Detail "A": SF Power Circuit Breaker Bushing Current Transformers
Detail "A": SF Power Circuit Breaker Bushing Current Transformers
8
01
QTY SEQ PART OR MATL. NO. DESCRIPTION
1 1 666C46202 BREAKER BLANK NAMEPLATE, SS
DETAIL "A" 1 2 666C53802 NMP, OPER MECH BLANK, SS
(SCALE 1" = 1") 13 3/16 1 3 660A94902 C.T. LEGEND NAMEPLATE, SS
A 335 A
1 4 663B72301 NAMEPLATE, CURRENT TRANSFORMER SS
SEE DETAIL A 1 5 681B42301 NAMEPLATE
11/64
11/64
5/32 BOM 2 200 200 300 100
X5 X4 X3 X2 X1 3
MAXIMUM VOLTAGE 550 kV SHORT CIRCUIT CURRENT 63 kA MARKED TURN SECONDARY
MARKED TURN SECONDARY
LINE SIDE TO GROUND CAPACITANCE REQUIRED WITHIN 300 FT OF BREAKER RATIO RATIO TAPS RATIO RATIO TAPS
N/A NEEDED FOR 90% SHORT LINE FAULT 500/5 100-1 X1-X2 2000/5 400-1 X3-X5
TYPICAL MOUNTING HOLE POSITIONING FREQUENCY 60 Hz IMPULSE WITHSTAND 1800 kV 1000/5 200-1 X3-X4 2500/5 500-1 X2-X4
FOR EACH NAMEPLATE WEIGHT WITH GAS 29,370 lbs INTERRUPTING TIME 2 CYCLES 1000/5 200-1 X4-X5 3000/5 600-1 X1-X4
B B
1 GAS PER BREAKER 1,254 lbs YEAR OF MANUFACTURE 3 1500/5 300-1 X2-X3 3500/5 700-1 X2-X5
CONTINUOUS CURRENT 4000 A WEIGHT WITHOUT GAS 28,116 lbs 2000/5 400-1 X1-X3 4000/5 800-1 X1-X5
VOLTAGE RANGE FACTOR"K" 1.0 INSTRUCTION MANUAL 4
SWITCHING IMPULSE TERM.-GND 1175 kV TERM.-TERM. 1300 kV
ABB Inc.
LOW PRESSURE ALARM 76 psig 3 STAMP MONTH & YEAR OF MANUFACTURE
Mount Pleasant, PA U.S.A.
LOW PRESSURE AUTO TRIP & BLOCK CLOSE 72 psig
SPRING CHARGE: 4 STAMP INSTRUCTION MANUAL NUMBER
NORMAL TRAVEL 1.63 IN TO 3.29 IN
ABB IS A REGISTERED TRADEMARK OF ABB ASEA BROWN BOVERI LTD.
5 MANUFACTURED BY/FOR A HITACHI POWER GRIDS COMPANY BYPASS VALVE OPERATION 5 STAMP CUSTOMERS PURCHASE ORDER NUMBER
PUMP MOTOR
* **
3.15 IN
OFF 3.29 IN ON
LOW ENERGY ALARM 2.68 IN 6 STAMP SERIAL NUMBER OF MECHANISM
BLOCK CLOSE 1.63 IN
BUSHING CURRENT TRANSFORMERS 7
AUTO TRIP 1.20 IN STAMP MECHANISM ASSEMBLY NUMBER
BUSHING MANUFACTURERS MAX ACCURACY CURVE
POCKET NO NUMBER TYPE RATIO SPECIAL CLASS NUMBER
4
UPPER 1-3-5 943A400-01 MR 4000/5 C800 5400
8 STAMP WIRING DIAGRAM NUMBER
UPPER 2-4-6 943A400-01 MR 4000/5 C800 5400 0.039 IN BEYOND PUMP MOTOR OFF
D
UPPER
1-3-5 943A400-01 MR 4000/5 C800 5400
*** A
4 MIDDLE
UPPER 943A400-01 MR 4000/5
MIDDLE 2-4-6 C800 5400
LOWER
MIDDLE
1-3-5 943A400-01 MR 4000/5 C800 5400 ABB Inc.
Mount Pleasant, PA U. S. A.
LOWER 943A400-01 MR 4000/5
2-4-6 C800 5400
MIDDLE
LOWER 1-3-5 943A401-01 MR 4000/5 C800 5401
LOWER 2-4-6 943A401-01 MR 4000/5
* C800 5401
TRF = 2.0
* 0.3B1.8
*
E B
IN BUSHING CT, METERING CT 943A401-01 WAS
AT UPPER POSITION 1-3-5 & 2-4-6 WITH CURVE
NO. 5401 & ACCURACY CLASS * 0.3B1.8.
PRK / KKS
REV. DESCRIPTION & DATE
JULY. 04, 2023