Quality Assurance Plan For MV Switchgear (Type - Unigear/Leangear Cubicle With " Vd4/Vind - Breaker")
Quality Assurance Plan For MV Switchgear (Type - Unigear/Leangear Cubicle With " Vd4/Vind - Breaker")
SUPPLIER NAME & ADDRESS: Sale Order No. -4202745308 -01 & 02 Issued by ELDS PAIS-QA
ABB India Ltd.
Plot No. 79, Street No. 17,
MIDC Satpur, Nashik -
Customer -TRIVENI TURBINES
PO No. -PO NO : 2000028582 DATE : 18.05.2023
Item : For MV Switchgear panel upto 11 kV
Revision No. 00
Date : 25/05/2023
QAP No. 1VYN479999-262
ABB
422007
INSPECTION BY
SL. COMPONENT & TYPE OF QUANTUM OF REFERENCE FORMAT OF M N C
CHARACTERISTICS ACCEPTANCE NORM REMARKS
NO. OPERATONS CHECK CHECK DOCUMENT RECORDS ABB/ABB Sub- Customer/End
TPI
Supplier client
Alu- Zinc / a) Dimensions Measurement a) 5 samples / type (EN 10346/ ASTM A 792) (EN 10346/ ASTM A 792)
Supplier Test
1 Galvanised sheet/ b) Finish Visual b) 100% /EN10346/ IS 277 /EN10346/ IS 277 P/R R R
Certificates
CRCA / Stainless steel c) Material composition Measurement c)1 pc min. /IS 513/IS 6911 /IS 513/IS 6911
B ) COMMON COMPONENTS
1 Breaker Type - a) Measurement of resistance of IEC : 62271-100 & IEC : 62271-100 & Routine Test
Electrical '100 % P W W
VD4/Vind main circuit. Approved Drg. Approved Drg. Certificates
b) Routine functional test ( On no IEC : 62271-100 & IEC : 62271-100 & Routine Test Customer inspection
Electrical '100 % P W W
load) Approved Drg. Approved Drg. Certificates on sample breaker of
i) 5 closing & 5 opening operation at each type/rating
" '100 % " " " P W W
specified minimum voltage 10 %
ii) 5 closing & 5 opening operation at
" '100 % " " " P W W
specified maximum voltage
QUALITY ASSURANCE PLAN FOR MV SWITCHGEAR ( TYPE - UNIGEAR/LEANGEAR CUBICLE WITH " VD4/Vind - BREAKER" )
SUPPLIER NAME & ADDRESS: Sale Order No. -4202745308 -01 & 02 Issued by ELDS PAIS-QA
ABB India Ltd.
Plot No. 79, Street No. 17,
MIDC Satpur, Nashik -
Customer -TRIVENI TURBINES
PO No. -PO NO : 2000028582 DATE : 18.05.2023
Item : For MV Switchgear panel upto 11 kV
Revision No. 00
Date : 25/05/2023
QAP No. 1VYN479999-262
ABB
422007
INSPECTION BY
SL. COMPONENT & TYPE OF QUANTUM OF REFERENCE FORMAT OF M N C
CHARACTERISTICS ACCEPTANCE NORM REMARKS
NO. OPERATONS CHECK CHECK DOCUMENT RECORDS ABB/ABB Sub- Customer/End
TPI
Supplier client
A ) RAW MATERIAL INSPECTION k) Paint shade verification and Dry film IEC:62271-200/ IEC:62271-200/ Routine Test
visual/ meas K) Sample panel P W W
thickness, adhesion test Approved Drg. Approved Drg. Report
l) Mechanical operation & interlocks IEC:62271-200/ IEC:62271-200/ Routine Test
Mechanical l) 10% of lot P W W
check Approved Drg. Approved Drg. Report
m) Measurement of resistance of IEC:62271-200/ IEC:62271-200/ Routine Test
Electrical m) Sample panel P W W
main circuit Approved Drg. Approved Drg. Report
n) Secondary Current Injection for IEC:62271-200/ IEC:62271-200/ Routine Test
Electrical n) 100 % P W W
CT's and relays Approved Drg. Approved Drg. Report