Professional Documents
Culture Documents
NDTS Lecture Notes
NDTS Lecture Notes
NDTS Lecture Notes
Unit 1
INTRODUCTION
Non-destructive testing (NDT) methods are techniques used to obtain information about the properties
or internal condition of an object without damaging the object. Non-destructive testing is a descriptive
term used for the examination of materials and components in such way that allows materials to be
examined without changing or destroying their usefulness. NDT is a quality assurance management
tool which can give impressive results when used correctly. It requires an understanding of the various
methods available, their capabilities and limitations, knowledge of the relevant standards and
specifications for performing the tests. NDT techniques can be used to monitor the integrity of the
item or structure throughout its design life.
Though non-destructive testing procedures are very straightforward to use, analyzing and interpreting
test findings is more difficult. As a result, analyzing the hardened characteristics of concrete
necessitates specialized expertise. Because the specimen is not loaded to failure in non-destructive
testing, the strength inferred or calculated cannot be anticipated to give absolute values of strength. As
a result, these approaches seek to test certain additional characteristics of concrete in order to
determine its strength, durability, and elastic parameters. Hardness, resistance to projectile penetration,
rebound number, resonance frequency, and capacity to transmit ultrasonic pulse velocity are some of
the characteristics of concrete.
Concrete’s electrical characteristics, as well as its ability to absorb, scatter, and transmit X-rays and
Gamma-rays, as well as its reaction to nuclear activation and acoustic emission, enable us to determine
its moisture content, density, thickness, and cement content.
Advantage
The greatest disadvantage of the conventional methods of testing concrete lies in the fact that
in-situ strength of the concrete can not be obtained without damaging the actual structure. Also the
test specimens are destroyed, once the test is performed and subsequent testing of the same specimens
is not possible. Thus, the effect of prolonged curing, weathering action and other time dependent
characteristics can not be correctly calculated. No matter how well a concrete mix is designed, there
are variations in mixing conditions, amount of compaction or curing conditions at site which cause the
variations in the final product. Conventional method of testing is not sufficient to predict the
performance of the structures under adverse conditions e.g. exposure to liquid, gas, and chemicals
radiation, explosion, fire, extreme cold or hot weather, marine and chemical environment. All such
severe exposure conditions may induce deterioration in concrete and impair the integrity, strength and
stability of the structure. Thus, conventional strength test does not give idea about the durability and
performance of the actual concrete in the structure. This gave the impetus to the development of non-
destructive methods for testing structural concrete in-situ.
Advantages of non-destructive testing of concrete are:
1. The equipment is simple to use.
2. Defects can be found without causing damage to the components.
3. The methods are rapid and precise.
4. Electrical, magnetic, and chemical characteristics can be used to sort components.
5. It’s simple to keep track of test results and other information.
Disadvantages of non-destructive testing of concrete are:
1. Manual operations need the attention of skilled experts.
2. Inspection of irregular components might be difficult.
3. The couplant’s requirement.
4. Water-resistant test items are required.
Thus, NDT methods are extremely valuable in assessing the condition of structures, such as bridges,
buildings, elevated service reservoirs and highways, etc. The principal objectives of the non-
1
Prepared by Dr. S.M. Laskar
destructive testing of concrete in situ is to assess one or more of the following properties of structural
concrete as below:
1. In situ strength properties
2. Durability
3. Density
4. Moisture content
5. Elastic properties
6. Extent of visible cracks
7. Thickness of structural members having only one face exposed
8. Position and condition of steel reinforcement
9. Concrete cover over the reinforcement.
10. Reliable assessment of the integrity or detection of defects of concrete members even when
they are accessible only from a single surface.
The standard life of R.C.C. frame structure is considered to be in the range of 50-60 years
approximately depending upon the use and the importance of the structure. But it has been observed
that many of the buildings completing just 50% of their life in coastal areas found to be in distressed
condition and this needs the evaluation of the strength of the building so that appropriate remedial
action can be taken to improve performance of the building depending upon the extent of deterioration
of the structure.
A structure may also get damaged due to fire, earthquake, explosion, etc. there could be loss
of strength and reduction in area of cross section due to fire depending on intensity of fire, temperature,
duration of fire and size of the structural member. Stability of such member becomes critical. It is
imperative to measure residual strength and assess stability by NDT means.
Earthquake effects could prevail on all members calling resistance to deformation and
distortions by way of ductility and toughness available with them. The resulting distress is more
pronounced at beam column junction, shear and flexural zones due to excessive deflection and
deformations exhibited by way of surface and deeper penetrated cracks. In such cases there is a loss
of integrity and stability of the structure. NDT is the only means to assess the extent of cracks and to
decide weather any structural damage has occurred. This decision helps to undertake appropriate
restoration or improvement strategy i.e., whether to go for grouting or strengthening of the member.
Due to explosion, structure is suddenly loaded by way of impact forces. The structure may get
heated up under high temperature generated by explosion and burn partially and deform when it is
under loads. Visible damage may immediately help to decide for replacement of the member. But an
invisible damage, which has distressed the structure, needs assessment for integrity, loss of strength
and stability. Assessment through NDT can guide for reuse of the structure.
NDT being fast, easy to use at site and relatively less expensive can be used for the following:
1. To test actual structure instead of representative cube samples.
2. To test any number of points and at any location.
3. Quality control and quality assurance management tool
4. To assess the structure for various distressed conditions
5. Damage assessment due to fire, chemical attack, impact, age etc.
6. To detect cracks, voids, fractures, honeycombs and week locations
7. To monitor progressive changes in properties of concrete & reinforcement.
8. To assess overall stability of the structure
9. Monitoring repairs and rehabilitation systems
10. Scanning for reinforcement location, stress locations.
Variables Involved
When considering the variables of the test material that affect test results we can group them into
three areas of concern:
1. Entry surface
2. Part size and geometry
2
Class notes on Non-Destructive Testing of Structures
3. Internal structure
a. Surface Roughness
Surface roughness have several possible effects on the inspection of a test piece. In contact testing
roughness on a gross scale result from weld spatter, plate scale, dirt (sand) and rough cast surfaces
from sand casting. These irregularities cause some points of contact to push away the couplant and
force it into the lower areas around the probe. If the couplant is not sufficiently viscous it drains away
quickly and fail to couple the probe to the test piece (ref. fig. below).
In addition to reduced coupling, which reduces signal amplitudes, the rough surface increases the rate
of wear on the probe. On an otherwise smooth surface isolated protrusions such as weld spatter can
hinder or stop probe motion or in the case of mechanized systems there may be sufficient force to
move the probe past the obstruction but this could result in damaging the probe by either tearing it
from its mounting or severely scoring the plastic wedge. When the dirt on the test piece is very fine
(similar to a flour texture) coupling can be prevented due to surface tension preventing the liquid
couplant penetrating to the metal. Unless a transfer value has been established between test piece and
calibration piece, this could go undetected.
b. Surface Coatings
Surface coatings are added to protect a surface from corrosion or to enhance its appearance. Thin films,
such as oxide layers, anodizing layers or electroplated finishes, and the slightly thicker coatings of
paint or lacquer are usually well bonded to the surface. Quality of bond may be compared to the
uncoated reference block by a simple transfer value. Even a slight loss due to the coating may be
preferable to removing the coating and trying to inspect on the rough surface it hides. When thickness
testing is done on a painted surface the paint thickness can add error to the reading.
c. Couplant Condition
Both contact and immersion methods utilize intervening media to transfer sound from the probe into
the test piece and back to the receiver. With immersion methods it is accomplished by a single fluid
medium. In contact testing there are nearly always at least two intervening media; the delay-line or
protective face and the thin film of coupling fluid or grease. Attenuation and acoustic velocity are the
two main properties that dictate the performance of a couplant. Attenuation affects amplitude of the
signal and velocity will determine both transit time and refracted angles.
But attenuation and velocity of couplants are not independent properties. Each is a function of other
parameters. Unless these parameters are controlled or in some way compensated for, gross variations
from the reference value or calibration conditions can result.
3
Prepared by Dr. S.M. Laskar
for contact testing on curved surfaces. When a flat probe is used on a convex curved surface only a
portion of the probe makes contact. This reduces the amount of sound that can be transferred to and
from the test piece. As a result sensitivity compared to coupling to a flat piece is reduced. The
proportion of sound reduction compared to a flat piece is a function of the curvature of the part, the
crystal diameter and the coupling ability of the couplant via its viscosity.
Some sources also consider the relative hardness of the probe face with a greater coupling or
contouring available from softer material such as plastics and virtually no contouring available.
3. Internal Structure
The final aspect of material variations affecting test results is the structure of material under test.
Material parameters are a function of makeup and environmental conditions. Makeup is determined
by design and processing. Whether the material under test is steel, aluminium or fibre-composite,
variations can occur by design. Proportion of resin to fibre vary in composites and metals may have
many alloying variations. In addition, metal grain structure can be varied by alloy, heat treatment and
working. All these factors provide differences in the results of ultrasonic tests manifested as variations
in velocity or attenuation. Also, just as temperature and pressures were noted to change velocity and
attenuation in couplants so too will the material under test be similarly affected by these externally
controlled conditions.
4
Class notes on Non-Destructive Testing of Structures
Unit 2
QUALITY TESTS
5
Prepared by Dr. S.M. Laskar
3. Endoscopy
4. Gamma Ray Radiography
1. Rebound Hammer
Damage – Fire; Blast
2. Ultrasonic Pulse Velocity
1. Ultrasonic Pulse Velocity
2. Acoustic Crack Detector
3. Dye Penetration Test
Cracks - Water Tanks; Pavements
4. X-Ray Radiography
5. Gamma-Ray Radiography
6. Crack Scope
1. Rebar Locator
Steel – Location; Cover; Size
2. Rebar Scanner
1. Half-Cell Potential
2. Resistivity
Corrosion
3. Carbonation
4. Chloride Content
Condition Endoscope/Borescope
1. Tapping
2. Pulse-Echo
Integrity & Performance 3. Acoustic Emission
4. Rader
5. Load Test
Principle of RH Test
The test is based on the principle that the rebound of an elastic mass depends on the hardness of the
surface upon which it impinges. When the plunger of the rebound hammer pressed against the surface
of the concrete, the spring controlled mass rebounds and the extent of such rebound depend upon the
surface hardness of concrete. The surface hardness and therefore the rebound is taken to be relation to
the compressive strength of concrete. The rebound is read off along a graduated scale and is designated
as the rebound number or rebound index.
6
Class notes on Non-Destructive Testing of Structures
Working of Rebound Hammer
A schematic cut way view of Schmidt’s rebound hammer is shown in Fig. 2.1. The hammer weight
about 1.8 kg and is suitable for use both in a laboratory and in the field. When the plunger of rebound
hammer is pressed against the surface of concrete, a spring-controlled mass rebounds and the extent
of such rebound depends upon the surface hardness of concrete.
The rebound distance is measured on a graduated scale and is designated as rebound number.
Basically, the rebound distance depends on the value of kinetic energy in the hammer, prior to impact
with the shoulder of the plunger and how much of that energy is absorbed during impact. The energy
absorbed by the concrete depends on the stress-strain relationship of concrete. Thus, a low strength
low stiffness concrete will absorb more energy than high strength concrete and will give a lower
rebound number.
Correlation Procedure
Each hammer is provided with correlation curves developed by the manufacturer using standard cube
specimens. However, the use of these curves is not recommended because material and testing
conditions may not be similar to those in effect when the calibration of the instrument was performed.
A typical correlation procedure is given as below:
7
Prepared by Dr. S.M. Laskar
1. Prepare a number of 150 mm cube specimens covering the strength range to be encountered
on the job site. Use the same cement and aggregates as are to be used on the job. Cure the
cubes under standard moist curing room conditions.
2. After capping, place the cubes in a compression testing machine under an initial load of
approximately 15% of the ultimate load to restrain the specimen. Ensure that cubes are in
saturated surface dry conditions.
3. Make 5 hammer rebound readings on each of four moulded faces without testing the same spot
twice and minimum 20 mm gap from edges.
4. Average the readings and call this the rebound number for the cube under test.
5. Repeat this procedure for all the cubes.
6. Test the cubes to failure in compression and plot the rebound numbers against the compressive
strength on a graph.
7. Fit a curve or a line by the method of least squares. It is important to note that some of the
curves deviate considerably from the curves supplied with the hammer.
Limitations
Although the rebound hammer provides a quick inexpensive means of checking the uniformity of
concrete, it has serious limitations and these must be understood clearly for interpretation of test
results.
9
Prepared by Dr. S.M. Laskar
There are three possible ways of measuring pulse velocity through concrete:
a. Direct Transmission (Cross Probing) through Concrete: In this method transducers are held
on opposite face of the concrete specimen under test as shown in fig. The method is most
commonly used and is to be preferred to the other two methods because this results in
maximum sensitivity and provides a well-defined path length.
b. Semi-direct Transmission through Concrete: Sometimes one of the faces of the concrete
specimen under test is not accessible, in that case we have to apply semi-direct method as
shown in fig. In this method, the sensitivity will be smaller than cross probing and the path
length is not clearly defined.
c. Indirect Transmission (Surface Probing) through Concrete: This method of pulse
transmission is used when only one face of concrete is accessible. Surface probing is the least
satisfactory of the three methods because the pulse velocity measurements indicate the quality
of concrete only near the surface and do not give information about deeper layers of concrete.
The weaker concrete that may be below a strong surface cannot be detected. Also in this
method path length is less well defined. Surface probing in general gives lower pulse velocity
than in the case of cross probing and depending on number of parameters.
10
Class notes on Non-Destructive Testing of Structures
Table 2.2 Velocity Criteria for Concrete Quality Grading (as per Table 2 of IS 13311 (Part 1) 1992)
Pulse Velocity by Cross Probing Concrete Quality
Sr. No.
(km/sec) Grading
1. Above 4.5 Excellent
2. 3.5 to 4.5 Good
3. 3.0 to 3.5 Medium
4. Below 3.0 Doubtful
Note: In case of doubtful quality of concrete, it may be necessary to carry out further tests.
Combined methods
There are different non-destructive testing methods which can be broadly classified as those which
measure the overall quality of the concrete, dynamic or vibration methods like resonance frequency
and ultrasonic pulse velocity tests and those which involve measurement of parameters like surface
hardness, rebound, penetration, pull-out strength etc. are believed to be indirectly related to the
compressive strength of concrete. In addition, radiographic, radiometric, nuclear, magnetic and
electrical methods are also available. Since such non-destructive tests are at best indirect methods of
monitoring the particulars, characteristics of concrete. The measurements are influenced by materials,
concrete mix proportions and environmental factors. When the data of the materials and mix
proportions used in the construction are not available, as is often the case. In view of the limitation of
the methods for the predicting the strength of concrete in the structure, IS 13311 (Part 1) 1992 has
suggested to use combined method of ultrasonic pulse velocity and rebound hammer methods to
alleviate the errors arising out of influence of materials, concrete mix proportions and environmental
parameters on the respective measurement.
The use of more than one methods are capable of providing useful information and statically
improved accuracy for estimation of in situ strength of concrete.
Combination of ultrasonic pulse velocity method and Schmidt rebound hammer may result much
better estimation of strength of concrete because the influence of certain factors in the composition of
the concrete and its curing are minimized.
11
Prepared by Dr. S.M. Laskar
Unit 3
SEMI-DESTRUCTIVE TESTS
A. Windsor Probe (Penetration Resistance Test)
Penetration resistance test is conducted on concrete structures using Windsor Probe test machine. In
this test method, a steel probe is fired on the concrete surface by a sudden explosion. The penetration
is inversely proportional to the strength of concrete. The result of the test is influenced by aggregate
strength and nature of formed surfaces of concrete.
The purpose of the penetration resistance test is used to determine the uniformity of concrete, specify
the poor quality or deteriorated concrete zones, and evaluate the in-place strength of concrete. It is
sometimes necessary to estimate the strength of concrete on-site for early form removal or to
investigate the strength of concrete in place because of low cylinder test results.
Due to the nature of the equipment, it cannot and should not be expected to yield absolute values of
strength. The penetration resistance test on hardened concrete can be carried out based on the
procedures and specifications of the Standard Test Method for Penetration Resistance of Hardened
Concrete (ASTM C 803/ 803M- 97) or British Standard (BS 1881 Part 207).
Apparatus
1. Probe
Probe consists of driver unit used to drive the probe into the concrete and probe manufactured from
alloy-steel rod plated for corrosion protection, with a blunt conical end that can be inserted into the
driver unit and driven into the concrete surface.
Probes of 79.4-mm overall length and 7.9-mm diameter, with the penetrating end diameter reduced to
6.4 mm for approximately 14.3 mm in length, is suitable for testing concrete with a unit weight of
2000 kg/m3 or greater. Pins can be used instead of probe when the penetration resistance test is carried
out using this tool.
12
Class notes on Non-Destructive Testing of Structures
2. Measurement Equipment
Measurement equipment such as a Vernier caliper or depth gauge to measure the exposed length of a
probe to the nearest 0.5 mm. The measuring equipment shall include a reference base plate which is
supported on the concrete surface at three equally spaced points at least 50 mm from the probe to be
measured.
3. Positioning Device
A single device or a triangular device with holes at the three corners can be used for positioning and
guiding the probe and driver unit.
Sampling
1. Concrete to be tested should have gain enough strength so that the probe would not penetrate
more than one half the thickness of the concrete member
2. Maximum spacing between probes is 175 mm
3. Minimum spacing between probes is 100 mm
4. Minimum spacing between concrete and the edge of a concrete surface is 100mm.
5. A minimum of three firmly embedded test probes in a given test area constitute one test.
Testing Procedure
1. Place the positioning device on the surface of the concrete at the location to be tested.
2. Mount a probe in the driver unit
3. Position the driver in the positioning device
4. Fire the probe into the concrete.
5. Remove the positioning device and tap the probe on the exposed end with a small hammer to
ensure that it has not rebounded and to confirm that it is firmly embedded.
6. Place the measuring base plate over the probe and position it so that it bears firmly on the
surface of the concrete without rocking or other movement.
Limitations
1. Tests only on through the thin layers of concrete surface.
2. Fails to yield the absolute value of the strength.
3. Damages the structures by making holes.
4. The accuracy of this test is ± 25 %.
13
Prepared by Dr. S.M. Laskar
B. Pull out Test
The fundamental principle behind pull-out testing is that the test equipment designed to a specific
geometry will produce results (pull-out forces) that closely correlate to the compressive strength of
concrete. This correlation is achieved by measuring the force required to pull a steel disc or ring,
embedded in fresh concrete, against a circular counter pressure placed on the concrete surface
concentric with the disc/ring.
Types of Pull-out Tests:
Depending upon the placement of disc/ring in he fresh concrete, pull out test can be divided into 2
types,
1. LOK test
2. CAPO test (Cut and Pull-out Test)
LOK Test:
The LOK-test system is used to obtain a reliable estimate of the in-place strength of concrete in newly
cast structures in accordance with the pullout test method described in ASTM C900, BS 1881:207, or
EN 12504-3.
14
Class notes on Non-Destructive Testing of Structures
When selecting the location for a CAPO-TEST, ensure that reinforcing bars are not within the failure
region. The surface at the test location is ground using a planing tool and a 18.4 mm hole is made
perpendicular to the surface using a diamond-studded core bit. A recess (slot) is routed in the hole to
a diameter of 25 mm and at a depth of 25 mm. A split ring is expanded in the recess and pulled out
using a pull machine reacting against a 55 mm diameter counter pressure ring. As in the LOKTEST,
the concrete in the strut between the expanded ring and the counter pressure ring is in compression.
Hence, the ultimate pullout force F is related directly to compressive strength.
15
Prepared by Dr. S.M. Laskar
By measuring the pull-out force of a cast-in disc or expanded ring, the compressive strength of in-situ
concrete can be determined from the relationship in figure below to a great degree of confidence.
The pullout test produces a well defined in the concrete and measure a static strength property of
concrete. The equipment is simple to assemble and operate.
The compressive strength can be considered as proportional to the ultimate pullout force. The
reliability of the test is reported as good. It is superior to rebound hammer and Windsor probe test
16
Class notes on Non-Destructive Testing of Structures
because of greater depth of concrete volume tested. However, this test is not recommended for
aggregates beyond size of 38mm.
The major limitation of this test is that it requires special care at the time of placement of inserts to
minimize air void below the disc besides a pre-planned usage.
Uses:
1. Determine in-situ compressive strength of the concrete
2. Ascertain the strength of concrete for carrying out post tensioning operations.
3. Determine the time of removal of forms and shores based on actual in-situ strength of the
structure.
4. Terminate curing based on in-situ strength of the structure.
5. It can be also used for testing repaired concrete sections.
17
Prepared by Dr. S.M. Laskar
Unit 4
CORROSION TESTING
A. Profometer
(Detection of reinforcement location, size and corrosion)
Steel shares about 40 to 70% of the load in RCC. During last few decades it has been observed that,
corrosion of reinforcement in severe in structures near seashore and in the vicinity of chemical
industries. A lot of attention is needed for detecting this deterioration and protecting it with proper
treatment. Thus, due importance shall be given for measuring the size of bar and the amount of
corrosion.
Applications of Profometer
Profometer is used for:
1. Determination of bar arrangement
2. Determination of cover of reinforcement
3. Determination of bar diameter
18
Class notes on Non-Destructive Testing of Structures
Corrosion Mapping
Reinforcement in concrete will not corrode if the protective iron oxide film formed by the high
alkaline condition of the concrete pore fluid with a pH around 13 is maintained. This film gets
destroyed by chlorides or by carbonation, if moisture and oxygen are present, resulting in corrosion.
In the corrosion process anodic and cathodic areas are formed on the reinforcement, causing
dissolution of the steel and the formation of expansive corrosion products at the anode.
B. Half-cell Potentiometer
19
Prepared by Dr. S.M. Laskar
The risk of corrosion is evaluated by means of the potential gradient obtained, the higher the gradient,
the higher risk of corrosion. The test results can be interpreted based on the following table.
Table 3.1 Half Cell Potential Corresponding to Percentage Chance of Corrosion Activity
Half-cell potential (mv) relative to Cu-Cu sulphate Ref.
% chance of corrosion activity
Electrode
Less than -200 10%
Between -200 to -350 50% (uncertain)
Above -350 90%
Ground penetrating radar (GPR) for the nondestructive evaluation of concrete is a relatively recent
application for a mature technology. When a GPR transmitting antenna directs high-frequency radio
waves into a solid surface, the waves scatter and reflect as they encounter objects or boundaries with
different densities.
The reflected electromagnetic energy detected by the receiving antenna documents changes in the
structure and density of the material. This non-intrusive method allows sub-surface investigations of
structures, pavements, soil and rock, and detects variations in material properties like cracks and voids.
(Please refer to the research paper, “Ground Penetrating Radar for Concrete Evaluation Studies”
by Michael D. Gehrig, Derek V. Morris, John T. Bryant attached herewith)
21
Prepared by Dr. S.M. Laskar
Unit 5
22
Class notes on Non-Destructive Testing of Structures
23
Prepared by Dr. S.M. Laskar
B. Permeability Test
24
Class notes on Non-Destructive Testing of Structures
25
Prepared by Dr. S.M. Laskar
26
by:-
The screening is based on Code based Seismic Intensity, Building Type and Damageability Grade as
observed in past earthquake and covered in MSK/European macro-intensity
i. To identify if a particular building requires further evaluation for assessment of its seismic
vulnerability.
ii. To assess the seismic damageability (structural vulnerability) of the building and seismic
rehabilitation needs.
iii. To identify simplified retrofitting requirements for the building (to collapse prevention level) where
further evaluations are not considered necessary or not found feasible.
Zone II Low seismic hazard (damage during earthquake may be of MSK Intensity VI or
lower)
Zone III Moderate seismic hazard (maximum damage during earthquake may be upto MSK
Intensity VII)
Zone IV High seismic hazard (maximum damage during earthquake may be upto MSK
Intensity VIII)
Zone V Very high seismic hazard (maximum damage during earthquake may be of MSK
Intensity IX or greater)
4
When a particular damage Intensity occurs, different building types experience different levels of damage
depending on their inherent characteristics. For carrying out the Rapid Visual Screening, all four hazard
zones have been considered.
The basic vulnerability class of a building type is based on the average expected seismic performance for that
building type. All buildings have been divided into type A to type F based on the European Macroseismic
Scale (EMS-98) recommendations. The buildings in type A have the highest seismic vulnerability while the
buildings in type F have the lowest seismic vulnerability. A building of a given type, however, may have its
vulnerability different from the basic class defined for that type depending on the condition of the building,
presence of earthquake resistance features, architectural features, number of storeys etc. It is therefore
possible to have a damageability range for each building type considering the different factors affecting its
likely performance. Some variations in building type are therefore defined as A, B, B+ etc.
The RVS procedure presented here has considered different building types, based on the building materials
and construction types that are most commonly found in India. RCC buildings are presented in Tables A.1.
The likely damages to buildings have been categorized in different Grades depending on the seismic impact
on the strength of the building.
As per MSK Intensity scale the average values of these terms may be taken as
Few: 5-15% Many: 50% Most: 75%
Table A.3 is generally based on MSK descriptions.
Important buildings*: Hospitals, Schools, monumental structures; emergency buildings like telephone
exchange, television, radio stations, railway stations, fire stations, large community halls like cinemas,
assembly halls and subway stations, power stations, Important Industrial establishments, VIP residences
& Residences of Important Emergency person.
*Any building having more than 100 Occupants may be treated as Important for purpose of RVS.
For these important buildings the value of I is specified as 1.5, by which the design seismic force is
increased by a factor of 1.5. Now the seismic zone factors for zone II to V are as follows.
Zone II III IV V
Zone Factor 0.10 0.16 0.24 0.36
It is seen that one Unit change in Seismic Zone Intensity increases the Zone Factor 1.5 times.
Hence to deal with the damageability of Important buildings in any zone, they should be checked for one
Unit higher zone. The assessment forms are designed accordingly.
2) Special Hazards
There are some special hazardous conditions to be considered:
I. Liquefiable condition: Normal loose sands submerged under high water table are susceptible to
liquefaction under moderate to high ground accelerations; building founded on such soils will require
special evaluation and treatment.
II. Land Slide Prone Area: If the building is situated on a hill slope which is prone to land slide/ land
slip or rock-fall under monsoon and/or earthquake, special evaluation of the site and treatment of the
building will be needed.
6
III. Irregular Buildings:
Irregularities in buildings are defined in Cl.7.1 of IS: 1893 – 2002 under the following sub- heads:
i. Plan Irregularities: These are defined in Table 4 of the Code as follows:
a) Torsion Irregularity
b) Re-entrant Corners
c) Diaphragm Discontinuity
d) Out of Plane Offsets
e) Non – Parallel Systems
The Geometric Irregularities in building plans which can be easily identified are shown in Fig.A.2
These irregularities enhance the overall damage (increased grade of damage e.g. at re-entrant
corners). Such a building may be recommended for detailed evaluation.
ii. Vertical Irregularities: The following vertical irregularities may be seen in masonry
buildings (see Fig. A.3).
a) Mass Irregularity
b) Vertical Geometric Irregularity
c) In-Plane Discontinuity in vertical Elements Resisting Lateral Forces.
If any of these irregularities are noticed, the building should be recommended for detailed evaluation.
IV. Falling Hazard: Where such hazards are present, particularly in Zones IV & V, recommendations
should make reference to these in the survey report as indicated.
V. Type of Foundation Soil: IS 1893-2002 defines three soil types hard/stiff, medium & soft. No
effect of these is seen in the design spectra of short period buildings, T< 0.4 second, covering all
masonry buildings, hence the effect may be considered not so significant.
7
Table A.1: Reinforced Concrete Frame Buildings (RCF) and Steel Frames (SF)
Frame Description
Type
C a) RC Beam Post buildings without ERD or WRD, built in non-engineered way.
b) SF without bracings having hinge joints;.
c) RCF of ordinary design for gravity loads without ERD or WRD.
d) SF of ordinary design without ERD or WRD
C+ a) MR-RCF/MR-SF of ordinary design without ERD or WRD.
b) Do, with unreinforced masonry infill.
c) Flat slab framed structure.
d) Prefabricated framed structure.
D a) MR-RCF with ordinary ERD without special details as per IS: 13920, with ordinary infill
walls (such walls may fail earlier similar to C in masonry buildings.
b) MR-SF with ordinary ERD without special details as per Plastic Design Hand Book
SP:6(6)-1972.
E a) MR-RCF with high level of ERD as per IS: 1893-2002 & special details as per IS: 13920.
b) MR-SF with high level of ERD as per IS: 1893-2002 & special details as per Plastic
Design Hand Book, SP:6(6)-1972
E+ a) MR-RCF as at E with well designed infills walls.
b) MR-SF as at E with well designed braces
F a) MR-RCF as at E with well designed & detailed RC shear walls.
b) MR-SF as at E with well designed & detailed steel braces & cladding.
c) MR-RCF/MR-SF with well designed base isolation.
IMPORTANT NOTE:
Buildings having severe vertical irregularity e.g. open plinth, stilt floor called soft storey & those
having floating columns resting on horizontal cantilever beams are not covered in the above table &
will require special evaluation.
8
Table A.2: Grades of Damageability of RCC Buildings
9
Table A.3: Damageability Grades of RCC Buildings
NOTE:
NOTE:
1. As per MSK scale, few, Many and Most may be taken as: Few: 15%, Many: 50% and Most: 75%.
2. Buildings having vertical irregularity (see note under table 3) may under go severe damage in
seismic zones III, IV & V if not specifically designed. Hence they will require special evaluation.
Also buildings sited in liquefiable or landslide prone areas will require special evaluation for
seismic safety.
3. Buildings having plan irregularity may under go a damage of one grade higher in zones III, IV &
V. The sur veyor may recommend re-evakuation.
10
ZONE V MM IX OR MORE
ZONE IV MM VIII
ZONE III MM VII
ZONE II MM VI OR LESS
11
IV 17.3 %
III 30.4 %
TOTAL DAMAGEABLE AREA
~ 58.6 %
Photograph 1.7 Storey Ht: 1st ________, 2nd _________, 3rd__________ etc.
1.8 Total Covered Area; all floors (sq.m) ___________________
1.9 Ground Coverage (Sq.m):____________________________
1.10 Soil Type:__________1.11 Foundation Type:____________
1.12 Depth of Ground water table: ____________
1.13 Bldg. Type: Frame Pre-cast
Frame - Shear Wall Flat Slab Frame
1.14 Thickness of infill wall: Exterior _______ Interior ______
1.15 Struct. Dwg./Calculations available: Yes / No (If yes,attach)
1.16 Extn. to the original bldg. Yes/ No ( If.yes pl. indicate)
1.17 Location of Shear walls (if any)
1.18 Special Confining R/F in Beam/Column/joints:
1.19 Stair case: Separated Connected Enclosed
Sketch Plan with Length & Breadth
4.0 FALLING
2.0 OCCUPANCY 3.0 SPECIAL HAZARD HAZARD RECOMMENDED ACTION:-
3.1 High Water Table (within 1m) Ensure adequate maintenance.
2.1 Important buildings: Hospitals,
Schools, monumental structures; emergency & if sandy soil, then liquefiable If any Special Hazard 3.0 found
buildings like telephone exchange, television, 4.1 Chimneys , re-evaluate for possible
site indicated.
radio stations, railway stations, fire stations, retrofitting.
large community halls like cinemas, assembly Yes No
4.2 Parapets
halls and subway stations, power stations, 3.2 Land Slide Prone Site
Important Industrial establishments, VIP
residences & Residences of Important Yes No
Emergency person. 3.3 Severe Vertical Irregularity 4.3 Cladding
*Any building having more than 100 Yes No
Occupants may be treated as Important. 3.4 Severe Plan Irregularity
4.4 Others
2.2 Ordinary buildings:- Other buildings Yes No
having occupants <100
Surveyor will identify the Building Type; encircle it, also the corresponding damage grade. Date of Survey:______________
13
2 Rapid Visual Screening of RC/Steel Buildings for Seismic Hazards
Seismic Zone III Ordinary Building
(Also for Zone II Important Building)
1.1 Building Name_____________________________________
1.2 Use______________________________________________
1.3 Address:__________________________________________
________________________Pin ______________
1.4 Other Identifiers____________________________________
1.5 No. of Stories____________ 1.6 Year of Const.___________
Photograph 1.7 Storey Ht.: 1st _______, 2nd ________, 3rd__________ .etc.
1.8 Total Covered Area; all floors (sq.m) ___________________
1.9 Ground Coverage (Sq.m):____________________________
1.10 Soil Type:__________1.11 Foundation Type:____________
1.12 Depth of Ground water table: ____________
1.13 Bldg. Type: Frame Pre-cast
Frame - Shear Wall Flat Slab Frame
1.14 Thickness of infill wall: Exterior _______ Interior ______
1.15 Struct. Dwg./Calculations available: Yes / No (If yes,attach)
1.16 Extn. to the original bldg. Yes/ No ( If.yes pl. indicate)
1.17 Location of Shear walls (if any)
1.18 Special Confining R/F in Beam/Column/joints:
1.19 Stair case: Separated Connected Enclosed
Sketch Plan with Length & Breadth
4.0 FALLING RECOMMENDED ACTION:-
2.0 OCCUPANCY 3.0 SPECIAL HAZARD HAZARD
Ensure adequate maintenance.
2.1 Important buildings: Hospitals, 3.1 High Water Table (within 3m)
If any Special Hazard 3.0 found ,
Schools, monumental structures; emergency & if sandy soil, then liquefiable
4.1 Chimneys re-evaluate for possible
buildings like telephone exchange, television, site indicated.
radio stations, railway stations, fire stations,
prevention/retrofitting.
large community halls like cinemas, assembly Yes No If any of the falling hazard is
4.2 Parapets
halls and subway stations, power stations, 3.2 Land Slide Prone Site present, either remove it or
Important Industrial establishments, VIP strengthen against falling.
residences & Residences of Important Yes No
Emergency person. 3.3 Severe Vertical Irregularity 4.3 Cladding
*Any building having more than 100 Yes No
Occupants may be treated as Important. 3.4 Severe Plan Irregularity
4.4 Others
2.2 Ordinary buildings:- Other buildings Yes No
having occupants <100
Surveyor will identify the Building Type; encircle it, also the corresponding damage grade. Date of Survey:______________
14
3 Rapid Visual Screening of RC/Steel Buildings for Seismic Hazards
Photograph 1.7 Storey Ht.: 1st _______, 2nd ________, 3rd__________ .etc.
1.8 Total Covered Area; all floors (sq.m) ___________________
1.9 Ground Coverage (Sq.m):____________________________
1.10 Soil Type:__________1.11 Foundation Type:____________
1.12 Depth of Ground water table: ____________
1.13 Bldg. Type: Frame Pre-cast
Frame - Shear Wall Flat Slab Frame
1.14 Thickness of infill wall: Exterior _______ Interior ______
1.15 Struct. Dwg./Calculations available: Yes / No (If yes,attach)
1.16 Extn. to the original bldg. Yes/ No ( If.yes pl. indicate)
1.17 Location of Shear walls (if any)
1.18 Special Confining R/F in Beam/Column/joints:
1.19 Stair case: Separated Connected Enclosed
Sketch Plan with Length & Breadth
4.0 FALLING RECOMMENDED ACTION:-
2.0 OCCUPANCY 3.0 SPECIAL HAZARD HAZARD
C: evaluate in detail for need for
2.1 Important buildings: Hospitals, 3.1 High Water Table (within 5m) retrofitting
Schools, monumental structures; emergency & if sandy soil, then liquefiable If any Special Hazard 3.0 found ,
buildings like telephone exchange, television, 4.1 Chimneys re-evaluate for possible
site indicated.
radio stations, railway stations, fire stations, prevention/retrofitting.
large community halls like cinemas, assembly Yes No
4.2 Parapets If any of the falling hazard is
halls and subway stations, power stations, 3.2 Land Slide Prone Site present, either remove it or
Important Industrial establishments, VIP strengthen against falling.
residences & Residences of Important Yes No
Emergency person. 3.3 Severe Vertical Irregularity 4.3 Cladding URM infill : evaluate in detail for
need of retrofitting
*Any building having more than 100 Yes No
Occupants may be treated as Important. 3.4 Severe Plan Irregularity
4.4 Others
2.2 Ordinary buildings:- Other buildings Yes No
having occupants <100
15
4 Rapid Visual Screening of RC/Steel Buildings for Seismic Hazards
Photograph 1.7 Storey Ht.: 1st _______, 2nd ________, 3rd__________ .etc.
1.8 Total Covered Area; all floors (sq.m) ___________________
1.9 Ground Coverage (Sq.m):____________________________
1.10 Soil Type:__________1.11 Foundation Type:____________
1.12 Depth of Ground water table: ____________
1.13 Bldg. Type: Frame Pre-cast
Frame - Shear Wall Flat Slab Frame
1.14 Thickness of infill wall: Exterior _______ Interior ______
1.15 Struct. Dwg./Calculations available: Yes / No (If yes,attach)
1.16 Extn. to the original bldg. Yes/ No ( If.yes pl. indicate)
1.17 Location of Shear walls (if any)
1.18 Special Confining R/F in Beam/Column/joints:
1.19 Stair case: Separated Connected Enclosed
Sketch Plan with Length & Breadth
4.0 FALLING RECOMMENDED ACTION:-
2.0 OCCUPANCY 3.0 SPECIAL HAZARD HAZARD
C: evaluate in detail for need for
2.1 Important buildings: Hospitals, 3.1 High Water Table (within 3m) retrofitting to achieve type E, E+.
Schools, monumental structures; emergency & if sandy soil, then liquefiable If any Special Hazard 3.0 found ,
buildings like telephone exchange, television, 4.1 Chimneys re-evaluate for possible prevention/
site indicated.
radio stations, railway stations, fire stations, retrofitting.
large community halls like cinemas, assembly Yes No
4.2 Parapets If any of the falling hazard is
halls and subway stations, power stations, 3.2 Land Slide Prone Site present, either remove it or
Important Industrial establishments, VIP strengthen against fall.
residences & Residences of Important Yes No
Emergency person. 3.3 Severe Vertical Irregularity 4.3 Cladding URM infill : evaluate for need of
reconstruction or possible
*Any building having more than 100 Yes No retrofitting to level D.
Occupants may be treated as Important. 3.4 Severe Plan Irregularity
4.4 Others
2.2 Ordinary buildings:- Other buildings Yes No
having occupants <100
16
Prepared by:
Professor Anand S. Arya and Ankush Agarwal
under the GoI-UNDP Disaster Risk Management Programme
Email: anand.s.arya@undp.org, ankush.agarwal@undp.org
NATIONAL DISASTER MANAGEMENT DIVISION
Ministry of Home Affairs, North Block, New Delhi
Tel: 91-11-23093178; Tele/fax: 23094019, Email: ndmindia@nic.in; Website: www.ndmindia.nic.in
41
Ground Penetrating Radar for Concrete Evaluation Studies
ABSTRACT
Ground Penetrating Radar (GPR) is a geophysical imaging technique used for
subsurface exploration and monitoring. It is widely used within the forensic,
engineering, geological, mining and archeological communities. GPR provides an
ideal technique for concrete evaluation in that it has the highest resolution of any
subsurface imaging, non-invasive method and is far safer than other method such as
x-ray technology. Recent improvements in hardware, and in particular, software
processing have contributed to the rapidly expanding popularity and usability of this
technique.
______________
1
Bryant Consultants, Inc., 2033 Chenault Dr, Suite 150, Carrollton, Texas 75006.
Phone 972-713-9109, Email: mgehrig@geoneering.com, Website: geoneering.com
1
INTRODUCTION
Ground penetrating radar covers a wide area in a relatively short period of time for
concrete evaluation studies. Due to recent hardware and software advances, real
time cursory analysis can be performed at the site. Because of these and other
reasons, GPR has become an increasingly attractive method for the engineering
community, in particular for shallow, high resolution applications such as concrete
evaluation studies. Standard test methods and guides involving GPR have been
derived by the American Society for Testing and Materials (ASTM). ASTM D
4748-87 is a standard test method for the exploratory use of GPR for the
determination of pavement layer(s) thickness. A more recent and broad guide for
GPR usage for subsurface investigation is standardized in ASTM D 6432-99. This
ASTM guide provides a compendium of related GPR information useful for a wide
range of applications including concrete evaluation studies.
Ground penetrating radar directs electromagnetic energy into the subsurface. The
propagation of electromagnetic energy is described by Maxwell’s equation with the
electric component (E) orthogonal to the magnetic component (H) (Reynolds,
1997). For concrete evaluation studies, both components are equally important.
Concrete material is a low conductivity, non-metallic medium that is ideal for GPR
signal propagation. However, concrete typically has steel reinforcement, which is a
metallic and therefore completely reflects the GPR signal and shadows anything
directly below the metal. If applicable, the sub-base beneath a concrete unit is non-
metallic. The sub-base may be highly conductive soils (such as expansive clays)
that effectively attenuate the GPR signal propagation thereby limiting depth
penetration. The relative dielectric constant (ε) of non-metallic medium is a
function of three different materials within the medium – solid, fluid and gas
(Lytton, 1995). Therefore, for example, the relative dielectric constant for an
unsaturated soil is a combination of the relative dielectric constant of the air,
relative dielectric constant of water, relative dielectric constant of soil, porosity and
degree of saturation.
2
wave propagation velocity. Wave propagation velocities (V) through a given
medium are important to convert a time domain radargram model into a distance
domain radargram model.
OPERATION PRINCIPLES
There are several antenna manufacturers, antenna types, signal pre- and post- setting
options, operating frequencies, software packages, etc. to consider for a specific
application within the engineering and construction industry, geological,
environmental and/or archaeological fields. Each radar system must be designed to
meet the objective(s) of a given project. For concrete evaluation studies, there are
several options available – all of which have certain advantages and disadvantages.
For the evaluation of various concrete structures, which include streets/highways,
parking lots, bridge decks, pools, tilt wall panels, sidewalks, various foundation
systems and retaining walls, a versatile and highly portable radar system with a
ground coupled, monostatic antenna is suitable. However, for specialized projects,
such as road condition evaluation, an air-launched (horn) antenna is commonly used
due to the efficient data collection characteristic of this antenna. Currently, GPR
data can be collected with these air-launched antennae at highway speeds.
A typical radar system for concrete evaluation studies generally consists of a control
unit (computer), pulse generator, transmitting and receiving antennae and video
monitor. A bistatic antenna describes a radar system with two antennae, one to
transmit and the other to receive. An antenna that both transmits and receives is
defined as a monostatic antenna. There are advantages and disadvantages of each
antenna type for a given application; however, for concrete evaluation studies,
monostatic antennae are typically more advantageous due to higher data collection
and processing efficiency.
Figure 1 provides the primary components of a radar system used extensively for
several concrete evaluation studies. As previously stated, there are numerous
system variations and/or alterations which can be used effectively. The control unit
3
(A) comprises of an electronic data storage unit and pulse generator in one unit.
The monostatic 1.5 GHz antenna (B) is encased within a broom-like device (C),
which includes a survey wheel essential for horizontal spatial control. The monitor
display (D) allows for on-site cursory analysis. A hundred foot cable (E) attaches
the antenna to the control unit. A direct current (DC) power conversion unit (F)
may also be necessary if the power source originates from a 110-volt alternating
current source. More recent radar systems are now available that are more compact
for field portability.
(C)
(D)
(F)
(A)
(E) (B)
Reflection Strength
4
Like many other geophysical techniques employed, a material property contrast is
necessary for subsurface identification, qualification and/or quantification. For
example, seismic surveys, which utilize elastic strain energy, are reliant on
contrasting seismic velocities of media. The elastic strain energy for seismic
exploration is analogous to electromagnetic energy used for GPR exploration. The
velocities at which seismic waves propagate through any given medium are dictated
by the elasticity modulus and density. The velocity at which GPR propagates
through a medium is a function of the dielectric constant. Changes in moduli and
densities result in incident seismic wave reflections. Similarly for GPR, changes of
dielectric properties of two materials result in electromagnetic wave reflections.
The greater the dielectric contrast between two media, the greater amount of
reflected energy. The amount of energy reflected is a function of the dielectric
properties of adjacent media. The reflection coefficient (R) quantifies the reflective
strength between two adjacent media:
ε 2 − ε1
(1) R=
ε 2 + ε1
where ε1 and ε2 are the dielectric constants of media (or layers) 1 and 2,
respectively. Therefore, the larger the dielectric contrast between two media, the
larger the reflection coefficient and subsequently, layer delineation and subsurface
feature detection is more evident. Figure 2 plots the reflection coefficient of layer 1
with respect to a range of dielectric constants between 1 and 81. The dielectric
constant of layer 1 equals seven, which is typical for a concrete layer. As shown in
Figure 2, the larger the dielectric contrast, the stronger the reflection.
5
0.6
0.4
Reflection coefficient, R
0.2
Moderate Positive Reflection
0 Weak Reflection ε1 = 7
-0.4
Strong Negative Reflection
-0.6
0 10 20 30 40 50 60 70 80 90
c
(2) V =
ε
where c is the speed of light through air (0.3 m/ns). As shown in Figure 3, certain
underlying soil conditions such as wetter clay may have similar dielectric constant
as concrete, which would result in a weak reflection or no reflection at that interface
between the two medium. On the other hand, if an air-filled or water-filled void
space is present beneath the concrete slab, a strong wave reflection will occur at this
interface. The corresponding reflection coefficient (R) for an air-filled or water-
filled void would exceed + 0.4 as shown in Figure 2.
6
0.3
V = c/sqrt(ε)
0.25
0.2
Velocity, m/ns
0.15
0.1
0.05
0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
Dielectric Constant
Signal Polarity
Reflection polarity can also provide valuable information regarding subsurface
conditions beneath the concrete unit. Reflection polarity is also a function of the
dielectric constant between two media. If the reflection coefficient, R, is a positive
value, a positive amplitude precedes a negative amplitude on the reflection signal.
The signature of a reversed polarity is just the opposite - negative amplitude
followed by a positive amplitude. Reversed polarity due to phase inversion occurs
when the dielectric constant of layer 1 is greater than the dielectric constant of layer
2, which results in a negative reflection coefficient. Figure 2 also indicates the
predicted polarity of the received signal based on dielectric variations of layer 2
with respect to layer 1 (concrete). A reversed polarity will occur within the blue
shaded region and is typical for an air-filled void beneath a concrete slab unit. The
other side of the dielectric spectrum is water (ε = 81) where a positive reflection
proceeds the negative reflection. The red region in Figure 2 graphically represents
this type of condition.
7
a. b.
Figure 4 – Oscilloscope Return Signal for (a) air-filled void beneath concrete slab
and (b) water-filled void beneath concrete slab.
Figure 4 provides radar signal data performed underneath the structurally suspended
foundation slab. As shown in Figure 4b, areas underneath the foundation slab with
water-filled void space resulted in a positive amplitude at the concrete slab and void
interface. A phase inversion occurred at the concrete and air void interface as
indicated by a negative amplitude preceding a positive amplitude. This principle in
determining air- or water- filled void space can also be useful for content detection
within buried PVC piping. An air-filled PVC pipe will have opposed polarity with
respect to a water-filled PVC pipe.
8
over a blue color (negative reflection). If this tubing was air-filled, opposite
polarity would have been recorded – blue color (negative reflection) over a red
color (positive reflection). The plastic tubing was part of a floor heating system that
piped warm water underneath the concrete slab.
Two-way travel time is also important in the conversion of time domain radargram
models into distance domain radargram models. Two-way travel time through a
given medium is typically collected at a known depth location (usually by means of
coring). The propagation velocity (V) can then be calculated based on the known
travel times (tt) and medium depth (d) at particular location based on the simple
formula:
2× d
(3) V =
tt
Equations 2 and 3 can then be used to approximate the relative dielectric constant, ε,
for a given medium. This velocity analysis provides the most accurate means to
convert radargram from time domain to distance domain. Other methods include
the assignment of relative dielectric constants from documented resources such as
the table provided in Figure 3, geometric scaling utilizing a data migration
technique and common depth point, which is uncommon in concrete evaluation
studies.
Hyperbolic Reflection
When the transmitting antenna radiates energy into the subsurface, the radiating
beam is conical in nature. The cone angle may range between 60 to 90 degrees with
the apex of the cone in the center of the antenna. Due to this broad energy
transmission pattern, hyperbolic shapes from reflections occurred when the antenna
crosses a linear target (steel reinforcement, pipes) situated perpendicular to the
antenna path. The hyperbolic shapes develop because of antenna beam has a broad
transmission pattern; therefore, the radar antenna will detect the target not only
when it’s directly above it, but also before and after the target. As the antenna
approaches the target, the left leg of the hyperbola is formed. The apex of the
9
hyperbola represents the top of the target. As the antenna retreats from the target,
the right leg of the hyperbola is formed. The hyperbolic shapes of several targets
(rebar) are shown in the time domain radargram section in Figure 5.
The shape of the hyperbola is a function of scan spacing, which a controlled setting
within the radar system, and dielectric medium that embeds the target. The higher
the relative dielectric constant value, the lower the propagation velocity and more
focused (less broad) the conical energy transmission into the ground (Conyers et al.
1997). Therefore, a target embedded within a medium having higher relative
dielectric constant will produce thinner hyperbolas and vice versa. Hence, since the
shape of the hyperbola is a function of the dielectric medium of which the target is
embedded within, propagation velocity, V, can be estimated based on geometric
scaling techniques. Geometric scaling involves the migration of GPR data from a
time domain radargram image to a “real world” distance domain radargram image
of the subsurface.
10
dielectric parameters, the distance domain radargram was generated. Note how the
hyperbolic shapes represent rebar, and water-filled tubing targets condense into
points.
CASE HISTORIES
However, as shown in Figure 6, rebar was not continuously present throughout the
concrete pavement sections as evident by the lack of hyperbolic reflections.
Observed concrete sections with moderate to high observed distress had no steel
reinforcement.
11
Figure 6 – Time-domain Radargram of a Heavily Loaded Traffic Pavement
Servicing a Manufacturing Facility.
Figure 7 shows a time-domain radargram across portions of the suspended slab with
varying interfaces. The signal polarity, two-way travel time and reflection strength
characteristics of this scan are important in the diagnosis of the concrete interfaces.
The first third of the scan shows a strong negative reflection (blue) followed by a
strong positive (red) reflection, which is indicative of an air-filled void beneath the
concrete slab. The middle third of the scans recorded an opposite polarity (strong
positive followed by strong negative) indicative of a water-filled void space. Soil
contact with the foundation slab was encountered at the latter third. It was
hypothesized (and confirmed) that the void space at this location collapsed due to
heaving soils; and not during construction. If it had occurred during construction,
the two-way travel time of the concrete section would have been significantly
greater due to a thicker concrete section. The reflection strength at the concrete/soil
interface is weaker with respect to the other two interfaces due to a lower dielectric
12
contrast between the two media. Based on Figure 7, the placement of reinforcement
and depth of concrete were within project specifications.
A three-dimensional (3D) GPR survey was also performed across an interior grade
beam, which had experienced upward movement and subsequent nearby
superstructure distress at this location. Three-dimensional GPR survey lines are
typically one to two feet on center. The model itself is compiled in highly robust
visualization software capable of integrating large volumes of GPR data. Figure 8
plots the GPR data in a 3D format with respect to the foundation floor slab, interior
grade beam and nearby column. The vertical scale is in inches and has been
exaggerated by a factor of five for visualization clarity. Recent software advances
has made three-dimensional model of GPR possible. However, additional
development is much needed to further facilitate a user-friendly platform and
expedite post-processing analysis. As indicated in Figure 8, the foundation slab
thickness was on the order of 7 inches, which is near project specification. An air-
filled void was present on both sides of the interior grade beam, as evident by a
strong negative reflection (blue color) preceding a strong positive reflection (red
color). However, the GPR data indicates that the interior grade beam width is
approximately 26 to 30 inches throughout model as compared to a specified design
width of 14 inches. This extended width may be attributed to over-pour at the
interior grade beam and/or collapsed void space on either side of the interior grade
beam. Whichever the case, the structural elements in close proximity to this interior
grade beam were most likely in direct contact with the highly expansive supporting
soils.
13
Figure 8 – 3D GPR Model of Interior Grade Beam
14
60
50
40
Distance, ft
30
20
10
0
0 10 20 30 40
Distance, ft
Figure 9 – Typical Void Detection Map
15
Top of Slab
POST TENSIONED
CABLES
Slab Bottom
VOID SPACE
UNDERNEATH SLAB
CONCLUSIONS
GPR provides an efficient and versatile means for concrete evaluation studies. Ideal
electrical properties of concrete make exploratory studies using GPR extremely
efficacious. Data collection and on-site cursory analysis are increasingly becoming
easier with recent hardware improvements. More importantly, readily available
GPR software has improved significantly, in particular for the concrete evaluation
usage. Significant research and development has recently been applied to the
determination of density and water content of each layer using GPR (Lytton, 1995).
This is an added benefit for concrete evaluation studies. Three-dimensional
modeling of GPR data is relatively new, but recent software advances using 3D
processing and modeling are becoming more feasible and user-friendly. Current
concrete evaluation studies involve the identification, qualification and/or
quantification of reflected GPR signatures. These GPR signatures include, but may
not be limited to, reflection strength, signal polarity, two-way travel time, signal
attenuation and hyperbolic reflection, which is necessary for subsurface feature
identification and/or delineation.
16
REFERENCES
Cardimona, S., Willeford, B., Webb, D., Wenzlick, J., Anderson, N., (2000).
Ground Penetrating Radar Survey of Interstate 70 Across Missouri, Proceedings
from the 2000 SAGEEP Conference.
ASTM Designation D 4748-87 (1995), Standard Test Method for Determining the
Thickness of Bound Pavement Layers Using Short-Pulse Radar.
ASTM Designation D 6432-99, Standard Guide for Using the Surface Ground
Penetrating Radar Method for Subsurface Investigation.
17