SAUDI ARAMCO TEST REPORT
Emergency Eyewash/Shower Functional Test Report SATR-B-4001 29-Aug-19 PLUMB
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
C. TEST RESULTS
D. CONCLUSIONS
ITEM
TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-TEST DATE
No.
The face of the shower head from the surface on which the user stands is
between 208.3 cm (82 inches) and 243.8 cm (96 inches)
SAES-B-069
D1 (ANSI 4.6.5.3)
Section 7
Note: Applicable to Emergency showers only
With the valve in the " full on" position, measured diameter of the
sprays pattern is a minimum of 50.8 cm (20 inch) at 152.4 cm
SAES-B-069
D2 (60 inch) above the standing surface. The center of the spray shall be at
Section 7
least 40.6 cm (16 inches) from any obstruction. (ANSI 4.6.5.4)
(Applicable to emergency showers only)
SAES-B-069
D3 Measured water temperature shall not exceed 38°C (100°F) at any time.
Para 5.3.1
REMARKS:
REFERENCE DOCUMENTS:
1-SAES-B-069 -- Emergency Eyewash and Showers, 26 Dec 2018
2-ANSI Z358.1 -- American National Standard for Emergency and Shower Equipment, 2004
*Person Responsible for Implementation of Test and Analysis of Results Y = YES N = NO F = FAILED