Professional Documents
Culture Documents
ACI 307-98配筋混凝土烟囱设计
ACI 307-98配筋混凝土烟囱设计
ACI 307-98配筋混凝土烟囱设计
This standard gives material, construction, and design requirements for CONTENTS
cast-in-place and precast reinforced concrete chimneys. It sets forth mini- <;p$ep):($p .$......&?n$?r&> p. 30’7..2
mum loadings for design and contains methods for determining the con- 1.1-Scope
crete and reinforcement required us a result of these loadings. The method
of analysis applies primarily to circular chimney shells; howeveu, a general
1.2-Drawings
procedure for analysis of noncircular shapes is included. 1.3-Regulations
This standard is written in explicit, mandatory language, and as such, is 1.&Reference standards
intended for reference in project speci3cations.
Equations are provided for determining the temperature gradient through ebapt$?r2 h pi&^, p. 3QI’..2
the concrete resultingfuom the diffèrence in temperature of the gases inside
2.1-General
the chimney and the surrounding atmosphère. Methods for combining the
effects of dead and wind (or earthquake) loads with temperature both verti- 2.2-Cement
cally and circumferentially are included in the standard. These methods 2.3-Aggregates
permit the designer to establish minimum concrete and reinforcement 2 .&Reinforcement
requirements.
This standard refers extensively to “Building Code Requirements for <;p$ep):($p 3.....-<~.on~~iu~~Bon
$.E‘q&($$X]$?&, p. 3Q7-3
Structural Concrete” @CI 318); construction requirements are generally
in accordance with ACI 318; and notation is in accordance with ACI 104. 3.1-General
3.2-Concrete quality
3.3-Strength tests
Keywords: chimneys; compressive strength; concrete construction; 3 .&Forms
earthquake-resistantstructures; formwork (construction); foundations; high
temperature; linings; loads (forces); moments; openings; precast concrete;
3.5-Reinforcement placement
quality control; reinforced concrete; reinforcing steels; specifications; 3.6-Concrete placement
static loads; strength; structural analysis; structural design; temperature; 3.7-Concrete curing
thermal gradient; wind pressure
3.8-Construction tolerances
AC1 Committee Reports, Guides, Standard Practices, and 3.9-Precast erection
Commentaries are intended for guidance in planning, de-
signing, executing, and inspecting construction. This doc-
ument is intended for the use of individuals who are
competent to evaluate the significance and limitations
of its content and recommendations and who will ac-
cept responsibility for the application of the material it
contains. The American Concrete Institute disclaims any
and all responsibility for the stated principles. The Institute
shall not be liable for any loss or damage arising there-
from.
Reference to this document shall not be made in con-
AC1 307-98 became effectiveNovember 1,1998, and supersedes AC1 307-95.
tract documents. If items found in this document are de- Copyright O 1998, American Concrete Institute.
sired by the Architect/Engineer to be a part of the contract All rights reserved including rights of reproduction and use in any form or by any
means, including the making of copies by any photo process, or by any electronic or
documents, they shall be restated in mandatory language mechanical device, printed, written, or oral, or recording for sound or visual reproduc-
tion or for use in any knowledge or retrieval system or device, unless permission in
for incorporation by the Architect/Engineer. writing is obtained from the copyright proprietors.
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
Deformed and Plain Bars for Concrete
Reinforcement
CHAPTER I-GENERAL ASTM A 706-96 Standard Specification for Low-Alloy
1.1-Scope Steel Deformed Bars for Concrete
This standard covers the design and construction of
Reinforcement
circular cast-in-place or precast reinforced concrete chimney
shells. If other shapes are used, their design shall be substan- ASTM C 33-93 Standard Specification for Concrete
tiated in accordance with the principles used here. The standard Aggregates
does not include the design of linings, but includes the ASTM C 150-95 Standard Specification for Portland
effects of linings on the concrete shell. Cement
A precast chimney shell is defined as a shell constructed ASTM C 309-95 Standard Specification for Liquid
wholly from precast reinforced concrete sections, assembled Membrane-Forming Compounds for
one atop another, to form a freestanding, self-supporting Curing Concrete
cantilever. Vertical reinforcement and grout are placed in ASTM C 595-95 Standard Specification for Blended
cores as the precast sections are erected to provide structural Hydraulic Cement
continuity and stability. The use of precast panels as stay-in-
place forms is considered cast-in-place construction. CHAPTER 2-MATERIALS
2.1-General
1.2-Drawings All materials and material tests shall conform to AC1 3 18,
Drawings of the chimney shall be prepared showing all except as otherwise specified here.
features of the work, including the design strength of the
concrete, the thickness of the concrete chimney shell, the 2.2-Cement
size and position of reinforcing steel, details and dimen- The same brand and type of cement shall be used through-
sions of the chimney lining, and information on chimney out the construction of the chimney. The cement used shall
accessories. conform to the requirements for Type I, Type II, Type III,
or Type V of ASTM C 150, or Type IS or Type IP of
1.3-Regulations ASTM C 595.
1.3.1 The design and construction of the chimney shall
meet the requirements of all ordinances and regulations
2.3-Aggregates
of authorities having jurisdiction, except that where such
2.3.1 Concrete aggregates shall conform to ASTM C 33.
requirements are less conservative than the comparable
requirements of this standard, this standard shall govern. 2.3.2 The maximum size of coarse aggregate shall be not
1.3.2 Consideration shall be given to the recommendations larger than l/x of the narrowest dimension between forms
of the Federal Aviation Administration with respect to chim- nor larger than 1/2 the minimum clear distance between
ney heights and aviation obstruction lighting and marking, reinforcing bars.
and the standards of the Underwriters Laboratories regarding
lightning protection and grounding. 2.4-Rei nforcement
Reinforcement shall conform to ASTM A 615, A 617, or
1.4-Reference standards A 706. Deformed reinforcement with a specified yield stress
Standards of the American Concrete Institute, the Ameri- fy exceeding 60,000 psi shall be permitted provided the ul-
can Society of Civil Engineers, and the American Society for timate tensile strain shall equal or exceed 0.07.
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
casting cores of precast sections. Grout used to seat precast
3.4-Forms sections shall have a compressive strength at least equal to
3.4.1 Forms for the chimney shell shall be made of metal, the design strength of the shell.
wood, or other suitable materials. If unlined wooden forms
are used, they shall be of selected material with tongue-and- 3.7-Concrete curing
groove joints and shall be kept continuously wet to prevent 3.7.1 Immediately after the forms have been removed all
shrinking and warping due to exposure to the elements. A necessary finishing of concrete shall be done.
nonstaining form oil shall be permitted to be used. Form oil 3.7.2 As soon as fiiishing has been completed, both faces
shall not be used unless it is a nonstaining type and it has of concrete shall be cured by coating with a membrane cur-
been established that specified protective coatings or paint ing compound or other method approved by the engineer.
can be applied to concrete exposed to form oil. The curing compound shall comply with ASTM C 309 and
3.4.2 Forms shall be sufficiently tight to prevent leakage shall be applied in strict accordance with the manufacturer's
of mortar. recommendations. If coatings are to be applied to the con-
3.4.3 No construction load shall be supported upon any crete, the curing compound shall be of a type compatible
part of the structure under construction until that portion of with these coatings.
the structure has attained sufficient strength to safely support
its weight and the loads placed thereon. 3.8-Construction tolerances
3.4.4 Forms shall be removed in such manner as to ensure 3.8.1 The chimney shell shall be constructed within the
the safety of the structure. Forms shall be permitted to be tolerance limits set forth here.
removed after concrete has hardened to sufficient strength to 3.8.1.1 Vertical alignment of centerpoint-The center-
maintain its shape without damage and to safely support all point of the shell shall not vary from its vertical axis by more
loads on it, including temporaiy construction loads. than 0.001 times the height of the shell at the time of mea-
3.4.5 Ties between inner and outer chimney shell forms surement, or l in., whichever is greater. Locally, the center-
shall not be permitted. point of the shell shall not be changed by more than 1 in. per
3.4.6 Construction joints shall be properly prepared to 10 ft.
facilitate bonding. As a minimum, all laitance and loose 3.8.1.2 Diameter-The measured outside shell diameter
material shall be removed. at any section shall not vary from the specified diameter by
more than 1 in. plus 0.01 times the specified or theoretical
3.5-Reinforcement placement diameter.
3.5.1 Circumferential reinforcement shall be placed 3.8.1.3 Wall thickness-The measured wall thickness
around the exterior of, and secured to, the vertical bars. All shall not vary from the specified wall thickness by more
reinforcing bars shall be tied at intervals of not more than than -'/, in., +'/, in. for walls 10-in.-thick or less, or by more
2 ft. Particular attention shall be paid to placing and securing than-'/, in., +1 in. for walls greater than 10-in.-thick.A single
the circumferential reinforcement so that it cannot bulge or wall thickness measurement is defiied as the average of at
be displaced during the placing and working of the concrete least four measurements taken over a 60-deg arc.
so as to result in less than the required concrete cover over 3.8.2 Openings and embedments-Tolerances on the size
this circumferential reinforcement. and location of openings and embedments in the shell cannot
be uniformly establisheddue to the varying degrees of accuracy 4.1.7.4 Consideration shall be given to the effects of
required depending on the nature of their use. Appropriate radiant heat of gases on any part of the foundation, including
tolerances for opening and embedment sizes and locations the foundation floor area which is exposed within the liner
shall be established for each chimney. and also concrete floors supported from the concrete shell.
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
over open terrain where VR= V. This speed V and im-
CHAPTER 4-SERVICE LOADS
AND GENERAL DESIGN CRITERIA portance factor I shall be as specified by ASCE 7. All
4.1-General chimneys shall be classified as Category IV structures as
4.1.1 The chimney shell shall be designed for the effects defined in ASCE 7-95. Terrain effects referenced in Sec-
of gravity, temperature, wind, and earthquake in accordance tion 6.5.5 of ASCE 7-95 are omitted.
with AC1 3 18, except as stated otherwise here. At a height z ft above ground, the mean hourly design
4.1.2 The chimney shell shall be designed for load combi- speed v(z) in fi/sec shall be computed from Eq. (4-1)
nations in accordance with the provisions of t. 3,
Design of chimney shell: Strength method. - O. 154
4.1.3 V(z) = (1.47)VR(&) (0.65) (4-1)
4.1.3.1 The chimney shell shall not be less than 8-in.
thick when cast in place, or less than 7-in. thick when com-
The provisions with respect to wind load take account of
posed of precast sections.
dynamic action but are simplified and lead to equivalent static
4.1.3.2 The chimney shell thickness, through openings,
loads. A properly substantiated dynamic analysis may be
shall not be less than 1/24 the height of the opening.
used in place of these provisions.
The thickened shell shall extend at least 1/2 the height of
4.2.2 Along-wind load: Circular shapes-The along-wind
the opening above and below the opening. Properly designed
load, w(z) per unit length at any height z ft, shall be the sum
buttresses or other means of lateral restraint may be used in
of the mean load w(z) and the fluctuating load w’(z).
place of this requirement; however, the buttresses shall be
ignored when calculating vertical strength. The mean load w(z) in lb/ft shall be computed from
Eq. (4-2)
4.1.3.3 When the internal diameter of the shell exceeds
28 ft, the minimum thickness shall be increased l/x in. for
each 1-ft increase in internal diameter. @(Z) = Cdr(z) d(z) *U(.) (4-2)
4.1.4 A chimney shell that supports lining loads shall com-
ply with the requirements of this standard with the lining in
where
place. The interaction of the liner with the shell shall be
considered. Cdr(z)= 0.65 for z < h ~ 1.5d(h) (4-3a)
4.1.5 Consideration shall be given to loadings during the
construction phase. Cdr(z)= 1.O for z 2 h ~ 1.5d(h) (4-3b)
4.1.6 If required during construction, temporary access
openings may be provided in the concrete shell. For the design
u(z) = 0.0013 [F(z)l2 (4-4)
of the shell, these openings shall be designed as permanent
openings. d(z) = outside diameter at height z, ft
4.1.7
h = chimney height above ground level, fi
4.1.7.1 The maximum foundation bearing pressure shall
be established using unfactored chimney loads. d(h) = top outside diameter, ft
4.1.7.2 The foundation shall be designed by the strength The fluctuating load w’(z) shall be taken equal to
method in accordance with the procedures of AC1 318. The
foundation design shall be based on a pseudo-bearing pressure
‘le loads, using the loading combinations w’(z) = 3.02 G,,>, M,(b)
(4-5)
‘4 . I and 5 2 . 2 . h3
4.1.7.3 The minimum factor of safety against overturning
shall be 1.50 using unfactored loads. where M;(b) = base bending moment due to w(z) and
where
(4-7)
1
I = - (4- 11)
where
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
h = chimney height above base, ft
2, = exposure length = 0.06 ft
t(h) = thickness at top, ft
t(b) = thickness at bottom, ft
- F1(B) = 0.089 + 0.337108,- h
d(b) = mean diameter at bottom, ft -
(4-12)
pck = mass density of concrete, kip-sec2/ft4 d(u)
Eck = modulus of elasticity of concrete, kip/ft2
but not > 1.0 or < 0.20.
If the lining is supported in any manner by the shell, the
pa = density of air = 0.075 lbs/ft3
effect of the lining on the period shall be investigated.
V,, = critical speed at 5/6h, ft/sec
4.2.3 Across-wind load: Circular shapes
4.2.3.1 General-Across-wind loads due to vortex
shedding in the first and second modes shall be considered in (4- 13)
the design of all chimney shells when the critical wind speed
Y,, is between 0.50 and 1.30 v(zc,) as defïned here. Across-
wind loads need not be considered outside this range. f = first-mode frequency, Hz
4.2.3.2 Analysis-When the outside shell diameter at S, = Strouhalnumber
1/3h is less than 1.6 times the top outside diameter, across-
wind loads shall be calculated using Eq. (4-8) which defies S, = 0.25Fl(A) (4- 14)
the peak base moment Ma
where
Ma = -SsCL?&d(u)h2
G
g Fl(A) = 0.333 + O.2061oge- h (4- 15)
4 u>
but not > 1.0 or < 0.60.
d(u) = mean outside diameter of upper third of chimney,
ft
h = chimney height above ground level, ft
- Eq. (4-8) defines the peak base moment Ma for values of
V, where v i s evaluated between 0.5 and 1.30v(z,,). When 7
2 v(z,,), Ma shall be multiplied by
O.lO[V- V(z )]
ß, = 0.01 + -
CI’
(4- 16)
where
-
V(z,,) = the mean design wind speed at zcr,zcr = 5/6h, (4-17)
ftlsec
where
- s = center-to-center spacing of chimneys, fi
wt(u) = average weight in top third of chimney, lb/ft
d(z,,) = outside diameter of chimney at critical height
Sp = spectral parameter Zer, ft
For chimneys that are not identical and for identical chim-
neys where s/d(z,,) < 3, the value of C, shall be established
by reference to model tests or observations or test reports of
similar arrangements.
4.2.3.5 Combination of across-wind and along-wind
loads-Across-wind loads shall be combined with the
where coexisting along-wind loads. The combined design moment
B = band-width parameter MJz) at any section shall be taken as
B = 0.10+2i (4-22)
.0.5
L = correlation length coefficient
L = 1.20
CE = end effect factor = 3
After solving for Mu, across-wind moments at any height where
Mu(.) may be calculated based on the corresponding mode Ma(.) = moment induced by across-wind loads
shape of the chimney column. moment induced by the mean
Ml(z) =
4.2.3.3 Second mode-Across-wind response in the sec- along-wind load wl(z)
ond mode shall be considered if the critical wind speed VCr2 where
as computed by Eq. (4-23) is between 0.50 and 1.30 F(z,,),
where F(z,,) is the mean hourly wind speed at 5/6h
(4-26)
(4-23)
where t(h) and t(b) are the thicknesses at the top and bottom, where
respectively, and d(h) and d(b) are the mean diameters at the r(z) = mean radius at height z, ft
top and bottom, respectively.
pr(z) = 0.0013[F((~)]~
G,(z), lb/ft2 (4-29)
The effect of a shell-supported liner on the period of the
second mode shall also be investigated. G,(z) = 4.0 O.Slog,,z, except G,(z)
~ =4 for z 5 1.0(4-30)
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
The pressure pr(z) shall be increased by 50 percent for a 4.4-Special design considerationsand
distance 1.5d(h) from the top. requirements
4.2.5 Wind loads: Noncircular shapes-The provisions of 4.4.1 Two layers of vertical and circumferential reinforce-
ment are required. The total vertical reinforcement shall be
ASCE 7 shall be followed including force coefficients and
not less than 0.25 percent of the concrete area. The outside
gust response factors. Unusual cross-sectional shapes not
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
is also permitted. Linear interpolation may be used in between A,, coefficients not given.
Frequency, cps.
The minimum size of circumferential reinforcing bars shall steel ratio times one-half the area of the opening. The extra
be No. 3. reinforcement shall be placed within a distance not exceed-
4.4.3 The circumferential reinforcement for a distance of ing twice the wall thickness unless otherwise determined by
0.2d(h) from the top of the chimney or 7.5 ft, whichever is a detailed analysis.
greater, shall be at least twice the amount required by 4.4.1 At both the top and bottom of each opening, addi-
‘;<:&I 1 F: :i. tional reinforcement shall be placed having an area at least
4.4.4 Where a segment between openings is critical as equal to one-half the established design circumferential rein-
related to the height of the openings, this segment shall be forcement interrupted by the opening, but the area A , of this
investigated as a beam-column. Where more than two open- additional steel at the top and also at the bottom shall be
ings occur at the same elevation, appropriate design methods not less than that given by Eq. (4-31), unless otherwise
consistent with the cases shown by Fig. 5.5.l(;g, fb‘:.. , and (c) determined by a detailed analysis
shall be used.
4.4.5 In addition to the reinforcement determined by design, 0.06f,’tl
extra reinforcement shall be provided at the sides, top, bot- A, = ~
4-
(4-3 1)
tom, and corners of these openings as hereinafter specified. JY
This extra reinforcement shall be placed near the outside
surface of the chimney shell as close to the opening as proper where
spacing of bars will permit. Unless otherwise specified, all
extra reinforcement shall extend past the opening a minimum
f,’ = specified compressive strength of concrete, psi
of the development length. t = concrete thickness at opening, in.
4.4.6 At each side of the opening, the additional vertical 1 = width of opening, in.
reinforcement shall have an area at least equal to the design & = specified yield strength of reinforcing steel, psi
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
QI = (5-4)
5.1.4 Refer to ?t"iiii>ii 5 .' for design procedures of noncir- 1 cosa -
cular shells.
h, = y + y, - 7c (radians) (5-5)
5.2-Design loads
5.2.1 Dead loads and wind or earthquake forces at service
y, T, y, = angles shown in Fig. 5.5.l(a).
conditions prior to the application of load factors,shall be in
accordance with Ch:?@:?r 4.of this standard. Thermal effects
at service conditions shall be in accordance with C1qxcr-6. COST = 1 ß l ( 1 cosa)
- -
(5-6)
% vertical reinforcement
r ( c o s p - c o s a ) = f y r(1-cos a )
EmEs
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
PLAN
TWO SYMMETRIC OPENINGS PARTLY IN
TWO OPENINGS IN COMPRESSION ZONE
COMPRESSION ZONE
(Dimensions not shown same as Fig 5.5.la) (Dimensions not shown same as Fig. 5.5.1~1)
Q = 0.89 (5-12f)
where
M, = nominal moment strength of section
where
2
a = one-half the central angle subtended (y,- y)( 1 + 2cos a )
by neutral axis + (1/2)(4sin2a+ sin2y- sin2y)
ß = one-half opening angle - 4cosa( sina + s k y , - shy)
Q2 = (5-13)
ß, = 0.85 forf,’ 5 4000 psi (1 - cosa)
-
0.85 0.05~,’ 4000)/1000 2 0.65,
- -
forf,‘ > 4000 psi K = siny, + siny + (7c -y,- y) cosa (5-14)
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
K, = Es I&
R = sin^ (T nip) cosa
cor = Pr&lf,’
- - -
Replacef, with
Replacef,’ with
1.4
-( f S T V - Ylf ”STV)
1 +Yi
MANUAL OF CONCRETE PRACTICE
(5-16a)
0 . w -
m
R
j;
r,
f,
I
I
I
I
I
I
I
b E,
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
Strain I
0.002 0.003
Strain
where yl, fSw, f ’&v, and f ’& are as defined in Chapter 6.
p = ratio of total area of vertical outside face T, = maximum specified design temperature of gas
reinforcement to total area of concrete chimney inside chimney, F
shell at section under consideration To = minimum temperature of outside air surrounding
yi = ratio of inside face vertical reinforcement area chimney, F
to outside face vertical reinforcement area C, = coefficient of thermal conductivity of the concrete
y2 = ratio of distance between inner surface of of chimney shell, Bhufi2/in. of thickness/hr/F
chimney shell and center line of outer face difference in temperature (12 for normal weight
vertical reinforcement to total shell thickness concrete)
n = EJE, c
b = coefficient of thermal conductivity of chimney
uninsulated lining or insulation around steel liner,
T,, the temperature gradient across the concrete shell, shall Bhuft2/in. of thickness/hr/F difference in
be computed by Eq. (6-3a), (6-3b), (6-3c), (6-3d), or by a temperature
complete heat balance study for all operating conditions. C, = coefficient of thermal conductivity of insulation
filling in space between lining and shell, Btw'ft2/in.
a) For unlined chimneys
of thickness/hr/F difference in temperature
(3 for lightweight concrete)
Ti To~
Ki = coefficient of heat transmission from gas to inner
(6-3a) surface of chimney lining when chimney is lined,
or to inner surface of chimney shell when chimney
is unlined, Btu/ft2/hr/F difference in temperature
KO = coefficient of heat transmission from outside
surface of chimney shell to surrounding air,
b) For lined chimneys with insulation completely filling Bhuft2/hr/F difference in temperature
the space between the lining and shell
r
K, = coefficient of heat transfer by radiation
between outside surface of lining and inside
T, =
tdbi
-
l+-+Sb2+-+-
\Ki '
Ti To
tbdbi t d . tdbi
Cbdb ' C,d,
~
'
dbi1
Cede ' KodcoJ
(6-3b)
K, =
surface of concrete chimney shell, Bhuft2/hr/F
difference in temperature
coefficient of heat transfer between outside surface
of lining, and inside surface of shell for chimneys
with ventilated air spaces, Bhufi2/hr/F difference
in temperature
c) For lined chimneys with unventilated air space between
dbi = inside diameter of uninsulated lining or insulation
the lining and shell
around liner, ft
db = mean diameter of uninsulated lining or insulation
around liner, ft
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
40
36
32
28
24
c
2
:: 2 0
W
u
O
The value of rq = 0.5 shall apply only where the distance f Crc = a,, c’ T, E, (6-5)
between the lining and the chimney shell is not less than 4 in.
throughout the entire height of the lining and air inlet and where
outlet openings are provided at the bottom and top of the cf =
6.3.2 The maximum stress in psi in the outside circumfer- d(u) = mean outside diameter of upper third
ential reinforcementfsTc due to temperature shall be comput- of chimney, ft (Chapter 4)
ed by Eq. (6-7) d(z) = outside diameter of chimney at height z , ft
(Chapter 4 and Commentary Chapter 4)
outside diameter of chimney at critical height
zcr, ft (Chapter 4)
APPENDIX A-N OTATION
A, = area of reinforcing steel at top and bottom of D = dead load (Clqxer. ::1 ’~
h = chimney height above ground level, fi M,.(z)= combined design moment at height z
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
(Chapter 4 and Commentary Chapter 4) for across-wind and along-wind loads (Chapter 4)
z = local turbulence parameter (Chapter 4) n = modular ratio of elasticity EJE, (Chapter 6)
I = importance factor for wind design in Chapter 4 ni = number of openings entirely in compression zone
and ASCE 7 (Chapter 5 )
k = ratio of wind speed (qto critical wind speed (V,,) pressure due to mean hourly design wind speed
at height z, lb/fi2 (Chapter 4)
ku = aerodynamic damping parameter (Chapter 4)
radial wind pressure at height z , lb/ft2
kuo = mass damping parameter of small amplitudes (Chapter 4 and Commentary Chapter 4)
~;-;>..$>,+.
B C.:^,,..' i.)
Per = pressure due to wind at critical speed (Chapter 4)
k, = equivalent sand-grained surface roughness factor
(Commentary Chapter 4) Pu = factored vertical load (Chapter 5 )
Ki = coefficient of heat transmission from gas to inner r = average radius of section (Chapter 5 )
surface of chimney lining when chimney is lined, rq
-
-
ratio of heat transmission through chimney shell
or to inner surface of chimney shell when chimney to heat transmission through lining for chimneys
is unlined, Btu/ft2/hr/F difference with ventilated air spaces (Chapter 6)
in temperature (Chapter 6)
r(z) = mean radius at height z, ft (Chapter 4)
KO = coefficient of heat transmission from outside R = parameter for nominal moment strength
surface of chimney shell to surrounding air, (Chapter 5 )
Btu/ft2/hr/F difference in temperature (Ciiapi.~5)
s = center-to-center spacing of chimneys, ft
K,. = coefficient of heat transfer by radiation between (Chapter 4 and Commentary Chapter 4)
outside surface of lining and inside surface of
concrete chimney shell, Bhuft2/hr/F difference in sp = spectral parameter (Chapter 4)
temperature (Chapter 6) s, = mode shape factor (Chapter 4)
K, = coefficient of heat transfer between outside s, = strouhal number (Chapter 4)
surface of lining and inside surface of shell for t = thickness of concrete shell (Chapters 5 and 6)
chimneys with ventilated air spaces,
Btu/ft2/hr/F difference in temperature (Chapter 6) tb = thickness of uninsulated lining or insulation
around steel liner, in. (Chapter 6)
t.7 = thickness of air space or insulation filling the
parameters for nominal moment strength (Chapter space between lining and shell, in. (Chapter 6)
5)
t(b) = thickness of concrete shell at bottom, fi
1 = width of opening in concrete chimney shell, in. (Chapter 4)
(Chapter 4)
t(h) = thickness of concrete shell at top, ft (Chapter 4)
length coefficient (Chapter 4) T = normal temperature effect (Chapter 6)
moment induced at height z by across-wind loads, T , = maximum specified design temperature
ft-lb (Chapter 4) of gas inside chimney, F (Chapter 6)
Mi(.)= maximum circumferential bending moment due to To = minimum temperature of outside air
radial wind pressure, at height z, tension on inside, surrounding chimney, F (Chapter 6)
ft-lb/R (Chapter 4)
T, = temperature drop across concrete shell
moment induced at height z by mean along-wind (Chapter 6)
load, ft-lb (Chapter 4)
Ti = fundamental period of vibration for unlined shell,
nominal moment strength at section (Chapter 5 ) sec per cycle (Chapter 4 and Commentary Chapter
maximum circumferential bending moment due to 4)
radial wind pressure, at height z, tension on T2 = second mode period of vibration for unlined shell,
outside, ft-lb/ft (Chapter 4) sec per cycle (Chapter 4 and
Mu = factored moment at section (Chapter 5 ) Commentary Chapter 4)
M;(b)= bending moment at base due to mean along-wind u, = required circumferential strength (Chapter 5 )
load, ft-lb (Chapter 4) u,,= required vertical strength (Chapter 5 )
v = basic wind speed, mph (ASCE 7 and Chapter 4) Pa = aerodynamic damping factor (Chapter 4)
ver = critical wind speed for across-wind loads, ßs = fraction of critical damping for across-wind
corresponding to fundamental mode R/sec load (Chapter 4)
(Chapter 4)
PI factor defined in Section 10.2.7.3of AC1 3 18
critical wind speed for across-wind loads (Chapter 6)
corresponding to second mode
v, = V(1°.5), mph (Chapter 4) on chimney cross section, one-half central angle
- subtended by the center lines of two openings
v = mean hourly wind speed at 5/6h varying (Chapter 5)
over a range of 0.50and 1.30v(z,,), R/sec
- d(h)/d(b)(Chapter 4)
V(h) = mean hourly wind speed at top of chimney, ft/ Yd =
AC1 307R-98
Commentary on Standard Practice for the Design
and Construction of Reinforced Concrete
Chimneys (AC1 307-98)
Reported by AC1 Committee 307
Victor A. Bochicchio
Chairman
This commenton discusses some of the hockgmunà and consideration of Chapter 2-Materials, p. 307R-3
Committee 307 in developing rhe provisions contained in “Standard Prac-
tice for the Design ond Construction of Reinforced Concrete Chimnem
Chapter 3-Construction requirements, p. 307R-3
(AC1 307-98).” The changes .from the previous edition are noted. Two
3.3-Strength tests
oppendices provide the derivation of the equations for nominal strength
and temperature stresses.
3.GForms
3.5-Reinforcing placement
Keywords: chimneys; compressive strength; concrete construction;earth-
quake-resistant structures; formwork (construction); foundations: high Chapter 4-Service loads and general design
temperature; linings; loads (forces); moments; openings; precast concrete; criteria, p. 307R-4
quality control; reinforced concrete; reinforcing steels; specifications; 4. l-General
static loads; strength; structural analysis; structural design; temperature; 4.2-Wind loads
thermal gradient: wind pressure. 4.3-Earthquake loads
4.5-Deflection criteria
CONTENTS
Chapter +Design of chimney shell-Strength
Introduction, p. 307R-2 method, p. 307R-7
5.1-General
Chapter l-General, p. 307R-3 5.4-Design strength
1. I-Scope
5.5-Nominal moment strength
5.6-Design for circumferential bending
1 .&Reference standards
Chapter 6-Thermal stresses, p. 307R-9
AC1 Committee Reports, Guides, Standard Practices, and 6. i -General
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
Commentaries are intended for guidance in planning, de- 6.2-Vertical temperature stresses
signing, executing, and inspecting construction. This doc-
ument is intended for the use of individuals who are Appendix A-Derivation of equations for nominal
competent to evaluate the significance and limitations strength, p. 307R-9
of its content and recommendations and who will accept
responsibility for the application of the material it con- Appendix B-Derivation of equations for
temperature stresses, p. 307R-13
tains. The American Concrete Institute disclaims any and
all responsibility for the stated principles. The Institute shall Appendix C-References, p. 307R-14
not be liable for any loss or damage arising therefrom.
Reference to this document shall not be made in contract
AC1 30713-98 supercedes AC1 307R-95and became effective Novemher I , 1998.
documents. If items found in this document are desired Copyright O 1998, American Concrete Institute.
All rights reserved including rights of reproduction and use in any form or by any
by the Architecangineer to be a part of the contract doc- means, including the making of copies by any photo process, or by electronic or
uments, they shall be restated in mandatory language for mechanical device, printed, written, or oral, or recording for sound or visual reproduc-
tion or for use in any knowledge or retrieval system or device. unless permission in
incorporation by the ArchitectfEngineer. writing is oblained from the copyright proprietors.
307R-1
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
No reproduction or networking permitted without license from IHS Not for Resale, 08/14/2006 20:14:55 MDT
307R-2 AC1 COMMITTEE REPORT
established two task forces for chimney liners, one for brick The vertical load factor for along-wind forces has been
and the other for fiberglass reinforced plastic. reduced from 1 .7 to 1.3.
The Committee had extensive discussion on the question 0 The vertical load factor for seismic forces has been re-
of including strength design in the 1979 specification. The duced from 1.87 to 1.43.
decision to exclude it was based on the lack of experimental The load factor for across-wind forces has been re-
data on hollow concrete cylinders to substantiate this form of duced from i .40 to 1.20.
analysis for concrete chimneys. However, the Committee The vertical strength reduction factor $ has been re-
continued to consider strength design and encouraged duced from 0.80 to 0.70.
experiments in this area. It should be noted that the reduced load factors must be
Shortly after the 1979 edition was issued, the Committee used in concert with the revised strength reduction factor and
decided to incorporate strength design provisions and update the wind and seismic loads specified in ASCE 7-95.
the wind and earthquake design requirements. The foregoing revisions are discussed in more detail in the
The 1988 edition of AC1 307 incorporated significant following commentary.
changes in the procedures for calculating wind forces as well Finally, the Cornmittee believes that the AC1 307 standard is
as requiring strength design rather than working stress. The particularly unique in its inclusion of specific procedures to
effects of these and other revisions resulted in designs with calculate wind and seismic forces on chimneys. Consequently,
relatively thin walls governed mainly by steel area and, in the Committee feels that the previous Commentary regarding
many instances, across-wind forces. these subjects should be retained wherever possible.
The subject of across-wind loads dominated the attention Similarly, the Committee believes that the Commentary
of the Committee between 1988 and 1995 and the 1995 stan- regarding the assumptions and procedures for strength de-
dard introduced modified procedures to reflect more recent sign and other recent revisions should also be retained for
information and thinking. reference.
Precast chimney design and construction techniques were A chapter-by-chapter commentary follows.
introduced as this type of design became more prevalent for
chimneys as tall as 300 ft. CHAPTER I-GENERAL
The subject of noncircular shapes was also introduced in 1995. 1.1-scope
However, due to the virtually infinite array of possible configu- The scope of the 1995 standard was expanded to include
rations, only broadly defined procedures were presented. precast chimney shells. Additional information may be
Because of dissimilarities between the load factors re- found in K I manuals.’-*Wames3 provides further guide-
quired by the AC1 307 standard and AC1 3 18, the Committee lines on connection details for precast structures. Additional
information is given in AC1 SOR, “Design Recommenda-
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
added guidelines for determining bearing pressures and
loads to size and design chimney foundations. tions for Precast Concrete Structures.”
In summary, the following highlights the major changes
that were incorporated into the 1995 standard: 1.&Reference standards
The year of adoption or revision for the referenced stan-
Modified procedures for calculating across-wind loads; dards has been updated.
0 Added requirements for precast concrete chimney col-
umns; CHAPTER 2-MATERIALS
0 Added procedures for calculating loads and for design- No changes of note have been made in this section.
ing noncircular chimney columns;
Deleted exemptions previously granted to “smaller” chim- CHAPTER 3-CONSTRUCTION REQUIREMENTS
neys regarding reinforcement and wall thickness; and 3.3-Strength tests
Requirements for testing precast concrete units were add-
Deleted static equivalent procedures for calculating
ed in the 1995 standard.
earthquake forces.
3.4-Forms
Synopsis of current revisions Shear transfer within precast concrete shells must be con-
Revisions to the ASCE 7-95 standard relating to wind and sidered in design especially if the structure has vertical as
seismic forces required that several changes be made to the well as horizontal construction joints.
1995 edition of AC1 307. The following highlights the
changes incorporated into the current standard: 3.5-Reinforcing placement
0 Site-specific wind loads are calculated using a “3-sec The size, spacing, and location of vertical cores within
gust” speed determined from Fig. 6- 1 in ASCE 7-95 in- precast concrete chimney shells will be determined by geom-
stead of the previously used “fastest-mile’’ speed. etry and steel area requirements. It is important that the de-
Site-specific earthquake forces are calculated using the sign of precast chimneys comply with the minimum spacing
effective peak velocity-related acceleration contours requirements of ACI 318 when arranging reinforcement
determined from Contour Map 9-2 in ASCE 7-95 in- within the cores to permit proper bar splicing and concrete
stead of previously designated zonal intensity. placement.
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
Table 4.2.3-Comparison of results: along- plus across-wind moments, 1988 versus 1995
procedures
Frequency,
Chimney I Height, ft I TOD, ft BOD, ft Tapers VI, mph h/d at 5/6h hz
6 I 485 I 47.67 53.50 3 85.0 10.17 0.485
13 500 52.17 52.17 1 76.8 9.58 0.428
7 534 51.09 61.55 1 74.9 10.1 1 0.591
8 545 33.00 55.00 1 85.6 14.86 0.432
9 613 73.00 73.00 1 74.9 8.40 0.406
12 978 7 1S O 114.58 3 74.9 13.68 0.295
2 275 28.00 28.00 1 85.6 9.82 0.752
4 375 20.00 32.00 1 85.6 17.05 0.529
The 1995 Committee had numerous user comments and Circular chimneys outside the bounds of these procedures,
I
discussions regarding the procedures included in the 1988 or where a flare or strong taper (nozzle) exists for more than
standard for across-wind forces. Virtually all of the com- one diameter near the top, may be conservatively analyzed
mentators felt that the 1988 procedures were unduly conser- using the procedures of Section 4.2.3.3 of AC1 307-88 or by
vative, especially in the absence of any record of structural the general approach put forth by Vi~kery.'~
failure. As a result of these discussions, and with the avail- It should be noted, however, that the procedures for deter-
ability of new data and full-scale observations, the proce- mining shedding forces are not materially affected by the
dures for calculating across-wind loads were extensively configuration of the lower third of the shell, which may
revised. range from plumb to any degree of taper.
A general solution for the across-wind response of circular However, it should also be noted that noncircular shapes
chimneys with any geometry was developed by V i ~ k e r y . ' ~ may be more sensitive to across-wind forces and may require
These procedures, based on Vickery's general solution, were analyses beyond the scope of this standard.
simplified to some extent, which requires that their applica- Eq. (4- 16) establishes a basis for increasing structural
tion be restricted to certain geometries. Similar models have damping from a minimum of 1.O percent to a maximum of 4.0
provided the basis for vortex-induced forces incorporated by percent when the wind speed exceeds vStructural v(zc,).
the National Building Code of Canada, and the ASMWANSI damping of 1 percent of critical is consistent with measured
STS-i - 1993 Steel Stack Standard. values and moderate stress levels with little cracking.Damping
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
detail but virtually all the test results are for subcritical val- horizontal ground acceleration of 1.O0with 5 percent of crit-
ues of Reynolds Numbers and their applicability to chimneys ical damping. It represents a spectrum of 50 percent shape-
is highly questionable. However, even with the scale effects bound probability level that the response of the structure dur-
introduced by the inequality of the Reynolds Number, the ing an earthquake would not exceed. It i s the same spectrum
wind tunnel is presently the only tool that will provide guid- that has been adopted for use in the design of steel chimney
ance as to the likely magnitude of interference effects. A re- liners for earthquakes by the Task Committee of the American
view of interference effects is given by Zdravk~kvich.’~ Society of Civil Engineers.*’ To obtain the design response
Vickery13 attributes the amplification of shedding forces to spectrum, the normalized spectrum must be scaled down to
increased turbulence and additional buffeting effects, which the effective peak velocity EPV related ground acceleration.
formed the basis for revisions made to this section. The ASCE 7-95 map for the EPV-related acceleration co-
At center-to-center spacings s, in excess of 2 to 3 diame- efficient is used in this standard. This map differs from those
ters, the prime interference effect is related to across-wind used in the Uniform Building Code, which was based on the
excitation due to shedding. The recommendations in Section maximum recorded intensity of shaking without regard to
4.2.3.4 are based on the results of Vickery and Daly” and the frequency with which earthquake shaking might occur.
were obtained at subcritical values of the Reynolds Number. The ASCE 7-95 map, on the other hand, has a more uniform
The first term in modifier (c) is an enhancement factor to ac- probability of earthquake occurrence, and is based on those
count for buffeting due to vortices shed by the upstream given by the NEHRP (see Reference 21). For example, in
structure; the second term accounts for small-scale turbu- Zone 4 seismic area, the EPV-related acceleration is 0.4g and
lence. The same reference also contains results for two cyl- the probability of not exceeding this peak EPVground accel-
inders of different size with the upstream structure having a eration within 50 years is estimated to be 90 percent. This is
diameter 25 percent greater than the diameter d of the other. equivalent to a mean recurrence interval of 475 years, or an
In this case the amplification of the response of the down- average annual risk of 0.002 events per year. The peak EPV-
wind chimney is roughly 3.4 - 0.2 sld for 4 < síd c 12. The related ground acceleration at a site can be determined either
amplification of shedding for grouped cylinders has also by using this contour map and the recommended scale fac-
been noted at full scaleI6 but the available data is not suffi- tors given in Table 4.3.2 or from the specific seismic record
cient to quantitatively validate model test results. available at the site. It should be noted that a ductility factor
4.2.4 Circumferential bending-The equation for the pre- of 1.33 is built into the scale factors of Table 4.3.2. For in-
diction of the circumferential moments is based upon mea- stance, instead of 0.40, a scale factor of 0.30 is used for a site
sured pressure distribution^.'^^'^ Comparative values for the with an A, of 0.4.
bending moments as obtained from different distributions It should also be pointed out that the recommended de-
are given in Reference 8. The use of a gust factor G, in this sign response spectrum is based on firm soil sites. Soil con-
computation is based upon the assumption that the mean ditions at the firm site consist of bedrock with shear wave
pressure distribution (when expressed in coefficient form) is velocity greater than 2500 ft/sec or stiff soils with deposits
also applicable for short-duration gusts. less than 200 ft. For chimneys to be built on shallow and
The increase in the loads near the tip is consistent with soft or medium-stiff clays and sands, a greater design re-
observations” that the drag coefficient increases significant- sponse spectrum is anticipated. Guidelines provided in
ly in this region. NEHRP*‘ to obtain a modified design response spectrum
and the soil-structure interaction may be used. reached first. If the steel fracture limit is reached first, the
In place of a dynamic response spectrum analysis, a time maximum concrete strain computed from the linear strain di-
history dynamic analysis is permitted, provided a reliable agram is below 0.003. This deviates from the design assump-
time history of earthquake ground motion is used. tions of AC1 318. For a given total vertical steel ratio, this
In the design of a chimney for horizontal earthquake forces, may occur when the ratio of the vertical load to the moment
only one horizontal direction need be considered. Unlike is below a certain value. A total vertical steel ratio in the
building structures, chimneys are generally axisymmetric, and chimney cross section less than that per the minimum re-
the orthogonal effects from two horizontal earthquakes acting quirement of AC1 3 18 for flexural members is permitted.
simultaneously in the two principal directions are negligible. Even when the maximum concrete compressive strain E,,
The effect of the vertical component of the earthquake on is less than 0.003, the stress block is still considered rectan-
the chimney has been determined to be of no design signifi- gular. However, in these instances, the stress level is modi-
cance. An extensive time history analysis made by the Com- fied by a correction factor called the parameter Q. See
mittee shows that the vertical stresses from dead load and commentary on Section 5.5.1.
horizontal seismic excitation are increased by at most a few 5.3.1-The Committee noted that the “fastest-mile’’ provi-
percent by the effects of vertical seismic excitations. This is sions in the 1988 edition of AC1 307 resulted in an increase
principally because the psa responses to vertical and hori- in wind moments of between O and 50 percent when com-
zontal acceleration do not occur simultaneously.
pared with AC1 307-79. The use of a “3-sec gust” wind speed
Design based on SRSS of vertical and horizontal earthquake results in further increases in axial bending moments, which
forces will be unduly conservative. Therefore, the inclusion of
are 10 to 20 percent higher than moments calculated using
vertical seismic effects is not recommended by the Committee.
“fastest-mile” speeds. Since the Committee has no data or in-
For cases in which the chimney lining (brick, steel, or oth-
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
sample chimneys. The effects of this fevision are discussed factor of 0.89. For values of a below about 20 deg, a further
more fully in Section 5.3. correction is required, leading to the values of the parameter
The formulas are also derived for cmss sections with one Q defined in Section 5.5. I .
or two openings in, or partly in, the compression zone. No re- Thus the correction factor, or the parameter Q, achieves a
duction in the forces and moments due to reinforcing steel is close equivalencebetween the resulting values of (a) and (b)
made to allow for the reduction in the distance of the addi- previously stated for the "thereby corrected" rectangular
tional vertical reinforcement on each side of the opening, stress block and the stress block based on the Hognestad
provided per Section 4.4.6. stress-strain relationship, yet retains the simplicity of the
rectangular stress block.
5.5-Nominal moment strength 55.6 Due to thermal exposure of the concrete chimneys,
The formulas for the nominal moment strength of chimney the temperature drop across the wall reduces the nominal
cross sections are obtained based on the design assumptions strength of chimney sections. This effect is accounted for by
of AC1 318, except as modified under Section 5.1.2 of this reducing the specified yield strength of steel and specified
standard. The derivations of the formulas are given in compressive strength of concrete.
Appendix A. The derivation of equations is included in Appendix A.
.
The factored vertical load P,, and the corresponding nom-
inal moment strength MI, are expressed in dimensionless
form, as given in Section 5.5.1 by Eq. (5-2) and (5-IO), re- SI = 2 ~ , K , ~ ~ r t f , ’[(y- a ) c o s a - siny + sina]
spectively. ( 1 - cosa)
Also a procedure to account for the temperature effects in
the vertical and horizontal directions is outlined. or
Forces are designated as follows:
SI= 2&,, K, O, rtf,’ Q’
design moment strength of the section
nominal moment strength of the section
2 = 2(JC- WP,
s rqv
factored moment acting on the section
total force in the concrete compressive but
stress block
factored vertical load acting on section
P t f v = Wrh’
moments of P, SI,S2, S3,S, about neutral
axis, respectively
S2 = 2(n - y)rto,f,.’
tensile force where steel stress is below
yield point, from a to y
tensile force where steel stress is at yield P = 2(2 - nlß)rt 0.85A.’
9
point, from y to JC
compressive force in steel where stress is = 1.7rtf,.’(z-n1ß)
below yield point, from p to a
compressive force in steel where stress is = 1.7r&.’ h
at yield point, from O to p
capacity-reduction factor where
h =t - n l ß
From Fig. 5.5.l(a) and 5.5.l(b)
COS^ = COSCI + [( 1 - ~~~a)/&,~,]cfi/E,,)
COST = 1 - ß 1 ( i -cosa)
COS^ = COSE - [( 1 - cosa)/~,,](f,/E,) s3 = 2L ar(Cose-
r(l -cosa)
E E p
*
K, = E,/&.
nI = number of openings in the compression zone -
- 2 E, Es P rt (sine - 0 c 0 s a a) ~
f
sI'= E, ? O, J ,
where
= 2O&; p
1 - cosa)
JI = U/(
Sum of vertical forces must equal zero, therefore
or
Pu= P + s3 + s4 - SI - s,
J I = [2(yr - a)cos2a+ 3sina cosa - 4COSCC sinyr
= 1.70rtf,'h + 2&, K, O, rtf,.'Q3 + 20, rtfcp + sinyr c o s y + (yr - a)]/(I - cosa)
- 2&, K, O, rlJ;.'Q' - 20, &'(x - v)
Pu =KI
S2' = 2
K p,rqy r( cosa - cose)&
+
= 1.70h 2&,K,0,(Q3 - Q') + = 22p,q,. (@cosa- sine);
2o,[p - (X - yr)l
= 2 3 p , tf,[(n: - yr)cosa + sinyr]
= 1.701+ 2&, K, O, QI+ 20, hl
but
where
PA. = ~ t f c '
h=z-nlß therefore
S,' = 2?&.'0,J2
sinyr- siny-(yr-p)cosa
QI =
(1 - cosa) where
-- 2&,K e a trLtf,'
( 1 - cosa)
2
- 2&,Keo,r ifc'
-
(1 - cosa)
[(w - a)cos2a- 2cosa(siniy- sina) + (1/2)(iy- a) Let
+ (1/4)(sin2iy- sin 2a)] J3 = 2[ I/( I - cosa)
LetJ=[ ]
or
= (yr - a)cos2a + 2 sina cosa - 2 cosa siniy J3 = [a- p + sina cosa - sinp cosp - 4cosa(sina - sinp)
+ ('/2)siniycosy - ('/&ina cosa + (I/&iy - a) + 2(a- p)cos2a]/(1 - cosa)
or therefore
therefore
s,' = 2?&!0~4
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
where
For P' with one opening in compression zone [Fig. M,,I?&.' = (P,cosdr&.') + K2
5.5.1(a)]
where
".
P' = 2r10.85t.'
K2 = 1.70R + &,Ke~,(Ji+ 53) + 20f(52 + 54)
b(% - rcosa) -
1
r( cose - cosar)d9
or
n1=y=ß=O Y-B<T
The situation is the same as for no openings in the com- It is conservative and convenient to use the same value for
pression zone with fy‘ on the leeward side as well.
2=6 Vertical temperature stresses in concrete eflect on f,‘
A=1 -
Face -1 1
P(1 +Y,) 1 +Yi
= ratio, outside steel area to total steel area
LOAD DIAGRAM
fY‘(c) = fY - i'05fsTc
f,”(~) = fc’- 1.05f”,Tc
p’
I for combination with temperature
e, = areT, 11
Since rotation is prevented, corresponding stresses are in-
0.003E, I fy '( c )
n duced
In concrete (inside)
Lmid in compression steel
.f34=&.
f,."(c)=A.'
pT.ï =fTSYI'P't
in/in
--``,``,,,`,,```,,`,`,``,````,,-`-`,,`,,`,`,,`---
12. Simiu, E.: Marshall, R. D.: and Haber, S., “Estimation of Along-
Wind Building Response,” Proceedings, ASCE, V. 103, ST7, July 1977.
pp. 1325- 1338.
c’ = -p’n(yl’ + i ) + 13. Vickery, B., “Across-Wind Loading on Reinforced Concrete Chim-
neys of Circular Cross Section,” Boundan Layer Wind Tunnel Reporí,
BLWT-3-1993, University of Western Ontario, Dec. 1993.
14. ïdravkokvich, M. M., “Review of Flow Interference Effects between
Wo Cylinders in Various Arrangements,” Journul of F1uiú.s Engineering,
APPENDIX C-REFERENCES V. 99, 1977, p. 6 18.
C.l -Recommended references 15. Vickery, B. J., and Daly, A., “Wind Tunnel Modelling as a Means of
American Concrete Institute Predicting the Response of Chimneys to Vortex Shedding,” Enginerring
307-69 Specification for the Design and Construction of Structures, V. 6, No. 4, Guildford, Oct. 1984, pp. 363-368.
Reinforced Concrete Chimneys 16. Ruscheweyh, H., “Problems with In-Line Stacks: Experience with
Full-Scale Objects,” Engineering Strucrures, V. 6, No. 4. Guildford. Oct.
307-88 Standard Practice for the Design and Construc- 1984, pp. 340-343.
tion of Cast-in-Place Reinforced Concrete 17. Dryden, H.li., and Hill, G. C., “Wind Pressure on Circular Cylinders
Chimneys and Chimneys,” Research Paper No. 221. National Bureiiu of Standards,
318 Building Code Requirements for Structural Washington, D.C., 1930. Also, NBS Journal ofReseurcb, V. 5 , Sept. 1930.
Concrete 18. ASCE Task Committee on Wind Forces, “Wind Forces on Struc-
tures,” Transactions, ASCE, V. 126. Part II, 1961. pp. I 124- I 198.
505-54 Standard Specification for the Design and Con-
19. Okamoto, T.. and Yagita, M.,“Experimental Investigation Flow Past
struction of Reinforced Concrete Chimneys a Circular Cylinder of Finite Length Placed Normal IO a Uniform Stream,”
550R-93 Design Recommendations for Precast Concrete Bulletin, Japan Society of Mechanical Engineers (Tokyo), No. 16. 1973, p.
Structures 805.
American Sociery of Civil Engineers 20. Task Committee on Steel Chimney Liners, Design and Construction
of Steel Chimney Liners,American Society of Civil Engineers, New York,
ASCE 7-88 Minimum Design Loads for Buildings and 1975,226 pp.
Other Structures (formerly ANSI A58.1) 21. “NEHRP 1994 Recommended Provisions for the Development of
ASCE 7-95 Minimum Design Loads for Buildings and Seismic Regulations for New Buildings Prepared by the Building Seismic
Other Structures Safety Council.”
22. Mokrin, Z. A. R., and Rumman, W. S., “Ultimate Capacity of Rein-
forced Concrete Members of Hollow Circular Sections Subjected to Mono-
American Concrete Institute tonic and Cyclic Bending,” AC1 JOURNAL, Proceedings V. 82, No. 5, Sept.-
P.O.Box 9094 Oct. 1985, p ~653-656.
.
Farrnington Hills, Mich. 48333-9094 23. Rumman, W. S., and Sun, R. T.,“Ultimate Strength Design of Rein-
forced Concrete Chimneys,” AC1 JOURNAL, Proceedings V. 74, No. 4, Apr.
1977, pp. 179- 184.
American Society of Civil Engineers
24. Hognestad, E., “Study of Combined Bending and Axial Load in
1801 Alexander Bell Drive Reinforced Concrete Members,” Bulletin No. 399, Engineering Experi-
Reston, Va. 20191 ment Station, University of Illinois. Urbana, 1951, 128 pp.