Wind Load Calculation for Transmission tower (C2)

wind zone 3
basic wind speed (160 kmph) 44 m/sec LENGTH OF CONDUCTER 34.5 m
refer wind speed 32 m/sec Area of insulator 0.25 m2
Area of conductor(surface 1.73 m2
Reliability level 1
k1 1
Terrain category 1
Terrain roughness 1
Height of structure (above ground) 10 m
wind span of conductor 10 m
Design wind speed 32
Design wind pressure 1750 N/m2

GUST RESPONSE FACTOR


FOR TOWER 1.7
FOR INSULATORS 1.7
FOR (CONDUCTOR/GROUND WIRE) 1.7
DRAG COEFFICIENT
FOR CONDUCTOR 1
FOR GROUND WIRE 1.2
FOR TOWER 1.7
FOR INSULATORS 1.2
WIND LOAD
WIND ON CONDUCTOR 2.975 Kn/m2
WIND ON GROUND WIRE 3.57 Kn/m2
WIND ON INSULATOR 3.57 Kn/m2
WIND ON STRUCTURE 5.0575 Kn/m2
WIND LOAD(IN KN)
WIND LOAD ON CONDUCTOR 5.15 kN
WIND LOAD ON GROUND WIRE 6.18 kN
WIND LOAD ON INSULATOR 6.18 Kn