - ESSE Missing Specs for Lift Station


WBS NO.: IFXX- FIS

ISSUE DATE: 03/20/2024


CONTRACT: C02 - FIS CMAR (HP)
03/27/2024
REQUIRED DATE:
TO: FAS
RESPONDED
Drawina/Soecification Reference: ‘Select*
Cost Impact: ‘Select*
Lift Station Pump Product Data, Lift Station Sewage DATE: STATUS:
AirA/acuum Valve
Time Impact ‘Select* PRIORITY: Urgent

QUESTION:

Discipline Review Please continue to use the submittal approval process for products seeking approval from the engineer.
Reviewing Discipline: Civil (In this case, we understand why the RFI was submitted)
Reviewed By: javillarreal Date: 3/28/2024
- Jose Villarreal (BMcD)

Digitally signed by Jose Calderon


Garcia AIA
DN: C=US,
Jose Calderon Garcia AIA E=garcia@fentressarchitects.com,
O=Fentress Architects, CN=Jose
Calderon Garcia AIA
Date: 2024.03.29 08:56:30-05'00'

Answered by:
Signed: Date:
The RFI response is incorporated into the Contract. Contractor is directed to submit a Change Request within 21 days for any responses received that impact the
cost and/or time of the Contract as per Exhibit C 7.3.2.1. If a Change Request is required, DO NOT START WORK until a Change Order is approved.
Revision: 141 Status: IFI | Issue Date: 20220302 IAH Terminal Redevelopment Program
Sewage Air/Vacuum Halve

Series 401 and larger Model APCO Sewage Air/


Shutoff Vacuum Valves are specifically designed for
Valve
operation on sewage and waste media.

Venting Air/Vacuum Valves are needed to vent large


Mechanism
volumes of air when the sewage line is filled and
allow air to re-enter when draining, to prevent
vacuum or column separation occurring. Sewage
Air/Vacuum Valves utilize two floats, each
connected to a common stem which is guided
through a bushing.

The upper float shuts off instantaneously against


Backflushing the seat, due to the impact zone and lifting force
Stem
Attachments of the much larger concave bottom float, as
Optional
sewage media enters the valve body.
l
Once closed, and pressurized, the Air/Vacuum
Valve will not open to release air. It will open
under negative pressure allowing air to re-enter
and prevent vacuum from forming in the line.

Concave
Float

Optional
Blowoff
Valve

Larger Sizes
Have Flanged
Inlets

Optional
Inlet Shutoff Valve

6 www.dezurik.com
Dimensions and Specifications
Series 401 Sewage Air Vacuum Valve

Size Height Major Weight


Model
Outlet Waliio w|Attai>hmontc Dia. Plain vl'/Altac htnsn* e
2" NPT r NPT 16.25" 2fl! Z 41 65
401 178 19 25
50 25 413 508

^ wi T377TF1 23.5 SJ=L J-.I.P.


402 241 39 52
60 50 502 597

3" NPT 3" NPT 19.75" 23,75" M! 85 118


403 80 502 603 241 39 54
80

4" NPT 4" Plain 30" 35.25" 12" 130 200


404 59 91
100 100 762 895 305

6" FLG 6" Plain 32.5" 36.5" 16" 190 290


406 406 86 132
150 150 826 927

8" FLG 8" Plain 36" 40" 18" 310 430


408 457 141 195
200 200 914 1016

10" FLG 10" Plain 41“ 45" 20" 600 800


410 272 363
250 250 1041 1143 508

12" FLG 12" Plain 47" 53.5" 25" 750 980


412 340 445
300 300 1194 1359 635

14" FLG 14" Plain 51.5" 57.25" 29" 950 1230


414 737 431 558
350 350 1308 1454

Inch Pounds 4" (100mm) and larger flanged outlets available.


Millimeter Kilograms

Specify APCO with Confidence - Sewage Air/Vacuum Valve Series 401


Sewage Air/Vacuum Valves shall allow unrestricted venting or re-entry of air through it during filling or
draining of the force main to prevent vacuum. The Sewage AirA/acuum Valve shall incorporate (2)
stainless steel floats directly connected by a stainless steel stem, to maintain an air gap between the bottom
concave float and top shut-off float. The air gap shall retard waste solids from fouling or clogging the top
shut-off float. The internal baffle shall be fitted with a guide bushings and act to protect the shut-off float from
direct air flow. The baffle shall retain the Buna-N seat in place, without distortion for tight shut-off.

All internals shall be easily removed thru the top cover without removing the main valve from the line. The
complete valve shall withstand 500 psi (3447 kpa) test. Optional - Inlet and blow off valves, quick disconnect
couplings and minimum 5' (1.5m) hose for flushing. Engineer to specify.

The valve manufacturer shall furnish professionally printed installation and maintenance instruction manuals
with each valve.

Materials of construction shall be certified the following ASTM specifications:

Body, Cover and Baffle Cast Iron ASTM A126 GR.B


Ductile Iron ASTM A536 GR 65-45-12
Upper Float Stainless Steel ASTM A240
Patented Concave Lower Float Stainless Steel ASTM A240 T304
Stem, Guide Bushing Stainless Steel Series T300
Seat Buna-N Nitrile Rubber
Exterior Paint Universal Metal Primer FDA Approved for Potable Water

www.dezurik.com 7
SECTION 2
Pumps □ UK

PARK
A Northwest Pipe Company
Headquarters North Texas South Texas Central Texas
-^r UHSJGN r~ a R w ATER
7015 Fairbanks 1200 I-45 South 20943 U.S. 77 8491 Highway 87 East
Houston, TX 77040 Dallas, TX 75125 Harlingen, TX 78550 San Antonio, TX 78263

SPARK
www.park-ues.com
Tel 713-937-7602
Fax 713-937-4254
Tel 972-263-0222
Fax 972-842-8871
Tel 956-428-2079
Fax 956-440-1834
Tel 210-227-PARK
Fax 210-566-7270

Voltage Verification Form j£.


Precast Concrete
‘Expect the betst”
Catch Basins
7 Manholes
To: Will Doran
Grease Interceptors
Park USA
Acid Neutralization
Company:
Wastewater Treatment
Pump Stations
Phone No.: (713) 849-7115
Oil-Water Separators
Water Meter Assemblies
Email: Wdoran@PARK-USA.COM
Backflow Prevention
Fire Check Assemblies
Quote No.: 20-26584 Water Break Tanks
Aboveground Fuel Tanks
Job Name: IAH - Mickey Leland

Item: WW96-NCD4/6

Your Purchase
Order:

Order No.: 103082

Note:
Pumps and controls cannot be ordered until this
information is verifiedby customer.

Please provide us with the electrical characteristics for


the pump(s)and controls for this system:

Select Only One of the Following

Three Phase Typical Lift Station Detail


□ 460V-3ph-60Hz
□ 230V-3ph-60Hz Did You Know
Park can assist with
□ 208V-3ph-60Hz
design and pricing on a
complete Lift Station
Package, including Wet Well,
Name:
Submersible Pumps, Control
Panels, and Valve Assemblies.
Date:

For your next Stormwater or


Company: Sanitary Sewage application,
CALL US!
Contact No.:
Bill of Materials- Mickey Leland International Terminal

Customer: Park USA

Engineer: Amani Engineering, Inc.

1. Two (2) NP-3102/463 5.5hp, 460/3. Pump includes 50’ power cable and FM rated motor.
Capable of pumping 490@26’
2. Two (2) 4” base elbows
3. Two (2) 2” upper guide rail brackets, 316SS
4. Two (2) 5/16” x 30’ lifting chains with shackles, 316SS
5. Two (2) 2” x 4” intermediate guide rail brackets, 316SS
6. One (1) control panel, NEMA 4X 304SS w/ high level alarm light
7. Four (4) control floats, model S40NO, 40’ cable
8. One (1) submersible transducer, 60’ cable
9. Two (2) cable holders, 316SS

Please verify power cable length and voltage prior to order.


a xylem brand

WARRANTY
Xylem Water Solutions USA, Inc.

For the period defined, Xylem Water Solutions USA, Inc. offers a commercial warranty to the original End Purchaser
against defects in workmanship and material on Flygt Products. Warranty covers Flygt parts and labor as outlined in
ADDENDUM -A.

COVERAGE:
Xylem Water Solutions USA, Inc. will pay the cost of parts and labor during the warranty period, provided that the Flygt
product, with cable attached, is returned prepaid to a Xylem Water Solutions USA, Inc. Authorized Service Facility for
Flygt Product repairs. Coverage for Flygt parts and labor will be provided for the period shown in ADDEMHJM - A. The
warranty period will begin from date of shipment or date of a valid Start-up (For permanently installed pumps only). In
cases where the Start-up date is used as the beginning of the warranty on a permanently installed Flygt pump, a Start-up
Report completed by an approved service technician from a Xylem Water Solutions USA, Inc. Authorized Service Facility
for Flygt products must be received by the Xylem Water Solutions USA, Inc. Area Service Manager for Flygt Products
within thirty (30) days of the initial onset of the unit placed into service. If not received, the beginning of the warranty
coverage will default to the Flygt product ship date. A Start-up for a permanently installed Flygt pump must occur within
one (1) year from the date of shipment from a Xylem Water Solutions USA, Inc. authorized facility for Flygt Products or
warranty will automatically default to ship date as start of warranty. (See STORAGE section) When using the start-up
date as the beginning of the warranty, a copy of the Start-up Report will be required to support any Warranty Claims.
Warranty on Flygt Dewatering pumps will begin with ship date only. No other date on Flygt Dewatering pumps will be
considered.

Xylem Water Solutions USA, Inc/s sole obligation under this Warranty for Flygt Products shall be to replace, repair or
grant credit for Flygt Products upon Xylem Water Solutions USA, Inc.'s exclusive determination that the Flygt Product
does not conform to the above warranty. In the event that the Flygt product is replaced, warranty on the replacement
product will be equal to the balance remaining on the original product or ninety (90) days, whichever is greater.

MISUSE:
This Warranty shall not apply to any Flygt product or part of Flygt product which (i) has been subjected to misuse,
misapplication, accident, alteration, neglect, or physical damage (ii) has been installed, operated, used and/or maintained
in a manner which is in an application that is contrary to Xylem Water Solutions USA, Inc.'s printed instructions as it
pertains to installation, operation and maintenance of Flygt Products, including but without limitation to (iii) operation of
equipment without being connected to monitoring devices supplied with specific products for protection; or (iv) damaged
due to a defective power supply, improper electrical protection, faulty installation or repair, ordinary wear and tear,
corrosion or chemical attack, an act of God, an act of war or by an act of terrorism; or (v) has been damaged resulting
from the use of accessory equipment not sold by Xylem Water Solutions USA, Inc. or not approved by Xylem Water
Solutions USA, Inc. in connection with Flygt products.

WEAR PARTS:
This warranty does not cover costs for standard and/or scheduled maintenance performed, nor does it cover Flygt parts
that, by virtue of their operation, require replacement through normal wear (aka: Wear Parts), unless a defect in material
or workmanship can be determined by Xylem Water Solutions USA, Inc.. Wear Parts are defined as Cutters, Cutting
Plates, Impellers, Agitators, Diffusers, Wear Rings (Stationary or Rotating), Volutes (when used in an abrasive
environment), oil, grease, cooling fluids and/or any items deemed necessary to perform and meet the requirements of
normal maintenance on all Flygt equipment.

xylem
Ver. 14-031618
a xylem brand

WARRANTY
Xylem Water Solutions USA, Inc
DISCLAIMERS:
(i) Xylem Water Solutions USA, Inc.'s warranties are null and void when Flygt Products are exported outside of the United
States of America without the knowledge and written consent of Xylem Water Solutions USA, Inc.; (ii) Xylem Water
Solutions USA, Inc. makes no independent warranty or representation with respect to parts or products manufactured by
others and provided by Xylem Water Solutions USA, Inc. (however, Xylem Water Solutions USA, Inc. will extend to the
Purchaser any warranty received from Xylem Water Solutions USA, Inc.'s supplier for such parts or products).

LIMITATIONS:
XYLEM WATER SOLUTIONS USA, INC. NEITHER ASSUMES, NOR AUTHORIZES ANY PERSON OR COMPANY TO ASSUME
FOR XYLEM WATER SOLUTIONS USA, INC., ANY OTHER OBLIGATION IN CONNECTION WITH THE SALE OF ITS FLYGT
EQUIPMENT. ANY ENLARGEMENT OR MODIFICATION OF THIS WARRANTY BY A FLYGT PRODUCT DISTRIBUTOR, OR
OTHER SELLING AGENT SHALL BECOME THE EXCLUSIVE RESPONSIBILITY OF SUCH ENTITY.

THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY AND ALL OTHER EXPRESS OR IMPLIED WARRANTIES,
GUARANTEES, CONDITIONS OR TERMS OF WHATEVER NATURE RELATING TO FLYGT PRODUCT(S), INCLUDING AND
WITHOUT LIMITATION ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
WHICH ARE HEREBY EXPRESSLY DISCLAIMED AND EXCLUDED. PURCHASER'S EXCLUSIVE REMEDY AND XYLEM WATER
SOLUTIONS USA, INC.'S AGGREGATE LIABILITY FOR BREACH OF ANY OF THE FOREGOING WARRANTIES IS LIMITED
TO REPAIRING OR REPLACING FLYGT PRODUCTS AND SHALL IN ALL CASES BE LIMITED TO THE AMOUNT PAID BY THE
PURCHASER HEREUNDER. IN NO EVENT IS XYLEM WATER SOLUTIONS USA, INC. LIABLE FOR ANY OTHER FORM OF
DAMAGES, WHETHER DIRECT, INDIRECT, LIQUIDATED, INCIDENTAL, CONSEQUENTIAL, PUNITIVE, EXEMPLARY OR
SPECIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE, LOSS OF PROFIT, LOSS OF ANTICIPATED
SAVINGS OR REVENUE, LOSS OF INCOME, LOSS OF BUSINESS, LOSS OF PRODUCTION, LOSS OF OPPORTUNITY OR
LOSS OF REPUTATION.

XYLEM WATER SOLUTIONS USA, INC. WILL NOT BE HELD RESPONSIBLE FOR TRAVEL EXPENSES, RENTED EQUIPMENT,
OUTSIDE CONTRACTOR'S FEES, OR ANY EXPENSES ASSOCIATED WITH A FLYGT PRODUCT REPAIR SHOP NOT
AUTHORIZED BY XYLEM WATER SOLUTIONS USA, INC. U.S.A., INC. REIMBURSEMENT COSTS FOR CRANES AND/OR ANY
SPECIAL EQUIPMENT USED IN CONJUNCTION FOR THE REMOVAL AND/OR REINSTALLATION OF ANY FLYGT
EQUIPMENT IS NOT COVERED UNDER THIS WARRANTY.

ANY UNAUTHORIZED ALTERATIONS TO SUPPLIED FLYGT EQUIPMENT USED WITHOUT XYLEM WATER SOLUTIONS USA,
INC. SUPPLIED FLYGT BRAND CABLE OR CONTROLS WILL NOT BE COVERED UNDER THIS WARRANTY, UNLESS IT CAN
BE PROVEN SUCH ANCILLARY EQUIPMENT IS SUITABLE FOR THE PURPOSE AND EQUAL TO XYLEM WATER SOLUTIONS
USA, INC. SUPPLIED FLYGT BRAND CABLES OR CONTROLS THAT WOULD ORIGINALLY HAVE BEEN SUPPLIED WITH THE
TYPE OF EQUIPMENT IN USE.

REQUIREMENTS:
A copy of Electrical System Schematics of the Control used (including a Control's Bill of Material) could be required to
support a Warranty Claim when a non Flygt Brand Control is used. In addition, a written record, hereby known as "the
log", will be associated with each unit serial number and must be maintained by the organization having product
maintenance responsibility. The log must record each preventative maintenance activity and any repair activity during the
life of the warranty or verification that a Xylem Water Solutions USA, Inc. authorized Service Contract for Flygt Products is
in force and must be available for review and/or auditing. Failure to meet these conditions could render this warrant null
and void. Such logs could be required to determine warranty coverage.

xylem
J tart Saint Wafer

Ver. 14-031618
a xylem brand

WARRANTY
Xylem Water Solutions USA, Inc.
STORAGE:
Should a delay occur between ship date and the date of start-up, maintenance as outlined in Xylem Water Solutions USA,
Inc/s Care & Maintenance Manual for Flygt Prodqcts must be performed by the "CONTRACTOR" and/or "OWNER" during
any such period of storage. Documentation providing proof and outlining what maintenance was performed must be provided
to Xylem Water Solutions USA, Inc. or its Flygt Products representative within thirty (30) days of said maintenance, or the
Xylem Water Solutions USA, Inc. warranty for Flygt Products could be considered void.

CONTROLS:
Warranty coverage for permanently installed controls will start for the end purchaser on the date of shipment. This
warranty does not apply to controls that have been damaged due to a defective and/or improper input power supply,
improper electrical protection, accidental damage, improper or unauthorized installation and/or repair, unauthorized
alteration, negligence, environmental corrosion or chemical attack, improper maintenance or storage of control, any act of
God, an act of war, an act of terrorism or damage resulting from the use of accessory equipment not approved by Xylem
Water Solutions USA, Inc.. Further, this warranty does not apply in the event an adjustment is found to correct the
alleged defect.

Solid state devices will be covered for a period of one (1) year. Electrical control panels containing controllers, PLC's,
drives, soft starts, and other computerized equipment will require Transient Voltage Surge Suppression (TVSS) protection
in order to satisfy the requirements of this warranty. The protection equipment associated with the control must be kept
in working condition during the life of the warranty. Auxiliary equipment supplied with the control (air-conditioners etc.) is
limited by the respective original equipment manufacturer's warranty offered. Consumable items such as: light bulbs,
fuses, and relays are covered under normal operating conditions. Electrical surges experienced during startups and/or
during normal operating use of the control panel will cause the consumable items not to be covered under this warranty
policy. Components not supplied by Xylem Water Solutions USA, Inc. will not covered by this warranty.

TOP (The Optimum Pump Station)


Xylem Water Solutions USA, Inc. will warrant the Flygt TOP pre-engineered fiberglass pump station components against
defects in material and workmanship for a period of one (1) year from date of start-up or eighteen (18) months from date
of shipment and is valid only to the original owner of the station. Warranty shall cover the cost of labor and materials
required to correct any warrantable defect, excluding any removal and reinstallation costs, FOB Xylem Water Solutions
USA, Inc.'s authorized warranty service location for Flygt's TOP.

Flygt Products contained within a TOP pre-engineered fiberglass pump station will carry the standard Xylem Water
Solutions USA, Inc. warranty for Flygt products and/or accessories installed in the TOP pre-engineered fiberglass pump
station.

All Flygt Product restrictions and/or limitations as outlined and described within the context of this warranty are germane
to all sections of this Xylem Water Solutions USA, Inc. Warranty document.

Xylem Water Solutions USA, Inc.


National Quality Assurance - US Corporate

xylem
* IjnSnUlUr

Ver. 14-031618
HSGT
axytem brand
WARRANTY
Xylem Water Solutions USA, Inc.

ADDENDUM - WARRANTYCOVERAGE BYPRODUCT


MONTHS MONTHS MONTHS MONTHS MONTHS MONTHS MONTHS MONTHS
PRODUCT PRODUCT SERIES AND CONFIGURATION
1-12 13-18 19-24 25-36 37-39 40-60 61-72 73-84
3000 Series (CP, NP, DP, CT, NT, CZ, NZ, LL)
Axial Flow/Mixed Flow/Centrifugal Pumps & Mixers 4000 Series (SR, PP) 100% 50% 25%

7000 Series (PL)


6000 Series (DP) 100% 50% 25%

Concertor Pumping System 100% 50% 25-48 MONTHS 25% 49-84 MONTHS
6000 Series (iPS)
Engineered to Order, Xylem Manufactured Control 100% 1 YR LIMITED-2 YEAR
ETO Electrical Control Panels
Panels (permanently installed) - 3 Years

Grinder Pumps 3000 Series (MP, MF, MH) 100% - 2 YEAR (From Ship Date) (From DOM) DOM= Date of Manufacture

3000 Series (FP, FS, FT, HP, HS)


Abrasion/Corrosion Resistant&Chopper Pumps 5000 Series (HP, HS) 100%
8000.280 Series (DP, DZ, DT, DS, DF)

Centrifugal Pumps 1300 Series 100% (FromShipDate)

2000 Series (BS, KS)


Dewatering Pumps 3000 Series (CS, NS, DS) 100% (FromShipDate)

8000.280 Series (DS, DF)


100% (From
Ship Date)
TOPS Fiberglass Pump Station

100% (From
Accessories Permanent / Portable Ship Date)

Hydroejectors/Aerators HE, JA 100% .

Portable Pump Controls Control Boxes (Nolta, MSHA etc.) 100% (From
ShiD Datel
TOPS Control Panels TOPS control panels (permanently installed)

100% (From
Small Pumps 3045, 3057, SX Ship Date)

100% (From
Parts - * All new Flygt parts (mechanical & electrical) Shio Date)

* - Parts that fail where used in a repair are warranted for one (1) year from the date of the repair for the failed part only - no labor; This Includes Flygtpump
controllers, Flygt supervision equipment, Flygt submersible level transducers, etc.

xylem
* Lxt&afevw
Ver. 14-031618
a xylem brand Issued: 10/08 Supersedes: 2/03

Explosion-proof Pumps

Explosion-proof Pumps for Hazardous Locations Special Features


Flygt Electric Submersible Explosion-proof Wastewater The construction of an Explosion Proof pump is similar
Pumps are examined, tested, and approved by Factory in most respects to the standard wastewater pump, but
Mutual Research (FM) as Explosion-proof. They conform differs in the following details:
to the latest edition of the National Electrical Code (NEC),
Articles 500,501,502, and 503 requirements as explosion 1. Hydrostatically pressure tested high strength, cast
proof and suitable for use in Class I, Division 1, Groups C iron housings are designed to withstand an internal
and D, and dust ignition proof and suitablefor use in Class explosion and have long tight flame paths to reduce exit
II, Division 1, Groups E, F and G hazardous locations, temperature of any exploding gases to a value belowthe
and suitable for use in Class III, Division 1 hazardous ignition temperature of the surrounding environment.
locations. FM approval also meets OSHA (Occupational
Safety and Health Administration) requirements. 2. All pumps have required pilot thermal sensors
embedded in stator windings, to guarantee that the
Definition of Hazardous Locations by NEC pump surface temperature never exceeds safe limits,
avoiding possible environmental ignition.
Class I locations are those in which flammable gases
or vapors are or may be present in the air in quantities 3. Externally mounted leakage sensors may not be
sufficient to produce explosion or ignitable mixtures. used unless explosion proof or intrinsically safe (consult
factory for details).
Class I, Division 1 location is a location: (1) in which
ignitable concentrations of flammable gases or vapors 4. Special approved power cables required: Flygt
exist under normal operating conditions; or (2) in which SUBCAB.
ignitable concentrations of such gases or vapors may
exist frequently because of repair or maintenance 5. Al I pu m ps, except 3045(X), 3057(X), 3085(X), 3102(X)
operations or because of leakage; or (3) in which and 3127(X), have a special stator inspection plug.
breakdown orfaulty operation of equipment or processes The 3085(X), 3102(X) and 3127(X) stator housings are
might release ignitable concentrations of flammable inspected for leakage through the cable entry. Here,
gases or vapors, and might also cause simultaneous penetration of oil from the oil chamber below, or water
failure of electric equipment. from the junction chamber above can be detected.

Class II locations are those that are hazardous because 6. Flygt controls supplied with these pumps incorporate
of the presence of combustible dust. the following required circuits:

Class II, Division 1 location is a location: (1) in which A. Motor pilot thermal sensors (connection is approval
combustible dust is in the air under normal operating mandatory).
conditions in quantities sufficient to produce explosive
or ignitable mixtures; or (2) where mechanical failure B. Intrinsically safe relays for ENM-10 level sensors (or
or abnormal operation of machinery or equipment equal) - usage is mandatory.
might cause such explosive or ignitable mixtures to be
produced, and might also provide a source of ignition CAUTION: All controls, used with these pumps but not
through simultaneous failure of electric equipment, supplied by Flygt, must be designed according to the
operation of protection devices, or from other causes; latest applicable standards. See Monitoring & Controls
or (3) in which combustible dusts of an electrically Section for additional details and requirements.
conductive nature may be present.
Environmental Limits
Class 111 locations are those that are hazardous because The maximum temperature of exposed (external) pump
of the presence of easily ignitable fibers or flyings but surfaces is self controlled by the motor pilot thermal
not likely in air suspension in quantities sufficient to switches. Maximum allowed ambient (environmental)
produce ignitable mixtures. temperature is 115°F (46°C).

Class III, Division 1 location is one in which easily Application of Explosion-proof Pumps
ignitable fibers or materials producing combustible These pumps may be used in sewage wet wells that are
flyings are handled, manufactured, or used. classified as Class I, Division 1, Groups C and D
a xylem brand Issued: 8/10 Supersedes: 10/08

Explosion-proof Pumps

hazardous locations (gases and vapors). They can also Depending on the type and geographical position of
be used in applications that are classified as Class II, the “location”, the Authority may range the gamut from
Division 1, Groups E, F and G hazardous locations a federal agency to state, regional, local agencies or
(typified by grain or coal storage); also, Class III, Division the consulting or plant engineer. Often the best source
1 locations (fibers and flyings). of information is the state Administrative Code or a
state agency such as a Department of Environmental
Other areas, which may be classified hazardous under Protection (DEP), Environmental Protection Agency
normal conditions and where the use of Explosion- (EPA), Department of Health, etc.
proof pumps for handling contaminated wastewater
is required are: refineries, petrochemical industry Approval Requirements (NEC/Factory Mutual)
locations, tank farms, gas utility vaults, etc., always Class I, Division 1: suitable equipment must be explosion
taking into consideration that these pumps are not proof. It must also contain pilot motor thermal sensors
designed or approved as process pumps deliberately (which must be connected in the motor control).
and protractedly handling high concentrations of
hazardous liquids, e.g.: gasoline, etc. Class II, Division 1: suitable equipment must be “dust
ignition proof” and use motor pilot surface temperature
Limitations limiting thermal switches as in Class I.
1. CP/CS, DP/DS and FP/FS 3085(X) does not
optionally have a terminal board as does the standard Class III, Division 1: suitable equipment need only be
version. totally enclosed, non ventilated.
2. This Explosion-proof pump is not available in the
Warm Liquid (WL) variant. Current Approvals for hazardous location pumps
previously noted are by FM (Factory Mutual Research).
Division 2, All Classes: For Class I or II locations, FM is officially listed by OSHA (Occupational Safety
a Division 2 designation means that the ignitable or & Health Administration) in the Federal Register as a
combustible materials will not normally be present Nationally recognized testing laboratory (NRTL). It is in
in hazardous concentrations except by accident or all regards equivalent to UL (Underwriters Laboratory).
malfunctions of containing or protective systems. In
Class III locations, Division 1 and 2 are almost the same Restrictions: The listed (X) pumps are not approved for
(check NEC Article 503). “process pumping” where high concentrations of liquids
(other than wastewater) are handled for process work,
Equipment approved as suitable for use in Division 1 transfer, or recovery. Theacceptable usage is for handling
locations is automatically suitable for use in Division 2 wastewater (contaminated water, sewage, etc.) for the
locations. However, if the Authority Having Jurisdiction purposes of treatment, transfer, storage, or disposal.
has definitely defined the area as Division 2, standard
submersible pumps (motors) may be used so long as No accessory equipment may be attached to an approved
they do not contain any open (non-hermetically sealed) pump unless it is specifically approved for the location
ignition sources (See NEC Article 501-8 and 502-8) or “intrinsically safe” (See NEC 500-2 for Intrinsic Safe
and use motor pilot thermal switches to limit surface requirements).
temperatures. Standard Flygt submersible pumps meet
these requirements. WARNING: All NEC and local code requirements must be
scrupulously observed when making an installation. Be
Classification certain that glands and conduits where pump(s) or control
A sewage wet well (or any other wastewater collection wiring/cable passes from a hazardous location (wet pit,
location) is not automatically a hazardous location. etc.) to electrical service, controls, or nonclassified area
The nature and classification of any location must be are suitably sealed against passage of gases or liquids.
determined and indicated by whoever is considered to
be the Authority Having Jurisdiction. Aggressive Liquids: Depending on temperature,
pH, concentration, and their intrinsic reactivity, certain
This Authority is not always easily determined. Care contaminant chemicals (acids, alkalies, solvents, etc.)
and diligence must be exercised to make sure, once a may have a deteriorating effect on the equipment and
preliminary identification has been made, that there is
not some other superseding Authority. r
a xylem brand Issued: 10/08 Supersedes: 6/94

Explosion-proof Pumps

pose a safety hazard to the installation. Be careful to Declassification: An examination of local/state


fully examine these circumstances with the end user or administrative codes, NEC Chapter 5, and NFPA
his representative and consult with Flygt. Standard 70C and 496, shows that a hazardous location
may be reduced in classification from Division 1 to
A number of alternative configurations or approaches Division 2 or even to a nonhazardous condition through
are available which may make the equipment suitable in the use of suitable air purging and use of monitoring
the presence of these materials: alternate elastomers, safeguards. This would then allow the installation of
cable sheathing, special cable entries, etc. standard pumping equipment.

Accessories: Non-sparking bronze “Safe-Slide®1' This is a common practice in many parts of the country
installation/removal guide accessories are available for when the installation makes it practical. The approach
all approved pumps. While not required by the Approval has additional benefits: purging not only removes
Authority they may be desired by local authorities and any explosive/flammable gases, but also removes
do provide an extra margin of safety for particularly smothering or poisonous gases thus improving the
hazardous classified locations. personnel safety aspects of the location.

Cable: Flexible cords or cables used in hazardous Mine Safety and Health Administration (MSHA)
locations must be of the NEC type “extra-hard usage” Equipment approved byMSHA(Permissible-suitab!efor
and be specifically approved/tested for the approved use in gassy mines) may not be used in any hazardous
equipment (motor/pumps) which they will be used with. location covered by the NEC categories (Class I, II, or
No unapproved substitutions may be made without III) without written permission of the authority having
loss of official approval. Cables supplied by Flygt and jurisdiction.
used with Flygt electric submersible pumps are FM
tested and approved for the hazardous locations listed Nor may equipment approved/listed by FM or UL be used
for the pumps in the beginning of this Explosion-proof in a gassy mine without the written approval of MSHA.
pumps section.

To protect against the damaging and unsafe effects of


very aggressive contaminants (liquids, dissolved solids)
in the wastewater, special cable entries are available
which will allow pipe or stainless steel flex hose sheathing
to be attached to protect the cable.

Special Exceptions for Hazardous Locations: It is


possible in some circumstances to use standard pumps
in what would normally be declared as hazardous
locations. These approaches are supported by various
codes but may not be used if specifically disallowed by
an Authority Having Jurisdiction.

Guaranteed Pump Submersion (GPS): Iftheequipment


is so controlled that the liquid level never falls below a
point 4 - 6 inches above the topmost point of the pump,
then standard non-approved pumps may be used. This
is because the volume below a liquid surface is not
considered hazardous.

The means for guaranteeing that a pump will always


remain submerged during operation vary from one part
of the country to another. Consult Flygt for appropriate
configurations.
FLYGT Authorized Service Locations
a xylem brand
General Information Issued: 05/13 Supersedes: 11/12
STATE CITY COMPANY TELEPHONE 2000 HP 3000 HP 4000 HP 5000 HP 7000 HP 8000 HP
Series Series Series Series Series Series
Pump Pumps Mixer Pumps Pumps Pumps

MS Olive Branch Gulf States Engineering (662)890-4768 2400 140 3300 88 4680 40 5540 20
Stevens Electric & Pump
ME Monmouth (207)933-9638 2290 110 3300 88 All All
Service Inc
ME South Portland Trask - Decrow (800)287-1538 2250 87 3300 88 4680 40 5560 88

MT Helena Godwin Pumps (406)495-1335

NC Charlotte Brown & Morrison (704)554-8570 2400 140 3312 240 4680 40 5560 85

NC Charlotte Xylem (704)504-8570 2400 140 3312 320 4680 40 5560 85

ND Fargo Electric Pump Inc (701)293-0371 All 3300 88 4680 40

NJ Middlesex Pumping Services (732)469-4540 2400 140 3602 250 4680 40 5680 85 7650 150

NM Albuquerque James, Cooke & Hobson (505)344-7100 2400 140 3356 150 4680 40 All 7081 110

NV Sparks Pac Machine Company (775)359-8500 2400 140 3356 150 4680 40 All 7081 110

NY Harrison Fleet Pump & Service (914)835-3801 2290 110 3300 88 4680 40 5660 85

NY Rochester Xylem (585)426-0280 All All All All All

OH Cincinnati Buckeye Pumps, Inc (513)679-6100 2151 30 3300 88 4680 40 5650 45

OH Galion Buckeye Pumps, Inc. (419)468-7866 2400 140 3312 280 4680 40 5570 250 7115 185

OH Milford Xylem (513)248-3200 2400 140 3602 318 4680 40 5660 85 7650 350

OK Tulsa Automatic Engineering (918)585-5703 2250 88 3300 88 4680 40

OR Portland Xylem (503)240-1980 All All All All All


RAM Industrial Services,
PA Carrolltown (814)344-6591 2400 140 3312 200 4680 40 5660 85 7060 110
Inc.
PA Malvern Xylem (610)647-6620 All All All All All All
RAM Industrial Services,
PA Winfield (570)524-4411 2400 140 3300 88 4680 40 5680 85
Inc.
PR Caguas INECO (787)286-3125 2290 110 3400 215 4680 40

TN Murfreesboro Nedrow & Associates (615)867-7576 2400 140 3312 240 4660 40 5660 77

TX Amarillo J & L Equipment (806)622-9955 2290 110 3300 88 5660 85

TX Corpus Christi Xylem (361)808-7867 2400 140 3602 350 4501 20 5250 228 7100 328

TX Dallas Xylem (972)418-2400 All All All All All All


. ~ , « , , ,
i—i 1 aou Jdllfcb OUUKC Ot 1 IUDSUII Ouuo

TX Houston Hahn Equipment Co.** (713)868-3255 2400 140 3602 350 4680 40 5350 328 7100 328
.
iuiK IuTTT}J L^uijjiiidil (v?Od)i oWl \J\J
TX San Antonio Xylem (210)946-7867 2400 140 3602 350 4501 20 5250 228 7100 328 All
Compressor Pump &
UT Salt Lake City (801)973-0154 2400 140 3300 88 4680 40 All 7081 110
Service
Engineering Equipment/
VA Richmond (804) 639-2400 2250 110 3300 88 4680 40 5560 85
TENCARV
WA Bothell Whitney Equipment Co ** (425)486-9499 3356 150 4680 40 All 7081 110

Wl Milwaukee Xylem (262)544-1922 All All All All All

wv Charleston Precision Pump Service (304)776-1710 2400 140 3602 215 4680 40 5660 77

Exept 460 V Motors ** Above 125 HP under direction of Flygt Regional Service Manager
NOTE: 4600 series mixers under direction of Flygt Regional Service Manager.
xylem Let's Solve Water
STANDARD Xylem Water Solutions
Doc Type:
No:
Standard
FUS.0722.61
FUS.0726.12
Edition: 2
Date: 2014/3/17
Storage: G/Dom/Specsheets/Standard paint

TIKKURILA Coating: Flygt Standard Heavy Duty Paint


System
Technical Data Sheet

Description/Type: A chemical and corrosion resistant Coating System utilizing a epoxidized vegetable oil
binder and a polyester resin hardener. This coating produces excellent protection to metal in
immersion service. Especially cast iron when subject to corrosion, chemical and industrial
environments.

Typical Use: Heavy Duty Coating System for pump, valves, tanks, piping, etc. in submerged or non
submerged environments.

Primer: On Carbon Steel and Irons: An Acrylic Dispersion Zinc Phosphate water based primer used
on the interior and exterior where active corrosion protection is needed. Exterior surfaces to
be topcoated with multiple layers of Duasolid 50 Epoxy Topcoat.

Chemical Resistance: Excellent chemical resistance to wide range of acids, solvents and water solutions. (See
chart)
Exposure Immersion Splash & Spillaqe
Salt solutions Excellent Excellent
Suqar solutions Excellent Excellent
Aliphatic hydrocarbons Verv Good Verv Good
Waste water Excellent Excellent
Fresh water Excellent Excellent
Mineral Oils Excellent Excellent
Alkali solutions (stronq) Limited Exposure Verv Good
Acids (stronqj Limited Exposure Verv Good
Acids (weak) Very Good Very Good

Coating pH Range: This coating system will handle a pH range of 4.0 through 10 .

Temperature Non Immersion: Continuous 210° F


Resistance: Intermittent 260° F

Immersion: Temperature resistance depends on media coating is immersed in.


(Consult your Flygt Regional office for specific information.)
Colors: Primer: Red P/N 90 24 89 Topcoat: Navy Gray P/N 90 29 12
Finish: Satin Finish: Gloss

Surface Preparation: All surfaces of cast iron, cast steel and galvanized steel shall be cleaned with grease
emulsifying agents and then rinsed.

Parts shall be blasted to remove surface contaminants, rust and foreign particles shall be
removed thoroughly so that any residues appear only as a slight discoloration of the surface.
• Parts will be blown off with compressed air or with a clean brush
• Relative humidity of blast room shall be less than 50%
• Shop primer and any other foreign paints must be totally removed.
• Cast iron and steel shall be blasted with olivine sand or steel sand.
• Blasted part shall be kept at a relative humidity less than 50% before painting.

Page 1 of2
Printed in U.S.A.
xylem Let's Solve Water
STANDARD Xylem Water Solutions
Doc Type:
No:
Standard
FUS.0722.61
FUS.0726.12
Edition: 2
Date: 2014/3/17
Storage: G/Dom/Specsheets/Standard paint

• Blasted parts shall be painted within 6 hours after blasting.

Volatile Organic UNTHINNED THINNED 10% w/ Xylene


Compounds (VOC):
Grams/Liter Lbs./Gal. Grams/Liter Lbs./Gal.
150-300 1.25-2.50 300-450 2.50-3.75

Dry Film Thickness: Primer: 1 coat • max. 30 /j,m • max. 1.2 mils
Topcoat: 1 or more coats *120 jum / layer • 5mils / coat
Total System Dry Film Thickness: 150jum • 6 mils minimum

Cure time at 75°F To touch: 2 hours • To recoat: 1 hour • To handle: 6 hours • Immersion Service: 7 days

Mixing Ratio by Primer - Single component


Volume. Qoat _ywo component ,Two (Part A) to One (Part B)

Performance Criteria: Experiments were performed on Cast iron test panels painted with Duasolid Epoxy paint
system.
Lab. Tests:
• Cast iron test panels were blasted to Sa 21X» (SSPC-SP10) before painting
• The coated panels were emerged in a 3% sodium chloride solution (corresponding to
18,200 PPM chlorides).
• The solution was constantly aerated to ensure a high oxygen level.

• The panels were intentionally damaged after coating by making an “X” with a razor knife
on the coated surface. This was done to simulate mechanical damage to the coating.

Results:
Panels with Duasolid 50 and no primer had failed after 3 months.

Application Mixing Top Coat: Stir contents of each container, (Part A and Part B) making sure no
Information: pigment remains on the bottom. Pour Part A into Part B and agitate immediately.

Thinning: Use Xylene (Flygt P/N 90 21 82) to thin. Thin for air spray up to 10%.

Pot Life: 15hrsat50°F • 8 hrs at 77°F • 4 hrs. at 100°F

Application Equipment: Air spray, Airless spray, Brush or Roller


Clean Up Instructions: Clean all equipment immediately after use with the recommended thinner or a compatible
solvent such as Methyl Ethyl Ketone (MEK) flush and clean spray equipment before material
sets up.
Safety Information: This product contains solvents and other chemical ingredients. Adequate health and safety
precautions should be observed during storage, handling, application and curing. For
information regarding the potential hazards associated with this product, please refer to the
container label or contact the manufacturer.

Page 2 of2
Printed in U.S.A.
Shaft and bearing calculation chart
Project name: Mickey Leland International Terminal

Product: NP-3102/463 5.5hp/460/3

Calcs performed for a duty range of: 490 gpm @ 26’ TDH

Bearing life: Upper bearing (radial) L10aa = > 100,000 hrs


Lwr. bearing (radial/axial) L10aa = >100,000 hrs

Bearing life calculations made in accordance with SKF adjusted rating life, new theory, L10aa.
the specific product and version.
Adjustment factor for contamination is 0.5 (normal).
Viscosity of lubricant at 40° C is 95.0 mm2/s.
(Refer to appendix 1 for bearing life methodology and additional details.)

The shaft, hub coupling and seals are calculated and checked in accordance with Flygt-Xylem
standards. Refer to the attached appendix for the methodology for each individual parameter.

Critical speed

First natural frequency due to bending and torsion is more than 30% away from
exciting frequencies at actual speed.

Torsional and combined stresses

Maximum allowed stress limits are calculated for static and dynamic load cases and
compared with the a reduction curve in a Haigh fatigue diagram. A minimum 15%
margin is required. A minimum of 1 X 107 load change was used (indefinite life time).

Maximum allowable combined stress, in accordance to v. Mises is;


xt2 = 80N/mm2

Shaft deflection

Valid for Flygt standard M0344.2321.00 (ASTM/AISI 431 Martensitic Stainless Steel)

Maximum shaft deflection, at the seal position during normal duty, is less than
0.1 mm.

Date: 1/10/2024 Approved: Xylem Water Solutions- Flygt Products


axylembrand Issued: 7/17 Supersedes: 3/13

N-3102.060,070
Materials of Construction

Components Cast Iron Pump

Major Castings: Cast iron, A48, Class 35B

Pump Lifting Handle: Stainless steel

Motor Cable: Chloroprene rubber jacketed

Cable Entry Grommets: Nitrile rubber

Shaft: Stainless steel


ASTM A479 S43100-T

Impeller (Adaptive): Hard Iron™ (25 ASTM A-532 (Alloy


III A) 25% chrome cast iron).

Insert Ring Hard Iron™ (25 ASTM A-532 (Alloy


III A) 25% chrome cast iron)

O-Rings: Nitrile rubber or optional Viton

Lubricant Plug 316 Stainless steel

Screws, studs and nuts 316 Stainless steel

Inner Mechanical Shaft *Tungsten carbide/


Seal: *Tungsten carbide

Outer Mechanical Shaft *Tungsten carbide/


Seal: *Tungsten carbide

*AII corrosion and abrasion resistant


a xylem brand Issued: 9/15 Supersedes: 7/15

N Pump Design Features


(Typical features for N-3085 - 3127)

1. Cable Entry
Cable entry consists of a gland nut, cable strain relief, and
compressible rubber bushing, flanked by stainless steel
washers to seal off the motor area.

2. Junction Box
The cable entry junction chamber and motor are separated by
a stator lead sealing gland.

3. Bearings
Bearings are rated for a minimum L10 bearing life of 50,000
hours. The upper guide bearing is a single row ball bearing.
The lower bearing consists of a two-row angular contact ball
bearing. The bearings are sealed and permanently lubricated
with high temperature grease.

4. Shaft
Motor shaft and rotor are a single integral unit. The short fifty
.. i.j J
overhang of the shaft virtually eliminates shaft deflection,
resulting in increased seal and bearing life, low vibration levels
and quiet operation. Shaft is stainless steel.

5. Motor
(Standard or optional Premium Efficiency)
The high performance submersible induction motors are
designed and manufactured by Flygt to be used specifically
with Flygt pumps. Stators are Class FI insulated using the
trickle impregnation method and rated to 356°F. The stators
are shrink fit into the stator housing, providing superior heat
transfer. Optional premium efficiency motors meet the efficiency
levels specified in the IEC standard 60034-30 for international
efficiency, Class IE3. shape of the impeller inlet provides an inducing effect for the
Stators incorporate three thermal switches connected in series handling of up to 5% sludge and rag-laden wastewater. Pumps,
(one in each phase). A leakage sensor is available as an option equipped with the Adaptive N impeller, have impellers available
to detect water in the stator chamber. The Float Leakage Sensor in grey cast iron or duplex stainless steel (ASTM CD-4MCuN)
(FLS) is a small float switch used to detect the presence of and capable of momentarily moving axially upwards a distance
water in the stator chamber. When activated, the FLS will stop of 15mm/0.6-in. to allow larger debris to pass through and
the motor and send an alarm, both local and/or remote. immediately return to normal operating position. The impeller
to volute clearance is readily adjustable by means of a single
Cooling system trim screw. Wear rings are not required.
In wet-pit applications, the surrounding liquid cools the pump.
8. Volute/Suction Cover
6. Shaft Seals Pump volute is of grey cast iron, Class 35B, non-concentric
Two sets of mechanical seals operate independently of each design with smooth passages large enough to pass any solids
other. This design provides superior reliability and sealing of that may enter the volute inlet. The volute has a replaceable
the motor from pumped liquid. suction cover insert ring in which are cast spiral-shaped, sharp-
edged groove(s). The spiral groove(s) provide trash release
7. Impeller pathways and sharp edge(s) across which each impeller
The standard N impeller is of grey iron. Select impellers are vane leading edge shall cross during rotation so to remain
available in Hard-Iron® (25% chrome cast iron), dynamically unobstructed. The insert ring for use with grey iron and stainless
balanced, semi-open, multi-vane, back swept, screw-shaped, steel impellers has a guide pin integral to the casting and is
non-clog design. The impeller leading edges are mechanically cast of ASTM A-48, Class 35B grey iron or Hard-Iron, when
self-cleaned automatically upon each rotation as they pass used with select Hard-Iron impellers and provides effective
across a spiral groove located on the volute suction area. sealing between the multi-vane semi-open impeller and the
The screw-shaped leading edges of the grey iron impeller volute housing.
are hardened to Rc 45, Hard-Iron impellers to Rc 60 and are
capable of handling solids, fibrous materials, heavy sludge
and other matter normally found in wastewater. The screw
NP 3102 MT3~ Adaptive 463
Patented self cleaning semi-open channel impeller, ideal for pumping in
waste water applications. Modularbased design with high FLYGT
adaptation grade.
a xylem brand

Technical specification
Curves according to: Water, pure Water, pure [100%],39.2 °F,62.42 lb/ft3,1.6891E-5 ft2/ s

Nominal (mean) data shown. Under- and over-perfoimance from this data should
be expected due to standard manufacturing tolerances.
Configuration Please consult your local Flygt representative for performance guarantees.

Motor number Installation type


N3102.920 18-11-4AS-W P - Semi permanent, Wet
IE3 5.5hp
Impeller diameter Discharge diameter
172 mm 4 inch

Pump information Material

Impeller diameter Impeller


172 mm Hard-Iron ™

Discharge diameter Stator housing material


4 inch Grey cast iron

Inlet diameter
100 mm

Maximum operating speed


1800 rpm

Number of blades
2

Max. fluid temperature


40 °C

Project Xylect-21683962 Created by Eric Prescott


Block Created on 1/11/2024 Last update 1/11/2024

FVogram version Date version Usergroup(s)


71.0 - 12/18/2023 (Buld 91) 12/14/2023 922 A12P12 )fylem:USA- EXT
NP 3102 MT 3~ Adaptive 463
Technical specification

Motor - General axylem brand

Motor number Phases Rated speed Rated power


N3102.920 18-11-4AS-W 3~ 1800 rpm 5.5 hp
IE3 5.5hp
ATEX approved Number of poles Rated current Stator variant
No 4 6.2 A 1

Frequency Rated voltage Insulation class Type of Duty


60 Hz 460 V H SI

Version code
920

Motor - Technical

Power factor -1/1 Load Motor efficiency -1/1 Load Total moment of inertia Starts per hour max.
0.90 91.9 % 0.612 lb ft2 30

Power factor - 3/4 Load Motor efficiency-3/4 Load Starting current, direct starting
0.86 91.5% 42 A

Power factor -1/2 Load Motor efficiency-1/2 Load Starting current, star-delta
0.75 90.1% 14 A

Project Xylect-21683962 Created by Eric Prescott


Block Created on 1/11/2024 Last update 1/11/2024

FYogram version Dab version Usergroup(s)


71.0 - 12/18/2023 (Buid 91) 12/14/2023 922 A12P12 tylentUSA- EXT
NP 3102 MT 3~ Adaptive 463
Performance curve

Duty point a xylem brand

Flow Head
511 US g.p.m. 26.3ft

Curves according to: Water, purdMater, pure [100%],39.2 °F,62.42 Ib/ft3,1.6891E-5 ft2/s

Created on 1/11/2024 Last update 1/11/2024

Program version Dab version Usergroup(s)


71.0 - 12/18/2023 (Buid 91) 12/14/2023 922 A12P12 Xylem: USA- EXT
NP 3102 MT 3~ Adaptive 463
Duty Analysis
FLYGT

a xylem brand
Curves according to: Water, pure [100%]; 39.2°F; 62.42lb/ft3; 1.6891E-5ft2/s

—I----- 1- ---- 1----- 1----- 1----- 1- ---- 1----- 1----- 1----- ------ 1----- 1- ---- 1----- 1- ---- 1----- 1- ---- 1----- 1----- 1- ---- 1----- 1----- 1----- 1- - - - - - 1- ---- 1- ---- 1----- 1- - - - - - 1- ---- ------ 1- ---- 1----- 1----- 1- ---- 1- ---- 1----- 1- ---- 1- ---- 1----- 1- - - - - - 1- ---- 1----- 1- ---- 1- ---- 1----- 1----- 1- ---- 1- ---- r-

0 100 200 300 400 500 600 700 800 [USg.p.m.]


Nominal (mean) data shown. Under- and over-performance from this data should be erpected due to standard manufacturing tolerances.
Please consult your local Flygt representative for performance guarantees.
Operating characteristics

Pumps / Flow Head Shaft power Flow Head Shaft power Hydr.eff. Spec Energy NPSHre
Systems
US g.p.m.ft_ hpUS g.p.m.ft_ hpkWh/US MG ft
1 511 26.3 4.92 511 26.3 4.92 69 % 130 16.7

Project Created by Eric Prescott


Block Xylect-21683962 Created on 1/11/2024 Last update 1/11/2024

FVogram version Dab version Usergroup(s)


71.0 - 12/18/2023 (Buld 91) 12/14/2023 922 A12P12 XylemiUSA- EXT
moo
CD r-

mioo
^1"

ro
* Only applicable for
intermittent duty.
(D Consult the IOM for
C
more info.
Q)
■+-*
£= Weight Pump
CD Disch
(J VIEW Z lbs 240 80
-M
CD 04" Scale Date
NP 3102 MT 04" 1:10 230629
=5
o 060,070,160,190,760,770,900,910,920,930,960,970
Drawhg number

6602300
FLYGT
a xylem brand Issued: 4/14 Supersedes: 2/12

Standard CP/NP Discharge Connections (Cast Iron)

All dimensions (inches)

Pump Part Disch. Disch.


Number Inlet Outlet
A B c D E F G H I J K
Model
2" - 3045, 3057, 486 55 01 2" 2"-11 1/2 NPT 3 13/16 4 4 1/2 5 1/2 7 1/4 6 3/4 3 15/16 7/8 — ... ...

CP/DP/FP-3068.

2 1/2" - DP/FP-3068. 493 17 06 2 1/2" 2 1/2" 11 5/8 7 7/8 4 3/4 7 7/8 11 7/16 9 7/8 6 1/2 4 9/16 45° 90° x 4 5 5/8

3" - 3045, 3057, 555 48 01 2" 3-8 NPT 6 3/4 5 1/2 4 1/8 5 1/2 10 3/4 6 3/4 3 15/16 7/8 ... ... ...

CP-3068.

3" - DP-3068, 3080, 444 68 05 3" 3" 14 9 7/8 8 10 5/8 15 3/8 15 3/4 7 7/8 4 9/16 45° 90° x 4 6
3085, 3102,
3127, 3153.

4" - 3080, 3085,


3102,3127, 540 13 05 4" 4" 14 3/8 9 7/8 8 10 5/8 15 3/8 15 3/4 7 7/8 4 9/16 22.5° 45° x 8 7 1/2
3153,3171,
3202.

6" -3102,
3127(MT), 444 70 06 5 1/2" 6" 15 9/16 11 10 12 3/16 15 3/8 17 3/4 9 7/8 4 9/16 22.5° 45° x 8 9 1/2
3153, 3171.

6" -3153, 3171, 602 33 06 5 1/2" 6" 15 9/16 11 10 12 3/16 15 15/16 17 3/4 9 7/8 4 9/16 22.5° 45° x 8 9 7/16
3202.

6" - R3231 388 25 06 6" 6" 20 11/16 19 3/4 15 3/4 19 3/4 23 5/8 15 3/4 7 7/8 6 7/8 22.5° 45° x 8 9 7/16
6" - 3127(LT), 3301, 604 56 06 6" 6" 15 9/16 11 1/8 10 12 3/16 15 15/16 18 10 1/8 4 9/16 22.5° 45° x 8 9 7/16
3315.
Note: Alternative discharge connections may be available, contact Flygt Application Engineering.

Caution:
Contact Flygt applications engineering
department when making a pump/
discharge connection combination other
than those paired in the chart above.

Note:
The discharge connection shown here
is typical in appearence for most pumps.
a xylem brand Issued: 11/11 Supersedes: 2/09
682017D

CP/DP/NP-3102
O NOTES:
1. CONFIGURATION AND DIMS. SHOWN ARE SUGGESTED 3. LOCATE ANCHOR BOLTS USING INSIDE EDGE OF
REQUIREMENTS ONLY. ALL DETAILS, INCLUDING CLEAR OPENING AND PUMP CENTERLINE AS
SIZING OF PIT, TYPE, LOCATION AND ARRANGEMENT REFERENCE POINT. BOLT LOCATIONS MUST BE HELD
OF VALVES AND PIPING, ETC. ARE TO BE SPECIFIED TO MAINTAIN EXACT POSITION OF PUMP TO CLEAR
BY THE CONSULTING ENGINEER AND ARE SUBJECT OPENING.
TO THEIR APPROVAL. 4. FLYGT MIX-FLUSH VALVE.
2. REFERENCE GENERIC DUPLEX LIFT STATION LAYOUT
FOR ELEVATION VIEW.

Duplex qpiT

PIT
BASE SECTION

ALL DIMENSIONS ARE IN INCHES

MODEL
NOM.
VERSION
s MP LEX DUPLEX
A B c D s T U V w Y S T u PL V w Y
SIZE
CP/NP 3” HT/SH 21 9^ 8 4 15| 9* 60 17 26* 28* 19| 13* 72 9 26 44* 28*
CP/DP/NP 4” MT 2i 9^ 8 4 13* 7i 60 17 26* 28* 17* 11 72 9 26 44* 28* |

CP/NP 4” LT 2i 9^ 8 4 13* n 60 16 25* 28* 17* 11 72 9 25 43* 28*


CP/NP 6" LT 4} 11 10 5 11 60 17* 27 28* 14$ 6* 72 9 26* 45 28*

CP 8” LT 5* 11 10 5 81 0 60 17* 27 28* 118 2* 72 9 26* 45 28*


a xylem brand Issued: 10/13 Supersedes: 9/13

Power Cable
3000 Series Pumps*

Max. Cable
Pump Cable Size/ Part No. of
Length
Model HP Volts 0 Nominal O.D. Number Cables
(Ft)

3102 5.0
A 200 3 4G2.5+2x1.5 94 20 59 1 80
Y// 230 3 0.69"-(17.5 mm) 1 110
Y/SER 460 3 *S3x2.5+3x2.5/3+S(4x0.5) 94 19 90 1 440
0.75"-(19.0mm)
A 575 3 1 685

5.5
A 200 3 4G4+2x1.5 94 20 60 1 125
0.83"-(21.0mm)
*S3x6+3x6/3 + S(4x0.5) 94 19 91
0.83"-(21.0mm)

Y// 230 3 4G2.5+2x1.5 94 20 59 1 110


Y/SER 460 3 0.69"-(17.5 mm) 1 435
A 575 3 *S3x2.5+3x2.5/3+S(4x0.5) 94 19 90 1 680
0.75"-(19.0mm)

3.9 230 1 4G6+2X1.5 94 20 56 1 175


0.94"-(24.0 mm)
*S3x6+3x6/3+S(4x0.5) 94 19 91
0.83"-(21.0mm)

*Optional Shielded Cable - Use with SmartRun™ intelligent controls. Note: Shielded cable max. lengths
and number of cables are the same
See page 1 for break down of conductors used in one cable. as standard cable.
Stainless Chain & Bow Shackle Compatability Size Chart
Chain Size Actual Link ID. WL (lbs) Shackle size Max pin diameter WLL (lbs) WLL for the set (lbs)
3/16" 0.315” 1200 3/16” 0.187” 520 520
3/16" 0.315" 1200 1/4” 0.25" 930 930
1/4" 0.365” 2000 5/16” 0.31” 1375 1375

5/16" 0.47” 2800 3/8” 0.375” 2365 2365

1/2" 0.78” 6500 5/8” 0.625” 5500 5500


5/8" 0.795” 9500 5/8” 0.625” 5500 5500
5/8" 0.795” 9500 3/4” 0.75” 7700 7700
3/4" 1.10" 15000 7/8” 0.875” 8000 8000
1" 1.24” 23250 1" 1” 10000 10000
1" 1.24" 23250 1-1/8” 1.125” 12000 12000

NACM Specifications Stainless Steel High Strength T-316 Chain


Trade Size Material Dia Material Dia Working Load Min Breaking Inside Length Inside Width Wgt / Per ft
inch mm inch lbs lbs inch inch lbs
1/8" 4 0.156 500 2,000 0.94 0.25 0.198
3/16" 5.5 0.218 1,200 4,800 0.98 0.3 0.4
/VV7C nnn (HW1

5/16" 8 0.315 2,800 11,200 1.29 0.44 0.96

' *»-----
1/2" 13 0.512 6,500 26,000 1.79 0.72 2.42
5/8' 16 0.63 9,500 38,000 2.2 0.79 3.57
3/4" 20 0.75 15,000 60,000 2.76 0.98 5.6
1" 26 1 23,250 93,000 3.49 1.24 9.24

T-316 Stainless Bow Shackles


Size Pin Dia Inside Length Opening Over-all Length WLL
3/16” .187" 1.00” .40” 1.50” 660lbs
1/4" .250” 1.20” .50” 1.80" 930lbs

3/8" 0.375 1.83” .84” 2.75” 2365lbs

5/8" .625” 2.85" 1.25” 4.45” 5500lbs


3/4" .750” 3.34” 1.40” 5.10” 7700lbs
7/8" .875” 3.70” 1.60” 5.85” 8000lbs
r .925” 4.16" 1.96” 6.625” 10,000lbs
1-1/8" 1.125” 4.96” 2.21” 7.22” 12,000lbs
9 1/4 I.D. BAR
5 1/8 I.D. BAR
01/2 ROD X
01/2 ROD X
27 1/2 LG. (OPTIONAL)
16 7/8 LONG
(OPTIONAL)
7 1/8 I.D. BAR
01/2 ROD X
22 LG. (OPTIONAL)

L2 X 2 X 1/4 - 12 7/8” LG.

L2 X 2 X 1/4 - 7 3/4” LG. HA


11 15/16 lu
' cr

l-k \ I / £3 7 1/8
01/2”-
"An
l!

1 1/2” SCH 40 PIPE

2” SCH 40 PIPE - 2” LG.

12 7/8
1 9/16 9 3/4 09/16 HOLES
2 5/8 7 5/8 NOTE:
3 5/8 5 5/8 1- MATERIAL: 316 STAINLESS STEEL
7/8 2- APPROXIMATE WEIGHT: 12 LBS.
£
r ■\ r •s (
T]r N V Nr Nr Np INTERPRET DIMENSIONS AND
TOLERANCES PER ASME Y14.5M
o
U.S.F. FABRICATION INC.
BREAK ALL SHARP CORNERS
° UJ HIALEAH, FLORIDA
& EDGES TO 0.01 ©£
TOLERANCES UNLESS
UNIVERSAL, INTERMEDIATE GUIDE BAR BRACKE
OTHERWISE SPECIFIED: PJ o FOR 4”, )6” & 8” D.l. PIPE W/. 2” RAILS
ol
THIS DOCUMENT IS THE PROPERTY OF U.S.F. FABRICATION, INC AND CONTAINS INCHES = ± 1/16
PROPRIETARY INFORMATION. IT SHALL NOT BE MODIFIED, COPIED, FURNISHED NOR DISTRIBUTED
o
o d
,
1=4 1 of 1 DA1Ei3/ 4/1 6
1/16 = ± 1/32 C APP'D BY: SHEET n
(IN WHOLE OR IN PART) WITHOUT PROPER AUTHORIZATION OF U.S.F. FABRICATION. INC. SIZE: B
1/32 = ± 1/64 ICF 1000002287
NOTE:
1- MATERIAL: 316L STAINLESS STEEL
2- APPROXIMATE WEIGHT: 17 LBS.

INTERPRET DIMENSIONS AND


TOLERANCES PER ASME Y14.5M U.S.F. FABRICATION INC.
BREAK ALL SHARP CORNERS
(((k HIALEAH, FLORIDA
1 12/1/15 DA V DAV UPDATED FORMAT & MODIFIED B.O.M. FOR FAB. & EDGES TO 0.01
TOLERANCES UNLESS
S.S. CABLE HOLDER
REV. DATE BY CHK. DESCRIPTION
OTHERWISE SPECIFIED: CH CD 6 X 18 X 1/2
THIS DOCUMENT IS THE PROPERTY OF U.S.F. FABRICATION, INC AND CONTAINS INCHES = ± 1/16
rv'
DRAWN BY: j |^| SCALE: * A
1 =4
SHEET: . 0
1 of 2 DATC: 04/29/14
PROPRIETARY INFORMATION. IT SHALL NOT BE MODIFIED, COPIED, FURNISHED NOR DISTRIBUTED 1/16 = ± 1/32
N°: -| 000002331
(IN WHOLE OR IN PART) WITHOUT PROPER AUTHORIZATION OF U.S.F. FABRICATION, INC. APP’D BY: ... SHEET p. REV: .
1/32 = ± 1/64 JM DW<3.
SIZE: B 1