A. HT / LT PANELS
The rates for the distribution boards apart from the Breakers and instruments shall also include the following :
2 Cubicle type, 16 gauge CRCA sheet steel enclosed & Type 3b modular construction.
3 Complete with interconnections and distribution bus bars along with connector strip.
5 Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit
diagram.
6 Providing cable clamps / supports within distribution boards cable alley.
8 Distribution panels / bus ducts / rising mains shall be Powder Coated with RAL-7032 shade or as approved.
9 IP 55 Degree of protection for all type of distribution panel enclosure shall be as per IS:13947-1993.
10 Current density of aluminium shall be 1 sq mm for 1.0 Amps for rated current of bus bars.
11 GI earth bus shall be provided through out the length of each board as per schematic diagram.
12 All measuring instruments (Meters) shall be of digital electronic (LED Type) of approved make.
13 All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
14 All panels shall have provision of the Pad locking of MCCB’s handles in “OFF” Position.
15 Additional set of C.T.s, potential free contacts, connectors, contactors with wiring etc are to be provided for BAS
including space required for various transducers in main LT panel sections, etc. Only transducers shall be supplied
by BAS tenderer.
16 All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive
(motor) load shall be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic.
17 All incoming and outgoing air circuit breakers shall be placed on middle portion of the vertical in single tier formation.
18 CT’s shall be properly mounted and clamped. Connection of CT’s for measuring instrument / relays shall be done
through connector / terminals.
19 Model, current capacity location and frame size of switchgear shall be written inside of the panel doors with paint /
permanent marker as approved shop drawings / site requirement.
20 All electronic meters with RS - 485 port and ACB's communication port shall be wired with shielded wire upto
separate marshalling box for termination of all control wires and communication system.
A. HT / LT PANELS
MS sheet enclosed cubicle type panel with main bus rated for 1250 A
and droppers rated for 630 A
630 Amps electrically operated trip free type vacuum circuit breaker
at 50 deg.C ambient.
Breaker control switch.
24 V DC tripping coil.
24 V DC closing coil.
Spring charging motor
Set of ON/OFF/TRIP indicating lamps.
Set of Phase indicating lamps.
Clear lamp for trip circuit health supply.
Load Manager
Digital VAF meter with inbuilt selector switch.
Aux. relays for Anti Pumping & indication.
Trip circuit supervision and lock out relay.
Digital electronic Trivector meter.
2 over current & Earth Fault IDMT relay with instantaneous high set
element range.
3 No. Cast resin CTs of dual ratio 250-500 / 5 Amps CL:1, 5P10, 15
VA.
3 No. Cast resin drawout type PTs 11 kV / √3 / 110 √3, class 1, 100
VA.
Suitable space for termination of 1 No. 11 kV, 3C x 300 sq.mm XLPE
cable as incoming.
MS sheet enclosed cubicle type panel with main bus rated for 1250 A
and droppers rated for 630 A
630 Amps electrically operated trip free type vacuum circuit breaker
at 50 deg.C ambient.
Breaker control switch.
24 V DC tripping coil.
24 V DC closing coil.
Spring charging motor
Set of ON/OFF/TRIP indicating lamps.
Set of Phase indicating lamps.
Clear lamp for trip circuit health supply.
Aux. relays for Anti Pumping & indication.
Trip circuit supervision and lock out relay.
2 over current & Earth Fault IDMT relay with instantaneous high set
element range.
3 No. Cast resin CTs of dual ratio 50-100 / 5 Amps CL:1, 5P10, 15
VA.
3 No. Cast resin drawout type PTs 11 kV / √3 / 110 √3, class 1, 100
VA.
MS sheet enclosed cubicle type panel with main bus rated for 630 A
and droppers rated for 630 A.
630 Amps electrically operated trip free type vacuum circuit breaker
at 50 deg.C ambient.
Breaker control switch.
24 V DC tripping coil.
24 V DC closing coil.
Spring charging motor
Set of ON/OFF/TRIP indicating lamps.
Set of Phase indicating lamps.
Clear lamp for trip circuit health supply.
Digital ammeter with selector switch.
Aux. relays for Anti Pumping & indication.
Trip circuit supervision and lock out relay.
Tripping relay for each type of transformer fault.
Restricted Earth Fault relay with CT's.
Suitable rating Power pack including charger, Batteries etc complete
as required for complete Panel Board
2 over current IDMT relay with instantaneous high set element range.
3 No. Cast resin CTs of dual ratio 75-150 / 5 Amps CL:1, 5P10, 15
VA.
Suitable space for termination of 1 No. 11 kV, 3 C x 185 sq.mm XLPE
cable as outgoing.
a. 3200 amps 4 Pole Electrically operated fully draw out type air circuit
breaker Ics 50 kA with microprocessor release unit. The release shall
have following protection:
• Over current
• Short Circuit (S),
• Ground Fault (G),
• Current Un balance
• Voltage Un Balance
• Under and over Voltage
• Under and over frequency
• Restricted Earth Fault protection with PS class CT’s.
• Trip Circuit supervision
• Phase sequence reversal
• Harmonic Analyser
Maximum demand, Fault History records, Event records facilities,
LED display, % loading with adjustable setting as per specification
- 1 Set
b. Digital VAF meter with 3 No. 3200/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
c. Breaker ON / OFF / TRIP indicating lights with control HRC Fuse - 1
Set
d. 24 V DC Shunt trip coil. - 1 Set
e. Under voltage Relay with timer - 1 Set
f. Over voltage Relay with timer - 1 Set
g. Breaker control switch - 1 Set
h. Digital Load Manager with RS 485 port. -1 Set
i. Phase indicating light protected by 2 amps MCB’s.
j. Class – B surge arrestor (Lines to Neutral) & (Neutral to Earth)
suitable for 3 phases.
Outgoings comprising of
a. 2500 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 6 Set
b 2000 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 4 Set
c 1600 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 1 Set
d 1250 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 3 Set
e 1000 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 2 Set
f 800 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 3 Set
g 630 amps TPN MCCB with over current, short circuit and earth fault
protection - 6 Set
h 400 amps TPN MCCB with over current, short circuit and earth fault
protection - 3 Set
i 250 amps TPN MCCB with over current, short circuit and earth fault
protection - 3 Set
j 200 amps TPN MCCB with over current, short circuit and earth fault
protection - 1 Set
k 160 amps TPN MCCB with over current, short circuit and earth fault
protection - 2 Set
Notes:
a All Outgoing feeders shall be provided with Digital Dual Energy Meter
with RS - 485 port
b All Outgoing feeders shall be provided with Three phase indicating
lamps through 415 / 110 V PT, primary / secondary of PT's shall be
protected by 2 amps SP MCBs.
c All Outgoing feeders shall be provided with ON/OFF/TRIP Indications
and shall be protected by 2 amps SP MCBs.
d All incoming, outgoing and buscoupler breakers shall be electrically/
mechanically interlocked.
e All incoming, outgoing and buscoupler breakers shall be minimum 50
kA rating with Icu = Ics.
f Each section of the panel shall be provided with CFL light & switch,
space heater and thermostat etc.
2.2 MDB - 1
Incomer comprising of :
a. 2000 amps TPN Electrically operated fully draw out type air circuit
breaker Ics 50 kA with microprocessor release unit. The release shall
have following protection:
• Over current
• Short Circuit (S),
• Ground Fault (G),
• Current Un balance
• Voltage Un Balance
• Under and over Voltage
• Under and over frequency
• Restricted Earth Fault protection with PS class CT’s.
• Trip Circuit supervision
• Phase sequence reversal
Maximum demand, Fault History records, Event records facilities,
LED display, % loading with adjustable setting as per specification
- 1 Set
b. Digital VAF meter with 3 No. 2000/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
c. Breaker ON / OFF / TRIP indicating lights with control HRC Fuse - 1
Set
d. Breaker control switch - 1 Set
e. Phase indicating light protected by 2 amps MCB’s.
i 2500 Amps TPN Aluminium Bus Bar with colour coded heat
shrinkable steeve - 1 set
Outgoing comprising of :
i 400 Amps TPN MCCB with Microprocessor based releases for SC,
OL and E/F protections - 3 Set
ii 250 Amps TPN MCCB with Microprocessor based releases for SC,
OL and E/F protections - 4 Set
iii 160 Amps TPN MCCB with thermal magnetic based releases for SC,
OL and E/F protections - 3 Set
Notes:-
2.3 MDB - 2
Incomer comprising of :
a. 2000 amps TPN Electrically operated fully draw out type air circuit
breaker Ics 50 kA with microprocessor release unit. The release shall
have following protection:
• Over current
• Short Circuit (S),
• Ground Fault (G),
• Current Un balance
• Voltage Un Balance
• Under and over Voltage
• Under and over frequency
• Restricted Earth Fault protection with PS class CT’s.
• Trip Circuit supervision
• Phase sequence reversal
Maximum demand, Fault History records, Event records facilities,
LED display, % loading with adjustable setting as per specification
- 1 Set
b. Digital VAF meter with 3 No. 2000/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
c. Breaker ON / OFF / TRIP indicating lights with control HRC Fuse - 1
Set
d. Breaker control switch - 1 Set
e. Phase indicating light protected by 2 amps MCB’s.
i 2500 Amps TPN Aluminium Bus Bar with colour coded heat
shrinkable steeve - 1 set
Outgoing comprising of :
i 1250 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 2 Set
ii 630 Amps TPN MCCB with Microprocessor based releases for SC,
OL and E/F protections - 3 Set
iii 100 Amps TPN MCCB with thermal magnetic based releases for SC,
OL and E/F protections - 1 Set
Notes:-
2.4 MDB - 3
Incomer comprising of :
a. 2000 amps TPN Electrically operated fully draw out type air circuit
breaker Ics 50 kA with microprocessor release unit. The release shall
have following protection:
• Over current
• Short Circuit (S),
• Ground Fault (G),
• Current Un balance
• Voltage Un Balance
• Under and over Voltage
• Under and over frequency
• Restricted Earth Fault protection with PS class CT’s.
• Trip Circuit supervision
• Phase sequence reversal
Maximum demand, Fault History records, Event records facilities,
LED display, % loading with adjustable setting as per specification
- 1 Set
b. Digital VAF meter with 3 No. 2000/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
c. Breaker ON / OFF / TRIP indicating lights with control HRC Fuse - 1
Set
d. Breaker control switch - 1 Set
e. Phase indicating light protected by 2 amps MCB’s.
i 2500 Amps TPN Aluminium Bus Bar with colour coded heat
shrinkable steeve - 1 set
Outgoing comprising of :
i 800 amps TPN Electrically operated fully drawout type air circuit
breaker with over current, short circuit & earth fault protection
releases etc. - 3 Set
ii 630 Amps TPN MCCB with Microprocessor based releases for SC,
OL and E/F protections - 2 Set
iii 250 Amps TPN MCCB with Microprocessor based releases for SC,
OL and E/F protections - 1 Set
Notes:-
2.5 MDB - 4
Incomer comprising of :
i 600 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 250 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 250/5 amps 15 VA CTs with inbuilt selector switch - 1 Set
ii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 9 No.
Notes:-
2.6 MDB - 5
Incomer comprising of :
i 300 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 60/5 amps 15 VA CTs with inbuilt selector switch - 1 Set
ii 32 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 30/5 amps 15 VA CTs with inbuilt selector switch - 2 Set
iii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 3 No.
iv 40 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 4 No.
v 25 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 4 No.
Notes:-
2.7 MDB - 6
Incomer comprising of :
i 800 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 40 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 60/5 amps 15 VA CTs with inbuilt selector switch - 2 Set
ii 32 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 30/5 amps 15 VA CTs with inbuilt selector switch - 4 Set
iii 125 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 7 No.
iv 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 5 No.
v 40 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 2 No.
Notes:-
2.8 MDB - 7
Incomer comprising of :
i 800 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
ii 125 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 14 No.
Notes:-
2.9 MDB - 8
Incomer I comprising of :
i 400 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 125 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 120/5 amps 15 VA CTs with inbuilt selector switch - 1 Set
ii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 60/5 amps 15 VA CTs with inbuilt selector switch - 1 Set
ii 40 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 40/5 amps 15 VA CTs with inbuilt selector switch - 1 Set
ii 125 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 4 No.
iii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 4 No.
iv 25 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 6 No.
Notes:-
a All Outgoing feeders shall be provided with Digital Dual Energy Meter
with RS - 485 port
b All Outgoing feeders shall be provided with ON/OFF/TRIP Indications
and shall be protected by 2 amps SP MCBs.
c All incoming and outgoing breakers shall be electrically/ mechanically
interlocked.
d All breakers shall be minimum 50 kA rating with Icu = Ics.
2.10 MDB - 9
Incomer comprising of :
i 600 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 125 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 120/5 amps 15 VA CTs with inbuilt selector switch - 5 Set
ii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 5 No.
Notes:-
a All Outgoing feeders shall be provided with Digital Dual Energy Meter
with RS - 485 port
b All Outgoing feeders shall be provided with ON/OFF/TRIP Indications
and shall be protected by 2 amps SP MCBs.
c All incoming and outgoing breakers shall be electrically/ mechanically
interlocked.
d All breakers shall be minimum 50 kA rating with Icu = Ics.
2.11 MDB - 10
Incomer comprising of :
i 800 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 400 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 400/5 amps 15 VA CTs with inbuilt selector switch - 2 Set
i 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 60/5 amps 15 VA CTs with inbuilt selector switch - 6 Set
ii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 6 No.
i 100 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 100/5 amps 15 VA CTs with inbuilt selector switch - 3 Set
ii 25 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. along with 1 No. Digital Energy Meter with 3
No. 20/5 amps 15 VA CTs with inbuilt selector switch - 2 Set
Notes:-
a All Outgoing feeders shall be provided with Digital Dual Energy Meter
with RS - 485 port
b All Outgoing feeders shall be provided with ON/OFF/TRIP Indications
and shall be protected by 2 amps SP MCBs.
c All incoming and outgoing breakers shall be electrically/ mechanically
interlocked.
d All breakers shall be minimum 50 kA rating with Icu = Ics.
2.12 MDB - 11
a. 800 amps TPN Electrically operated fully draw out type air circuit
breaker Ics 50 kA with microprocessor release unit. The release shall
have following protection:
• Over current
• Short Circuit (S),
• Ground Fault (G),
• Current Un balance
• Voltage Un Balance
• Under and over Voltage
• Under and over frequency
• Restricted Earth Fault protection with PS class CT’s.
• Trip Circuit supervision
• Phase sequence reversal
Maximum demand, Fault History records, Event records facilities,
LED display, % loading with adjustable setting as per specification
- 1 Set
b. Digital VAF meter with 3 No. 800/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
c. ON / OFF / TRIP indicating lights with control HRC Fuse - 1 Set
d. Breaker ON / OFF / TRIP indicating lights with control HRC Fuse - 1
Set
e. Breaker control switch - 1 Set
f. Phase indicating light protected by 2 amps MCB’s.
i 1000 Amps TPN Aluminium Bus Bar with colour coded heat
shrinkable steeve - 1 set
Outgoing comprising of :
i 630 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 1 Set
ii 100 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 3 No.
iii 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 3 No.
iv 40 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 9 No.
Notes:-
a All Outgoing feeders shall be provided with Digital Dual Energy Meter
with RS - 485 port including CT etc.
b All Outgoing feeders shall be provided with ON/OFF/TRIP Indications
and shall be protected by 2 amps SP MCBs.
c All incoming and outgoing breakers shall be electrically/ mechanically
interlocked.
d All breakers shall be minimum 50 kA rating with Icu = Ics.
Incomer comprising of :
a. 100 amps TPN MCCB with thermal magnetic release unit - 1 Set
b. Digital VAF meter with 3 No. 100/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
c. ON / OFF / TRIP indicating lights with control HRC Fuse - 1 Set
d. Phase indicating light protected by 2 amps MCB’s.
i 200 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
i 63 amps TPN MCCB with over current, short circuit & earth fault
protection releases etc. - 10 No.
Notes:-
a All Incoming and Outgoing feeders shall be provided with Digital Dual
Energy Meter with RS - 485 port
b All Outgoing feeders shall be provided with ON/OFF/TRIP Indications
and shall be protected by 2 amps SP MCBs.
c All incoming and outgoing breakers shall be electrically/ mechanically
interlocked.
d All breakers shall be minimum 50 kA rating with Icu = Ics.
Incomer comprising of :
i 100 Amps TPN Aluminium Bus Bar with colour coded heat shrinkable
steeve - 1 set
Outgoing comprising of :
Notes:-
Incomer comprising of :
a. 1250 amps TPN Electrically operated fully draw out type air circuit
breaker Ics 50 kA with microprocessor release unit. The release shall
have following protection:
• Over current
• Short Circuit (S),
• Ground Fault (G),
• Current Un balance
• Voltage Un Balance
- 1 Set
c. Digital VAF meter with 3 No. 1200/5 amps 15VA CTs with inbuilt
selector switch - 1 Set
d. Breaker ON / OFF / TRIP indicating lights with control HRC Fuse - 1
Set
e. Phase indicating light through 415 /110 V PT, Primary / Secondary of
PT's shall be protected by 2 amps MCB’s. - 1 Set
1500 Amps TPN Aluminium Bus Bar . with colour coded heat
shrinkable steeve - 1 set
Outgoing comprising of :
Notes:
3.1 3200 amps TPN bus ducts from Transformer to DRUPS including 90
deg bends. RM 400 30000 12000000
3.2 3200 Amps Flexible end connection on Transformer No. 4 50000 200000
3.3 3200 Amps Flexible end connection on Rotary UPS No. 6 50000 300000
3.4 3200 Amps Flexible end connection on Rotary UPS POP No. 6 50000 300000
3.5 3200 Amps Flexible end connection on LT Panel No. 4 50000 200000
B. 11/0.415 KV TRANSFORMERS
2 All fixing accessories such as foundation bolts, nuts and bolts etc as required.
4 Interlocking shall be provided between transformer and VCB HT breaker panel. When transformer open respective
HT breaker shall be tripped.
B. 11/0.415 KV TRANSFORMERS
2 Providing all fixing accessories such as clamping devices nuts, bolts and screws.
3 Excavation laying of cable filling of sand, brick protection, back filling of earth, watering, ramming and making good.
4 Wherever the cables are of aluminium and bus bars of copper bimetallic lugs shall be used.
7 Fire retardent paint one meter on both side of wall penetration and at termination as per specifications.
9 All cutouts / Sleeves shall be sealed with fire redardant sealent as per specification.
10 All cuts/perforations/folded sections where contact with wires/cables is expected shall be burr free.
11 Zinc coating shall be 120 gm / square meter or more. The materials shall conform to relevant IS / BS standards for
the category / application specified.
12 The cable tray / ducts / trunking shall be factory built. Only cutting to achieve assembly system length shall be
permitted at site.
13 Accurate fabrication formed section with tolerances of + 2 mm on width and + 5 mm on length expected.
14 Dimensional and general arrangement drawing of the system are expected to be provided by tenderer / cable tray /
duct supplier.
15 The system shall be designed for installation with a temperature classification of + 60 deg.C.
4.1 3.5 core 400 sq. mm Al arm. No. 270 2000 540000
4.2 3.5 core 300 sq. mm Al arm. No. 100 1800 180000
5 Supply and installation of following RCC (NP-2 class) Hume pipe for
underground laying of cables under paved/soil/rock areas with all
necessary material and at required depth upto 1 mtr including
excavation, back filling with excavated material, providing pipe
protection layer all around pipe (75 mm thick cement concrete all
around pipe 1:3:6 (1 cement, 3 coarse sand and 6 crushed stone
aggregate), cable route marker, brick etc, ramming and making the
surface finish good in all respect as required.
a. 300 mm ID RM RO 800
b. 150 mm ID RM RO 500
6 Supply and fixing of factory fabricated GI ladder type cable trays, with
radial bends, suspenders and supports as per specification and of
the following sizes.
1 All fixing accessories such as brass saddles, brass screws rawl plugs etc.
2 Jointing by rivetting and brazing after rivetting in case of copper and welding / bolting in case of GI earthing.
3 Cutting chases holes and making good the same wherever required.
8 All equipment motors, DB’s, panels to be connected on either ends (double earthing) with suitable strip / wires.
9 Copper earthing shall be provided for UPS & equipment / LV system only.
1.1 50 x 6 mm thick Copper tape with heat shrinkable sleeves RM 500 900 450000
2 Supply, installation & testing of earthing station with 600 X 600X 3.15
mm thick Cu plate electrode. 2 Nos.50 X 6 mm Cu strip connecting
the inspection chamber to Cu., plate electrode, 50 mm. dia `B' class
GI pipe. G.I. funnel with GI wire mesh,cement concrete chamber with
concrete base CI. manhole cover dia 560 mm heavy duty with frame
and packing of a mixture of charcoal and salt around plate electrode
and excavation and backfilling of all kinds of earth, masonary work,
connecting the earth pit with earthing grid with bitumin covering of No. 20 25000 500000
joints, all work as per IS:3043,
3 Supply, installation & testing of earthing station with 600 X 600X 6
mm thick GI plate electrode. 2 Nos.50 X 6mm GI strip connecting the
inspection chamber to GI., plate electrode, 50 mm. dia `B' class GI
pipe. G.I. funnel with GI wire mesh,cement concrete chamber with
concrete base CI. manhole cover dia 560 mm heavy duty with frame
and packing of a mixture of charcoal and salt around plate electrode
and excavation and backfilling of all kinds of earth, masonary work,
connecting the earth pit with earthing grid with bitumin covering of No. 125 15000 1875000
joints, all work as per IS:3043,
4 Supply, installation, testing and commissioning of lockable earth
terminal box fabricated out of 14/ 16 gauge CRCA sheet steel in
cubical formation, dust and vermin proofin with transparent cover with
2 No. 50 x 6 mm copper strip with 30 No. 8mm dia holes with 8mm x
25mm dia brass nut bolt with double washer. No. 20 2000 40000