30XA Fixed Speed 080-501

30XA Variable Speed 140-352


30HXA,HXC076-271
Ground-Fault Interrupter
Convenience Outlet Accessory

Installation Instructions
Part No. 30GT-911---049
For 115 vac, 60 Hz Control Circuit Applications Only
SAFETY CONSIDERATIONS INSTALLATION
Installation of this accessory can be hazardous due to elec- 1. Inspect package contents for missing or damaged parts.
trical components and equipment location (such as a roof or File a claim with the shipping agency if parts are dam-
elevated structure). aged, and notify your Carrier representative if any item is
Only trained, qualified installers and service technicians missing.
should install and service this equipment. 2. Open and tag all electrical disconnects.
When installing this accessory, observe precautions in the 3. Open the unit control box door.
literature, on labels attached to the equipment, and other safety 4. Install the GFI-CO in the opening provided using the
precautions that apply. screws provided. See Fig. 1-4.
• Follow all safety codes. 5. Referring to Fig. 1-4, connect the black wire (in the unit)
• Wear safety glasses and work gloves. from FU 1 in 30HXA,HXC units (TB9-L1 in 30XA
• Use care when handling and installing this accessory. units) to either brass screw on the GFI-CO. Connect the
white wire (in the unit) from TB4-2 in 30HXA,HXC
WARNING units (TB9-L2 in 30XA units) to either silver screw on
the GFI-CO. Connect the green/yellow ground wire (in
Electrical shock can cause personal injury and death. Shut 30HXA,HXC units and field-supplied for 30XA units)
off all power to this equipment during installation. There from the GFI-CO to the unit ground near the GFI-CO. All
may be more than one disconnect switch. Tag all discon- wires are secured in the harness at the GFI-CO location.
nect locations to alert others not to restore power until work Remove the factory wire nuts to connect the wires to the
is completed. GFI-CO outlet.
6. Ensure that electrical connections are tight and restore
INTRODUCTION power to the unit.
The ground-fault interrupter convenience outlet (GFI-CO) 7. Test the GFI-CO by pressing its “Test” button and check-
accessory provides two auxiliary 115 v, 60 Hz outlets for hand ing for power at the outlet. If the accessory is incorrectly
tools, lights, and other devices. The GFI-CO also cuts power to wired, the GFI-CO may not trip and power may be pres-
the outlets in the event of a ground fault, and includes test and ent at the outlet. If power is present, disconnect all power
reset switches for this feature. See Table 1 for the contents of to the unit, correct the accessory wiring, reconnect the
the GFI-CO accessory package. unit power, and retest the outlet.
8. When the GFI-CO trips and no power is present at the
Table 1 — Accessory Package Contents outlet, restore the circuit by pressing the “Reset” button
ITEM PART NO. QUANTITY
on the GFI-CO.
GFCI (GFI-CO) HY01GF001 1 9. Remove tags from disconnects and close the control box
door.
The 30HXA,HXC076-271 and all 30XA units accept one NOTE: After the GFI-CO is installed, periodically test the
GFI-CO accessory. The 30HXA,HXC076-271 units provide ground fault feature as described in preceding Steps 7 and 8.
all necessary wires for accessory installation. However, 30XA
units require field-supplied ground wire for the installation of
the GFI-CO accessory.
NOTE: There is a 5-amp limit for the convenience outlet.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300140-01 Printed in U.S.A. Form 30-26SI Pg 1 2-15 Replaces: 30-22SI
LEGEND
FIOP — Factory-Installed Option a30-4540
FU — Fuse
GFI-CO — Ground Fault Interrupter Convenience Outlet
a30-4525 TB — Terminal Block
Accessory (Field Installed)
Wiring (Field-Installed)

CONTROL BOX

Fig. 1 — GFI-CO Location and Wiring — 30HXA,HXC076-271 Units

a30-4527 LEGEND
CB — Circuit Breaker
COMFORTLINK
NAVIGATOR
FIOP — Factory-Installed Option
GFI-CO — Ground Fault Interrupter Convenience Outlet
CARRIER
MAIN BASE BOARD
ISOL VLV — Relay Isolation Valve
NAV — Navigator™ Device
SW — Switch
TB — Terminal Block
Accessory (Field Installed)
Wiring (Field-Installed)
ENTER

CONTROL BOX

a30-4526

TB9-L1 TB9-L2

Fig. 2 — GFI-CO Location and Wiring — 30XA080-122 Units, 200/230 V;


30XA Fixed Speed 140-501 Units, All Voltages

2
a30-4528 LEGEND
COMFORTLINK
CB — Circuit Breaker
NAVIGATOR
FIOP — Factory-Installed Option
GFI-CO — Ground Fault Interrupter Convenience Outlet
CARRIER
CONTROL BOX SW — Switch
TB — Terminal Block
Accessory (Field Installed)
Wiring (Field-Installed)

ENTER

a30-4526

TB9-L1 TB9-L2

Fig. 3 — GFI-CO Location and Wiring — 30XA Fixed Speed 080-122 Units, 460/575 V

LEGEND
CB — Circuit Breaker
EMM — Energy Management Module
FIOP — Factory-Installed Option
GFI-CO — Ground Fault Interrupter Convenience Outlet
CONTROL BOX LEI — Local Equipment Interface
LON — Local Operating Network
SW — Switch
TB — Terminal Block
UPC — Universal Protocol Converter
Accessory (Field Installed)
GFI-CO Wiring (Field-Installed)

a30-4526
TB9-L1 TB9-L2

Fig. 4 — GFI-CO Location and Wiring — 30XA Variable Speed 140-352 Units, All Voltages

3
© Carrier Corporation 2015

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.