Series DS-8 – 8.0 K-factor, Dry-Type Sprinklers


Pendent and Horizontal Sidewall
Quick Response, Standard Coverage
Use the sprinklers in wet-pipe, dry-
IMPORTANT pipe, or preaction systems based on
Refer to Technical Data Sheet the following criteria:
TFP2300 for warnings pertaining to
regulatory and health information. • On dry pipe systems that are
exposed to freezing temperatures,
Always refer to Technical Data for example, sprinkler drops from
Sheet TFP700 for the “INSTALLER unheated portions of buildings
WARNING” that provides cautions
with respect to handling and instal- • When sprinklers and/or a portion
lation of sprinkler systems and com- of the connecting piping may be
ponents. Improper handling and exposed to freezing tempera-
installation can permanently damage tures, for example, sprinkler drops
a sprinkler system or its compo- from wet systems into freezers,
nents and cause the sprinkler to fail sprinkler sprigs from wet systems
to operate in a fire situation or cause into unheated attics, or horizontal
it to operate prematurely. piping extensions through a wall to
protect unheated areas of a building
such as loading docks, overhangs,
Scan the QR code or enter the URL and building exteriors
in a web browser to access the most • On systems that are season-
up-to-date electronic version of this ably drained to avoid freezing, for
Technical
document. Data rates may apply. example, vacation resort areas

NOTICE Data
The TYCO Series DS-8 Dry-Type Sprin-
klers described herein must be installed Approvals
and maintained in compliance with this UL and C-UL Listed
document, as well as with the applica- Note: For more information, see Table A and
ble standards of the NATIONAL FIRE Table B.
PROTECTION ASSOCIATION (NFPA), Maximum Working Pressure
in addition to the standards of any other 175 psi (12,1 bar)
authorities having jurisdiction. Failure
to do so may impair the performance Inlet Thread Connections
of these devices. 1 in. NPT
ISO 7-R 1
The owner is responsible for main-
docs.jci.com/tycofire/tfp513 Discharge Coefficient
taining their fire protection system
and devices in proper operating con- K=8.0 gpm/psi½ (115,2 lpm/bar½)

General dition. Contact the installing contrac-


tor or product manufacturer with any
Temperature Ratings
See Table A and Table B
Description questions.
Series DS-8 Dry-Type Sprinklers must
Finishes
Sprinkler: See Table D
TYCO Series DS-8 8.0 K-factor Pendent only be installed in fittings that meet Escutcheon: See Table D
and Horizontal Sidewall (HSW), Quick the requirements of the Design Crite-
Response (3 mm bulb), Standard Cov- ria section. Physical Characteristics
Inlet �������������������������������������������������������������Brass
erage Dry-Type Sprinklers are dec-
Sprinkler
Plug �������������������������������������������������������������Brass
orative glass bulb, stainless steel, Yoke. . . . . . . . . . . . . . . . . . . . . . . . Stainless Steel
automatic sprinklers listed by UL and Casing. . . . . . . . . . . . . . Galvanized Carbon Steel
C-UL. The quick response bulb size is
3 mm. For information about the Series Identification Bulb Seat �������������������������������������� Stainless Steel
Bulb (3 mm dia.) ����������������������������������������� Glass

Number (SIN)
Compression Screw �����������������������������������Brass
DS-8 Standard Response (5 mm bulb) Deflector ���������������������������������������������������Bronze
sprinklers, see technical data sheet Frame ���������������������������������������������������������Brass
TFP503. TY4235 ���������������������������������Pendent Guide Tube ���������������������������������� Stainless Steel
TY4335 ���������������Horizontal Sidewall Water Tube ���������������������������������� Stainless Steel
Spring. . . . . . . . . . . . . . . . . . . . . . Stainless Steel
Sealing Assembly. . Beryllium Nickel w/TEFLON
Escutcheon. . . . . . Brass Plated, Chrome Plated
Polyester, or Stainless Steel

Page 1 of 8 AUGUST 2023 TFP513


TFP513
Page 2 of 8

Sprinkler Escutcheon Temperature Bulb Sprinkler Finish


Type Type Rating Liquid Color Natural Brass Chrome Plated Polyester
135°F (57°C) Orange
155°F (68°C) Red
Standard 175°F (79°C) Yellow 1, 2 1, 2
200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
155°F (68°C) Red
Recessed 175°F (79°C) Yellow 1, 2 1, 2
200°F (93°C) Green

Pendent 286°F (141°C) Blue


(TY4235) 135°F (57°C) Orange
155°F (68°C) Red
Deep 175°F (79°C) Yellow 1, 2 1, 2
200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
155°F (68°C) Red
Without 175°F (79°C) Yellow 1, 2 1, 2
200°F (93°C) Green
286°F (141°C) Blue
NOTES
1. Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 in. 2. Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 in.
TABLE A
SERIES DS-8 DRY-TYPE SPRINKLERS, 8.0K, PENDENT, QUICK RESPONSE
LABORATORY LISTINGS AND APPROVALS

Sprinkler Escutcheon Temperature Bulb Sprinkler Finish


Type Type Rating3 Liquid Color Natural Brass Chrome Plated Polyester
155°F (68°C) Red
Standard 200°F (93°C) Green 1, 2 1, 2
286°F (141°C) Blue
155°F (68°C) Red
Recessed 200°F (93°C) Green 1, 2 1, 2
Horizontal 286°F (141°C) Blue
Sidewall
(TY4335) 155°F (68°C) Red
Deep 200°F (93°C) Green 1, 2 1, 2
286°F (141°C) Blue
155°F (68°C) Red
Without 200°F (93°C) Green 1, 2 1, 2
286°F (141°C) Blue
NOTES
1. Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 in. 2. Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 in.

TABLE B
SERIES DS-8 DRY-TYPE SPRINKLERS, 8.0K, QUICK RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP513
Page 3 of 8

PLUG WITH INLET


SEALING
ASSEMBLY
WRENCH
PLUG RECESS
SPRING
YOKE

INLET
CASING BAND WRENCH
FLAT

GUIDE WATER
TUBE TUBE PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
3 mm BULB BULB
WRENCHING AREA
SEAT
FIGURE 3
W-TYPE 7
FRAME WRENCH
VENT HOLE

Temperatures for
COMPRESSION Heated Area(1)
SCREW DEFLECTOR Ambient
Temperature 40°F 50°F 60°F
FIGURE 1 Exposed to (4°C) (10°C) (16°C)
SERIES DS-8 PENDENT DRY-TYPE SPRINKLER, 8.0K, Discharge
QUICK RESPONSE ASSEMBLY End of Minimum Exposed
Sprinkler Barrel Length(2),
in.
(mm)
INLET YOKE INLET WATER CASING BULB VENT DEFLECTOR
BAND TUBE SEAT HOLE 40°F 0 0 0
(4°C)
30°F 0 0 0
(-1°C)
20°F 4 0 0
(-7°C) (100)
10°F 8 1 0
(-12°C) (200) (25)
0°F 12 3 0
PLUG WITH PLUG GUIDE FRAME 3 mm COMPRESSION (-18°C) (305) (75)
SEALING SPRING TUBE BULB SCREW -10°F 14 4 1
ASSEMBLY (-23°C) (355) (100) (25)
FIGURE 2 -20°F 14 6 3
SERIES DS-8 HORIZONTAL SIDEWALL DRY-TYPE SPRINKLER, 8.0K, (-29°C) (355) (150) (75)
QUICK RESPONSE ASSEMBLY
-30°F 16 8 4
(-34°C) (405) (200) (100)
Operation The glass bulb contains a fluid that
expands when exposed to heat. When -40°F 18 8 4
When TYCO Series DS-8 8.0K Pendent the rated temperature is reached, the (-40°C) (455) (200) (100)
and Horizontal Sidewall, Quick fluid expands sufficiently to shatter -50°F 20 10 6
Response, Standard Coverage Dry- the glass bulb, and the bulb seat is (-46°C) (510) (255) (150)
Type Sprinklers are in service, water is released.
-60°F 20 10 6
prevented from entering the assembly Once the bulb seat is released, the (-51°C) (510) (255) (150)
by the plug with sealing assembly as compression holding the sealing
shown in Figure 1 and Figure 2 in the assembly is released. The spring is Notes:
1. For protected area temperatures that occur
inlet of the sprinkler. then able to flip off to the side and out between values listed above, use the next cooler
of the waterway. This action pushes the temperature.
water tube as well as the guide tube 2. These lengths are inclusive of wind velocities up
to 30 mph (18,6 kph).
outward. This action allows the sprin-
kler to activate and water to flow. TABLE C
EXPOSED SPRINKLER BARRELS
IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED
LENGTHS
TFP513
Page 4 of 8

Design SPRINKLER FITTING


(REFER TO DESIGN
SPRINKLER FITTING
(REFER TO DESIGN
Criteria CRITERIA SECTION) CRITERIA SECTION)

TYCO Series DS-8 8.0K Pendent and FACE OF FACE OF


Horizontal Sidewall, Quick Response, SPRINKLER SPRINKLER
Standard Coverage Dry-Type Sprin- FITTING FITTING
klers are intended for use in fire sprin-
kler systems designed in accordance
with the standard installation rules ORDER LENGTHS: ORDER LENGTHS:
recognized by the applicable listing 2-3/4" to 48" 1-3/4" DIA. 3-3/4" to 48"
or approval agency. For example, (69,9 to 1219,2 mm) (44,5 mm) (95,3 to 1219,2 mm)
the UL Listing is based on NFPA 13 IN 1/4" (6,4 mm) IN 1/4" (6,4 mm) 2-1/4" DIA.
requirements. INCREMENTS INCREMENTS (57,2 mm)

Sprinkler Fittings FACE OF


Install 1 in. NPT Series DS-8 Dry-Type CEILING
Sprinklers in the 1 in. NPT outlet or run FACE OF
of the following fittings: CEILING

• Malleable or ductile iron threaded


tee fittings that meet the dimen-
3" DIA. 2-7/8" DIA.
sional requirements of ANSI B16.3 2-3/16" ± 1/8" 1-3/8" ± 1/8"
(76,2 mm) (73,0 mm)
(Class 150) (55,6 ± 3,2 mm) (34,9 ± 3,2 mm)
• Cast iron threaded tee fittings that FIGURE 5
meet the dimensional requirements FIGURE 4 PENDENT
of ANSI B16.4 (Class 125) PENDENT WITH STANDARD
WITH STANDARD ESCUTCHEON RECESSED ESCUTCHEON
Do not install sprinklers into elbow
fittings. The inlet of the sprinkler can
contact the interior of the elbow. SPRINKLER FITTING SPRINKLER FITTING
The unused outlet of the threaded tee is (REFER TO DESIGN (REFER TO DESIGN
plugged as shown in Figure 13. CRITERIA SECTION) CRITERIA SECTION)

You can also install Series DS-8 Dry- FACE OF FACE OF


Type Sprinklers in the 1 in. NPT outlet SPRINKLER SPRINKLER
of a GRINNELL Figure 730 Mechanical FITTING FITTING
Tee and GRINNELL G-FIRE Figure 522;
however, the use of the Figure 730 Tee
and Figure 522 for this arrangement is ORDER LENGTHS: 3-1/2" DIA.
limited to wet pipe systems. 3/4" to 46" (88,9 mm) ORDER LENGTHS:
(19,1 to 1168,4 mm) 5-1/4" to 48"
The configuration shown in Figure 9 is 2-1/2" DIA.
IN 1/4" (6,4 mm) (133,4 to 1219,2 mm)
only applicable for wet pipe systems (63,5 mm)
INCREMENTS IN 1/4" (6,4 mm)
where the sprinkler fitting and water- INCREMENTS
filled pipe above the sprinkler fitting
are not subject to freezing and where FACE OF
the length of the dry-type sprinkler has CEILING
the minimum exposure length depicted MINIMUM
in Figure 12. See the Exposure Length 4-1/4" ± 1/8" 1-3/4" (44,5 mm)
section. (108,0 ± 3,2 mm) DEFLECTOR
TO CEILING
For wet pipe system installations of
1 in. NPT Series DS-8 Dry-Type Sprin-
klers connected to CPVC piping, use FIGURE 6 FIGURE 7
only the following TYCO CPVC fittings: PENDENT PENDENT
• 1 in. x 1 in. NPT female adapter WITH DEEP ESCUTCHEON WITHOUT ESCUTCHEON
(P/N 80145)
• 1 in. x 1 in. x 1 in. NPT sprinkler head
adapter tee (P/N 80249)
For dry pipe system installations,
use only the side outlet of maximum
2 1/2 in. reducing tee when locat-
ing Series DS-8 Dry-Type Sprinklers
directly below the branchline; other-
wise, use the configuration shown in
Figure 13 to assure complete water
drainage from above Series DS-8
Dry-Type Sprinklers and the branch-
line. Failure to do so may result in pipe
freezing and water damage.
TFP513
Page 5 of 8

NOTICE ORDER LENGTHS:


2-3/4" to 48" (69,9 to 1219,2 mm) 2-3/16" ± 1/8"
Do not install Series DS-8 Dry-Type (55,6 ± 3,2 mm)
Sprinklers into any other type fitting IN 1/4" (6,4 mm) INCREMENTS
without first consulting the JOHNSON 1/2"
FACE OF FACE OF (12,7 mm)
CONTROLS INC. (JCI) Technical Ser- SPRINKLER MOUNTING
vices. Failure to use the appropriate FITTING SURFACE
fitting may result in one of the following:
• Failure of the sprinkler to operate 3" DIA.
properly due to formation of ice over (76,2 mm)
the inlet plug or binding of the inlet
plug.
SPRINKLER FITTING
• Insufficient engagement of the (REFER TO DESIGN 1-3/4" DIA.
CENTERLINE
Inlet pipe-threads with consequent (44,5 mm)
CRITERIA SECTION) OF WATERWAY
leakage
FIGURE 8
Drainage HORIZONTAL SIDEWALL WITH STANDARD ESCUTCHEON
In accordance with the minimum
requirements of the NATIONAL FIRE
PROTECTION ASSOCIATION for dry ORDER LENGTHS:
3-3/4" to 48" (95,3 to 1219,2 mm) 1-3/8" ± 1/8"
pipe sprinkler systems, branch, cross, (34,9 ± 3,2 mm)
and feed-main piping connected to IN 1/4" (6,4 mm) INCREMENTS
1/2"
dry-type sprinklers and subject to FACE OF FACE OF (12,7 mm)
freezing temperatures must be pitched SPRINKLER MOUNTING
for proper drainage. FITTING SURFACE
Exposure Length
When using dry-type sprinklers in 2-7/8" DIA.
wet pipe sprinkler systems to protect (73,0 mm)
areas subject to freezing temperatures,
use Table C to determine a sprinkler’s
appropriate exposed barrel length to SPRINKLER FITTING
(REFER TO DESIGN 2-1/4" DIA.
prevent water from freezing in the con- (57,2 mm) CENTERLINE
necting pipes due to conduction. The CRITERIA SECTION) OF WATERWAY
exposed barrel length measurement FIGURE 9
must be taken from the face of the HORIZONTAL SIDEWALL WITH STANDARD RECESSED ESCUTCHEON
sprinkler fitting to the surface of the
structure or insulation that is exposed
to the heated area as shown in Figure ORDER LENGTHS:
1/2" to 45-3/4" (12,7 to 1162,1 mm) 4-1/4" ± 1/8"
12. (108,0 ± 3,2 mm)
IN 1/4" (6,4 mm) INCREMENTS
For protected area temperatures 1/2"
between those given on the next FACE OF FACE OF (12,7 mm)
page, the minimum recommended SPRINKLER MOUNTING
length from the face of the fitting to the FITTING SURFACE
outside of the protected area may be
determined by interpolating between 3-1/2" DIA.
the indicated values. (88,9 mm)
Clearance Space
In accordance with NFPA 13, when
SPRINKLER FITTING
connecting an area subject to freez- (REFER TO DESIGN 2-1/2" DIA.
CENTERLINE
ing and an area containing a wet pipe CRITERIA SECTION)
(63,5 mm)
OF WATERWAY
sprinkler system, the clearance space
around the sprinkler barrel of dry-type FIGURE 10
sprinklers must be sealed. Due to tem- HORIZONTAL SIDEWALL WITH DEEP ESCUTCHEON
perature differences between two
areas, the potential for the formation 5-1/2" to 48" (139,7 to 1219,2 mm)
of condensation in the sprinkler and ORDER LENGTHS: IN 1/4" (6,4 mm) INCREMENTS
subsequent ice build-up is increased. If
this condensation is not controlled, ice FACE OF MINIMUM 2-1/4" (57,2 mm)
build-up can occur that might damage SPRINKLER DEFLECTOR TO MOUNTING
the dry-type sprinkler and/or prevent FITTING SURFACE
proper operation in a fire situation.
Use of the Model DSB-2 Dry-Type
Sprinkler Boot, as described in techni-
cal data sheet TFP591, and as shown 1/2"
in Figure 15 and Figure 16, can provide SPRINKLER FITTING CENTERLINE (12,7 mm)
the recommended seal. (REFER TO DESIGN CRITERIA SECTION) OF WATERWAY
FIGURE 11
HORIZONTAL SIDEWALL WITHOUT ESCUTCHEON
TFP513
Page 6 of 8

RUN 1-3/4" DIA.


FACE OF OUTLET (44,5 mm)
SPRINKLER PLUGGED CLEARANCE INSULATED
HOLE FREEZER
FITTING SPRINKLER
ADHESIVE STRUCTURE
FITTING
HEATED EXPOSURE TO DRY (SEE DESIGN
AREA LENGTH SYSTEM DSB-2
CRITERIA
(SEE DESIGN SECTION) BOOT
DSB-2 CRITERIA AREA
INTENDED SECTION) SUBJECT DSB-2
FOR FREEZER TO INTENDED
STRUCTURES FREEZING FOR FREEZER
STRUCTURES

STRAP TIES
DS-8
(ENDS ON
SHOWN WITH
OPPOSING
STANDARD
SIDES OF
ESCUTCHEON
FIGURE 13 BOOT)
FIGURE 12 SPRINKLER FITTING FIGURE 16
EXPOSURE LENGTH UNHEATED AREA MODEL DSB-2 DRY SPRINKLER
BOOT WITH HORIZONTAL
STRAP TIES SIDEWALL SERIES
(ENDS ON DS-8 DRY-TYPE SPRINKLER
TO WET SIDE
SYSTEM OUTLET OPPOSING
PLUGGED
SIDES OF
BOOT) Installation
HEATED TYCO Series DS-8 8.0K Pendent and
DSB-2 BOOT
AREA Horizontal Sidewall, Quick Response,
ADHESIVE Standard Coverage Dry-Type Sprin-
SPRINKLER klers must be installed in accordance
DSB-2 1-3/4" DIA.
FITTING with this section.
INTENDED (44,5 mm)
(SEE DESIGN
FOR FREEZER CLEARANCE General Instructions
STRUCTURES CRITERIA HOLE
SECTION) Series DS-8 Dry-Type Sprinklers must
only be installed in fittings that meet
INSULATED
the requirements of the Design Cri-
FREEZER
STRUCTURE
teria section. See the Design Criteria
section for other important require-
DS-8 ments regarding piping design and
SHOWN WITH sealing of the clearance space around
STANDARD the sprinkler casing.
ESCUTCHEON
Do not install any bulb-type sprinkler
FIGURE 15 if the bulb is cracked or there is a loss
FIGURE 14 MODEL DSB-2 DRY SPRINKLER of liquid from the bulb. With the sprin-
SPRINKLER FITTING BOOT WITH PENDENT SERIES kler held horizontally, a small air bubble
HEATED AREA DS-8 DRY-TYPE SPRINKLER should be present. The diameter of the
air bubble is approximately 1/16 in. (1,6
mm) for the 135°F (57°C) rating to 1/8 in.
(3,2 mm) for the 360°F (182°C) rating.
TFP513
Page 7 of 8

Obtain a leak-tight 1 in. NPT sprin-


kler joint by applying a minimum-to- Care and Care must be exercised to avoid
damage to the sprinklers before,
maximum torque of 20 lb-ft to 30 lb-ft
(26,8 N·m to 40,2 N·m). Higher levels Maintenance during, and after installation. Sprin-
klers damaged by dropping, striking,
of torque may distort the sprinkler Inlet TYCO Series DS-8 8.0K Pendent and wrench twist/slippage, or the like, must
with consequent leakage or impairment Horizontal Sidewall, Quick Response, be replaced. Also, replace any sprinkler
of the sprinkler. Standard Coverage Dry-Type Sprin- that has a cracked bulb or that has lost
Do not attempt to compensate for klers must be maintained and serviced liquid from its bulb. See the Installation
insufficient adjustment in an escutch- in accordance with this section. section.
eon plate by under or over-tightening Before closing a fire protection system The owner is responsible for the
the sprinkler. Re-adjust the position of main control valve for maintenance inspection, testing, and maintenance of
the sprinkler fitting to suit. work on the fire protection system their fire protection system and devices
Note: Install pendent sprinklers only in that it controls, obtain permission to in compliance with this document, as
the pendent position. The deflector of a shut down the affected fire protection well as with the applicable standards
pendent sprinkler is to be parallel to the systems from the proper authorities of the NATIONAL FIRE PROTECTION
ceiling. and notify all personnel who may be ASSOCIATION such as NFPA 25, in
affected by this action. addition to the standards of any other
Step 1. With a non-hardening pipe- authorities having jurisdiction. Contact
thread sealant such as TEFLON applied Absence of the outer piece of an the installing contractor or product
to the inlet threads, hand-tighten the escutcheon, which is used to cover a manufacturer with any questions.
sprinkler into the sprinkler fitting. clearance hole, may delay the time to
sprinkler operation in a fire situation. Automatic sprinkler systems are rec-
Step 2. Wrench-tighten the sprinkler ommended to be inspected, tested,
using either of the following tools: A vent hole is provided in the bulb seat and maintained by a qualified Inspec-
as shown in Figure 1 and Figure 2 to tion Service in accordance with local
• Pipe wrench on the inlet band or the indicate if the dry sprinkler is remaining
casing, see Figure 1 and Figure 2 requirements and/or national codes.
dry. Evidence of leakage from the vent
• W-Type 7 Sprinkler Wrench on the hole indicates potential leakage past
wrench flat, see Figure 3 the inlet seal and the need to remove
the sprinkler to determine the cause
Apply the wrench recess of the W-Type of leakage; for example, an improper
7 Sprinkler Wrench to the wrench flat. installation or an ice plug. Close the
Note: If sprinkler removal becomes fire protection system control valve and
necessary, remove the sprinkler using the drain the system before removing the
same wrenching method noted above. sprinkler.
Sprinkler removal is easier when a non- Sprinklers which are found to be
hardening sealant was used and torque leaking or exhibiting visible signs of
guidelines were followed. After removal, corrosion must be replaced.
inspect the sprinkler for damage.
Automatic sprinklers must never be
Step 3. After installing the ceiling or painted, plated, coated, or other-
wall and applying a ceiling finish, slide wise altered after leaving the factory.
on the outer piece of the escutch- Modified sprinklers must be replaced.
eon until it comes in contact with the Sprinklers that have been exposed to
ceiling/wall. Do not lift the ceiling panel corrosive products of combustion, but
out of its normal position. have not operated, should be replaced
When using the deep escutcheon, if they cannot be completely cleaned
hold the outer piece in contact with the by wiping the sprinkler with a cloth or
mounting surface (ceiling or wall). Then by brushing it with a soft bristle brush.
rotate the inner piece approximately 1/4
turn with respect to the outer piece,
to hold the deep escutcheon firmly
together.
TFP513
Page 8 of 8

P/N* 65 – XXX – X – XXX

Temperature Sprinkler Escutcheon Order


Orientation Escutcheon
Rating3 Finish Finish1 Length4
Signal White
36 Standard 0 135°F (57°C) Chrome 055 5.50 in.
0 (RAL9003)
Plated Polyester
33 Deep 1 155°F (68°C) Signal White 082 8.25 in.
Natural
Pendent 1 (RAL9003)
Brass
37 Recessed 2 175°F (79°C) Polyester 180 18.00 in.
Natural Brass
32 Without 2
3 200°F (93°C) Brass Plated 187 18.75 in.

Signal White Signal White


34 Standard 4 286°F (141°C) 4 (RAL9003) (RAL9003) 372 37.25 in.
Polyester Polyester
43 Deep 480 48.00 in.
Horizontal Chrome Stainless
8
Sidewall Plated Steel2
45 Recessed
Chrome Chrome
44 Without 9 Plated Plated

NOTES
1. Escutcheon Finish applies to sprinklers provided with escutcheons.
2. The stainless steel escutcheon finish is available for the pendent sprinkler only.
3. 135°F (57°C) and 175°F (79°C) temperature ratings apply to pendent sprinkler assemblies only.
4. Dry-type sprinklers are furnished based upon “Order Length” as measured according to Figures 3 to 6, as applicable, and for each individual sprinkler where it is to be
installed. After the measurement is taken, round it to the nearest 1/4 in. increment.
* Use Prefix “I” for ISO 7-R 1 Connection (for example, I-65-361-9-180).
TABLE D
SERIES DS-8 DRY-TYPE SPRINKLERS
8.0 K-FACTOR, 1 IN. NPT, QUICK RESPONSE, STANDARD COVERAGE
PART NUMBER SELECTION

Limited Horizontal Sidewall Dry-Type Sprin-


klers are furnished based upon order
Specify: (specify type), (specify) finish,
P/N (specify):
Warranty length as measured according to Fig-
ures 8 to 11, as applicable. After the
Recessed (Style 10)
Brass Plated . . . . . . . . . . . . . . . . . 91-960-2-010
measurement is taken, round it to the Signal White (RAL9003) ����������������91-960-4-010
For warranty terms and conditions, visit nearest 1/4 in. increment. Chrome Plated . . . . . . . . . . . . . . . 91-960-9-010
www.tyco-fire.com. Stainless Steel . . . . . . . . . . . . . . . 91-960-0-010
• Inlet Connections:
Ordering 1 in. NPT (Standard)
ISO 7-R 1
Standard (Push-On)
White Color . . . . . . . . . . . . . . . . . . 91-106-0-007

Procedure
Brass Plated . . . . . . . . . . . . . . . . . 91-106-2-007
Note: For information on ISO Inlet Chrome Plated . . . . . . . . . . . . . . . 91-106-9-007
Thread Connections, contact John- Stainless Steel . . . . . . . . . . . . . . . 91-106-8-007
Contact your local distributor for avail- son Controls Technical Services. Standard Horizontal Sidewall
ability. When placing an order, indi- • Temperature Rating Brass Plated �������������������������������������������� 854922
cate the full product name, including Signal White (RAL9003) �������������������������� 854902
description and part number (P/N). • Sprinkler Finish Chrome Plated ���������������������������������������� 854912

• Escutcheon Type and Finish, as Deep


Dry-type Sprinklers Brass Plated . . . . . . . . . . . . . . . . . . 91-107-2-010
When ordering Series DS-8 8.0K applicable White . . . . . . . . . . . . . . . . . . . . . . . . 91-107-4-007
Pendent or Horizontal Sidewall, Quick • P/N from Table D Chrome Plated . . . . . . . . . . . . . . . 91-107-9-007
Response, Standard Coverage Dry- Part numbers are for 1 in. NPT stan- Stainless Steel . . . . . . . . . . . . . . . 91-107-0-007
Type Sprinklers, specify the following dard order sprinklers. Orders for Sprinkler Wrench
information: all other sprinkler assemblies must Specify W-Type 7 Sprinkler Wrench,
be accompanied by a complete P/N 56-850-4-001
• SIN: description.
TY4235 – Pendent
TY4335 – Horizontal Sidewall (HSW) Sprinkler Boot
Replacement Escutcheons Specify Model DSB-2 Dry Sprinkler
• Order Length: Order separately. Boot, P/N 63-000-0-002
Pendent Dry-Type Sprinklers are fur- Note: Style 10 Recessed Escutcheons
nished based on Order Length as This part number includes one (1) Boot,
are shipped as assemblies comprised two (2) Strap Ties, and 1/3 oz of Adhe-
measured according to Figures 4 to of closure ring and mounting plate. The
7, as applicable. After the measure- sive (a sufficient quantity for installing
included mounting plate is not used for one boot).
ment is taken, round it to the nearest dry type sprinkler applications, discard
1/4 in. increment. accordingly.

1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220


© 2023 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;