Calculate Size of Diesel Generator jiguparmar@yahoo.com
System Voltage ( P-P ) 415 Volt Linear Load: General Equipments, Heater www.electricalnotes.wordpress.com
Non-Linear
System Voltage ( P-N ) 230 Volt UPS,Invertor,Ballast,VFD
Load:
Future Load Expansion 10% % 1.1
Average Use of Equipment 0.8 (0.7 To 1.0) 0.8
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load
Sr.N Running Diversity Starting Full Load Full Load Full Load
Equipment Load Type Supply Qty Starting P.F Motor Starter Starting Kva Starting Kw
o Load Kw/Hp P.F Factor Amp Kva Kw Amp :Calculation:
motor Motor 1Ph 1 10 Kw 0.7 0.8 0.8 Freq.Conv 52.2 13.7 9.6 10.0 8.0 43 Starting Kva 437 Kva
Motor 3Ph 1 120 Kw 0.7 0.8 0.8 Auto.Tra. 500.8 411.4 288.0 120.0 96.0 167 Starting Kw 307 Kw
Linear 1Ph 4 0.08 Kw 0.8 0.8 1 1.7 0.4 0.3 0.4 0.3 2 Starting Amp 603 Amp
Non-Linear 1Ph 2 3 Kw 0.8 0.8 0.8 41.7 9.6 7.7 6.0 4.8 26 Running Kva 137 Kva
Non-Linear 1Ph 2 0.5 Kw 0.8 0.8 0.8 7.0 1.6 1.3 1.0 0.8 4 Running Kw 110 Kw
0.0 0.0 0.0 0.0 0.0 0 Running Amp 243 Amp
0.0 0.0 0.0 0.0 0.0 0 Alternator Details
0.0 0.0 0.0 0.0 0.0 0 Voltage (P-N) 230 Volt
0.0 0.0 0.0 0.0 0.0 0 Efficiency 80%
0.0 0.0 0.0 0.0 0.0 0 Engine Overload Capacity 130% (Appro 130% To 150%)
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0 :Required Size of Diesel Generator:
0.0 0.0 0.0 0.0 0.0 0 Diesel Generator Size 384 KVA (Select D.G near This Value)
0.0 0.0 0.0 0.0 0.0 0 Engine of Generator 114 KW
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0 Calculate Efficiency & Unit Rate of Power of Calculate Approximate Fuel
0.0 0.0 0.0 0.0 0.0 0 D.G set Consumption
0.0 0.0 0.0 0.0 0.0 0 D.G Size ( Kva ) 412
0.0 0.0 0.0 0.0 0.0 0 D.G P.F 0.9 D.G Size (Kva) 412
0.0 0.0 0.0 0.0 0.0 0 D.G Running Hours 5 D.G P.F 0.9
0.0 0.0 0.0 0.0 0.0 0 Diesel Consumption (Liter) 1000 D.G Operation Full Load
0.0 0.0 0.0 0.0 0.0 0 KWH Reading of Meter 400
0.0 0.0 0.0 0.0 0.0 0 M.F of KWH Meter 1 Required Diesel
0.0 0.0 0.0 0.0 0.0 0 Diesel Rate /Liter (Rs) 54 Liter/Hour 95.1
0.0 0.0 0.0 0.0 0.0 0 Efficiency of D.G 22%
0.0 0.0 0.0 0.0 0.0 0 KWH/Liter (Unit Per Liter) 0.40
0.0 0.0 0.0 0.0 0.0 0 Unit Rate of Power (Rs) 135.0
0.0 0.0 0.0 0.0 0.0 0
CalculateCalculate
SizeSize ofofDiesel Gener
Diesel Generator
System Voltage ( P-P ) 400 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear UPS,Invertor,Ballast,VFD
Load:
Future Load Expansion 10% % 1.1
Average Use of Equipment 0.8 (0.7 To 1.0) 0.8
Total Connected Load on Diesel Generator Set
Load
Sr.N Equipment Load Type Supply Qty Starting Running Diversity
o Load Kw/Hp P.F P.F Factor

1
2
3
4
5

englogs.com
future
esel Generator
el Generator

Starting Condition Running Condition


Full Full
Motor Starting Starting Starting Full Load
Starter Amp Kva Kw
Load Load
Amp Calculation
Kva Kw
0.0 0.0 0.0 0.0 0.0 0 Starting Kva
0.0 0.0 0.0 0.0 0.0 0 Starting Kw
0.0 0.0 0.0 0.0 0.0 0 Starting Amp
0.0 0.0 0.0 0.0 0.0 0 Running Kva
0.0 0.0 0.0 0.0 0.0 0 Running Kw
0.0 0.0 0.0 0.0 0.0 0 Running Amp
0.0 0.0 0.0 0.0 0.0 0 Alternator Details
0.0 0.0 0.0 0.0 0.0 0 Voltage (P-N)
0.0 0.0 0.0 0.0 0.0 0 Efficiency
0.0 0.0 0.0 0.0 0.0 0 Engine Overload Capacity
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0 Required Size of Diesel Gene
0.0 0.0 0.0 0.0 0.0 0 Diesel Generator Size
0.0 0.0 0.0 0.0 0.0 0 Engine of Generator
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0
0.0 0.0 0.0 0.0 0.0 0 Calculate Efficiency & Unit Rate of Power of D.G
0.0 0.0 0.0 0.0 0.0 0 set
0.0 0.0 0.0 0.0 0.0 0 D.G Size ( Kva )
0.0 0.0 0.0 0.0 0.0 0 D.G P.F
0.0 0.0 0.0 0.0 0.0 0 D.G Running Hours
0.0 0.0 0.0 0.0 0.0 0 Diesel Consumption (Liter)
0.0 0.0 0.0 0.0 0.0 0 KWH Reading of Meter
0.0 0.0 0.0 0.0 0.0 0 M.F of KWH Meter
0.0 0.0 0.0 0.0 0.0 0 Diesel Rate /Liter (Rs)
0.0 0.0 0.0 0.0 0.0 0 Efficiency of D.G
0.0 0.0 0.0 0.0 0.0 0 KWH/Liter (Unit Per Liter)
0.0 0.0 0.0 0.0 0.0 0 Unit Rate of Power (Rs)
0.0 0.0 0.0 0.0 0.0 0
0 0 0 0 0 0
Calculation
0 Kva

englogs.
0 Kw
0 Amp
0 Kva
0 Kw
0 Amp
or Details
230 Volt
80%
130% (Appro 130% To 150%)

ed Size of Diesel Generator


0 KVA (Select D.G near This Value)
0 KW

Unit Rate of Power of D.G Calculate Approximate Fuel


set Consumption
412
0.9 D.G Size (Kva) 412
5 D.G P.F 0.9
1000 D.G Operation Full Load
400
1 Required Diesel
54 Liter/Hour 95.1
22%
0.40
135.0
nglogs.com