Fire & Gas – Pre.

Commissioning

Confirm the tag and description in HMI is correct as per field tag
Check the wire ferrule readability, wiring in secondary JB, and associated FGS Smart JB Charms CH, correspond to the
loop wiring.
Check screen wires of IS and NIS IOs are terminated at IS & NIS earth bar respectively
Check the redundancy power by switching ON / OFF its associated MCB in the primary & secondary PDB.

Check the redundancy modules of Smart JB with the support of Emerson system team
Check the status of the Charms module LED is solid Green when the associated IO is loop tested.
Check Zero (calibration) LEL in the FGD transmitter LCD and verify in ICSS HMI the same reading.
Apply 50% LEL Methane Calibration Cylinder model: CAL‐CYL‐METH and check the corresponding reading in ICSS HMI
and transmitter display and verify the alarm with correct zone representation
Confirm that range / set points are as per Alarm and trip set point document/as indicated in the FGS C&E document for
FGS detectors/All fire zones.
Check Zero (calibration) reading of Toxic gas detector' in TX LCD and in HMI .Apply span gas (58L of 25 ppm ,H2s cylinder
model,943‐050000) and verify the PPM reading HMI

Confirm the alarm and Fire Zone representation associated with the Toxic detector in the ICSS HMI

Check Flame detector by pointing the Flame simulators (975 MR Units) from the target distance and verify the alarm and
the associated fire zone in the HMI. Simulate the dirty optics function and check the status in the HMI

Open path gas detector, Carry out transmitter and receiver alignment with the help of telescope.

Open path gas detector Zero Calibration and span calibration with the help of magnet and test slide provided by the
vendor. Check the alarm and associated Fire zone representation
Manual call point, activate the MCP by the test key and verify fire Zone representation and alarm

Verify the EOL and series Resistor values are installed in the MCP device as per Line monitoring CCT.
Check short CCT and open CCT alarm in HMI.
Confirm that maintenance / shutdown override function operate correctly.
Confirm that all items within the loop operate correctly through ICSS / HMI including graphics, alarms and face‐plate.
Enter if any specific check carried out related to the tag in the remarks