Professional Documents
Culture Documents
Enyecontrols System Info Updated
Enyecontrols System Info Updated
Enyecontrols System Info Updated
Systems Info
Introduction
Controls can be devices used to monitor the inputs and regulate
the output of systems and equipment.
Introduction
Major reason and objective of automatic controls
The ultimate aim of every HVAC system and its controls is to provide a
comfortable environment suitable for the process that is occurring in the facility.
Introduction
Basic Parameters of Controls
• Input - is something (such as power or energy) that is put into a machine or system. In
HVAC system, input is DC voltage (0-10VDC), current (4-20mA), thermistor, lux sensor or
contact that goes into the controller. There are three (3) types of inputs. The analog
input, digital input and universal input.
• Output - is defined as the act of producing something, the amount of something that is
produced or the process in which something is delivered. It is the outcome of the
controller. There are two types of output, the analog output and digital output.
• Control loop – are the collection of sensor, controlled device, process plant, and
controller.
• Control modes – the type of action that the controller takes place.
Introduction
Type of Current
Alternating current – is a state of an electric current which is the charge carried
by the conductor are vary periodically reverse its direction of movement.
Type of wires
TF Wire – it is also known as Teflon wire. It is a type of
wire that covered with thermos plastic materials. It
was also used on various electrical equipment and
devices. The typical wire gauge used on
instrumentation is AWG #18.
Ball Valve
The ball valve basically a bored ball which
rotates in the valve body. Ball valve without
characteristic disc can be used for small pipes
in FCU application. Ball valve with characteristic
disk may used in AHU application because of
equal flow percentage output.
Introduction
Control Valves and Dampers
Three-way control valves
Three-way valve provide for variable flow through the coil while maintaining
somewhat constant flow in the system.
Introduction
Selecting and sizing valves
Control valve selection will depend on the following considerations:
where:
Kvs = the amount of water from 5° to 30°C which flows through the valve
at a pressure loss of 1 bar.
V = nominal flow in cmh (cubic meter per hour)
ΔP = differential pressure across the valve (kPa)
Note:
One size lower is not applicable on the ball valves (manual) and butterfly valves
Introduction
Control Damper
Dampers are used to direct or modulate the air flow. It may be round, rectangular or oval.
Circular or round as well as oval is a single blade with a central angle. Dampers for HVAC
are commonly made up of galvanized steel or extruded aluminum. Aluminum dampers are
usually preferred for outdoor type application due to its resistance on oxidation. Other
materials are available such as stainless steel for use in corrosive atmosphere such as
industrial facilities.
Kinds of blade:
•Parallel Blade
•Opposed Blade
Introduction
Sensors and auxiliary devices
• Temperature Sensors
• Humidity
• Moisture Sensors
• Pressure Sensors
• Flow Sensors and Meters
ASHRAE Terminology of Heating, Ventilating, Air Conditioning and Refrigeration
(1991)
Accuracy - Ability of an instrument to indicate the true value of a measured physical quantity.
Range - Region between limits within which a quantity is measured, transmitted, or received,
expressed by stating the lower and upper range values.
Reliability - Probability that a device will function without failure over a specified time period or
amount of usage.
Repeatability, precision - Closeness of agreement among repeated measurements of the same
variable under the same conditions.
Transmitter - A device that accepts a signal and transmits the information in the signal in a
different form to another device.
Introduction
Temperature Sensors
Temperature sensor is used as the surrogate for human comfort.
This would allow integration of the different systems to have them work efficiently as a
fully integrated system, such systems shall include:
The system is designed to save energy by optimizing the efficiency of all equipment
/systems, minimizing unnecessary energy usage and improve operation and
maintenance. Data required for effective monitoring, maintenance and cost-effective
measures shall be available and save on the data base.
C. Facilities Management
Scope of Work
• Optimization
1. Chilled water pumps shall be paired with a specific chiller, its operation shall be dependent on the
energization/de-energization of the chiller.
2. Pressure drops between the main CHWS and CHWR headers shall be monitored. The rise and fall
of the system pressure shall be an indication of the demand for additional cooling.
1. Cooling towers shall be paired with a specific chiller its operation shall be dependent on the
energization/de-energization of the chiller.
2. However, if required, the lag cooling tower shall be used if needed to maintain the cows of 85°F.
3. The COWR temperature shall be monitored and if the temperature goes lower than the setpoint
(normally 95°F), the cooling tower fan shall reduce its speed or additional fans will be turned on if
multistage reverse action shall be done if the temperature goes higher.
1. All monitored points shall be recorded and stored for presentation and analysis in the EC-CPMS
plant manager. Data such as daily, weekly, monthly, or yearly records & comparisons of:
• Chiller, CTs, COWPs, CHWPs lead /lag, start/stop
• CHWS & CHWR temperature, COWS & COWR temperatures, differential pressures,
flowrates, KW/BTUH assumptions, KHWR readings, etc. All can be presented in figures,
graphs, or charts for comparative analysis.
2. Daily, weekly, monthly & yearly system efficiency in KW/TON or Coefficient of Performance (COP)
can be recorded & presented in figures, graphs or charts
Chiller Plant Management
System (EC-CPMS)
System Components
1. Workstation / Plant Manager
3.2. Actuator
Chiller Plant Management
System (EC-CPMS)
System Components
4. Temperature Sensors 6. Differential Pressure Transmitter
5. Flow Switch
Is a systematic approach to the existing system that will enhance functionality and
efficiency. The intention is to synchronize the mechanical portion (AHU, VAV, etc...) and
the controls portion (temperature, pressure, airflow, etc...) to produce one stand-alone
system that is BMS ready and deliver (a) comfort (b) efficiency (c) savings.
Pressure-independent
controller & damper
actuator VAV thermostat
NSVA Seres
ECVA Series ECVD Series
Intelligent VAV System
There are two distinct advantages that the system offers (a) flexibility, (b) adaptability.
a.) Flexibility – with the use of multifunction technology the system can be flexible enough to suit the
expectations of the users such as changes in design during and after project implementation. On
extreme cases, it may not be able to provide a 100% solution but it can ensure the best solution given
that situation charges such as (a) design (mechanical/architectural); (b) tenant’s requirements (set
points, time schedule, etc.); (c) future expansion
b.) Adaptability - the common problem during project implementation is the unforeseen site
condition. For example, proper distance of VAV box from obstructions, locations of room controllers,
location of duct static pressure transmitters, etc.; the efficiency of the system is highly affected thus
resulting to lesser savings and tenants comfort.
Intelligent VAV System
2. Initially all the VAV boxes shall open at 100% capacity (designed max airflow) then after 5 minutes the Air Handling Units shall be
energized.
3. The central controller shall check for alarms and error and shall automatically notify/send an alarm signal thru the LED on the panel and
to the BMS or any connected remote device to the system.
4. After the energization of the AHU’s , the VAV’s shall modulate based on the temperature setpoint and the VFD based on the static
pressure setpoint.
5. In case of supply duct high pressure alarm, the AHU shall automatically de-energized and alarm signals shall be seen to the central panel
and sent to the BMS or any connected remote devices.
6. The supply air temperature shall be monitored and maintained at 13-16°C or at a specified setpoint by modulating the motorized valve.
7. All the VAV boxes shall be connected to the central control panel thru BACnet for monitoring, alarm and override control.
8. The VAV boxes shall modulate to satisfy the room temperature setpoint as specified by the tenant. Room temperature can be set thru
room controller. Last setpoints shall be saved on the room controller in case of power failure or de-energization.
9. During fire mode, the system shall automatically shut down the AHU’s and fully close all VAV boxes
10. The following points also be monitored and log by the system; VFD S/S, trip, status, supply air velocity, differential pressure, supply air
temperature, alarms and other necessary data as specified.
AHU Control & Monitoring
System
- It is a system designed to control & monitor Air Handling Units to deliver the intended design
and required parameters.
- EC-AHUCS maintains the temperature setpoint by calculating the output position based on the
proven Pl algorithms. For monitoring purposes, a display for the actual temperature and
setpoint is provided.
Features:
• Verification of flow and minimum differential pressure due to unique P/T plug design
• The presetting function has no impact on the stroke; Full stroke modulation at all times,
regardless the preset flow
• The constant differential pressure across the modulating control component guarantees
100% authority
• Atuomatic balancing eliminates overflows regardless of fluctuating pressure conditions in
the system
• Compatible with thermic actuators On/Off or 0-10V, normally closed. Also compatible
with motoric actuators 0-10V, linear or Logarithmic or 3 point control
• Differential pressure operating range up to 800kPa
• High flows with minimal required differential pressure due to advanced design of the valve
• Small dimensions due to compact housing
• Higher presetting precision due to stepless analogue scale
• Rangeability > 100:1
AHU Control & Monitoring
System
System Components
II. Pressure Independent Balancing and Control Valve (PIBCV)
II.II. Logica Actuator
Features:
• BACnet MS/TP & Modbus RTU support
• Simple addressing via dip switches
• 1 binary or analog input supporting binary input
• 0-10V or Pt1000
• 1 universal input/output supporting binary, 0-10V in,
Pt1000, 0-10V out or 0-10V position feedback
• Complete built-in library of OPTIMA compact valves
• Selectable Linear or EQ% characteristic
• Flow indication
• Thermal Power indication (when combined with 2
temperature sensors)
• Thermal Energy Consumption indication
Selectable control methods in BMS:
- External BMS setpoint
- Control of minimum delta-T
- Securing design return remperature
- Control by thermal power
- Limitation of terminal unit energy output
AHU Control & Monitoring
System
System Components
III. Enyecontrols Damper Actuator
• Specifically designed to prevent fire and smoke from passing thru the building’s air duct which
will endanger lives and properties as well.
• During fire mode, the system moves the fire & smoke dampers to a safety position as per
designed – either close or open position
Life & Property Safety System
1. Enyecontrols damper actuator is closed and the smoke detector is not trigger in
normal operation
3. If smoke detects in the area the FDAS will command to fully open the damper actuator
4. Air diffuser will be opened to extract the smoke from the room
5. Once the smoke is extracted the devices are back to normal operation
Life & Property Safety System
• Specifically designed to control and monitor differential pressure between the stairway and
inside of the building.
• This is to ensure positive pressure in the stairway thus assuring safe passage of the building
tenants during a fire emergency.
• The intelligent stand-alone controller measures the differential pressure and then controls
(on/off or via VFD interface) the stairwell pressurization fan in order to meet the required set
point.
Life & Property Safety System
1. The DDC Control Panel consists of Controller which has the capability to control and monitor all
the field devices interlocked. Maintains desired set points (Pascal reading at staircase), monitor
the run status, fault status, FDAS status and override main equipment
2. Variable Frequency Drive modulates the frequency running of the fan depending on the pressure
required
3. If a fire broke out, the Fire Detection Alarm System (FDAS) will send a signal to activate the
pressurization fan
4. The system controller shall maintain the differential static pressure by modulating the VFD
stairwell pressurization fan to make the exit point accessible while preventing the smoke to enter
at the same time
5. The system shall be flexible to accommodate changes in the actual operation such as Schedule of
Operation, Override On/Off and Setpoint
Life & Property Safety System
• Specifically designed to extract large quantities of smoke and poisonous fumes for building
tenants and fire rescuers to have clear access thru the escape routes.
• During fire mode, the system moves the smoke extraction dampers to a safety position as per
designed – either close or open position and simultaneously turns on the smoke extraction
fans.
Life & Property Safety System
1. The Direct Digital Controller has the capability to control and monitor all the field devices
interlocked. Monitor the run status, fault status, smoke detector, FDAS status and override the main
equipment
2. Smoke Detector detects smoke fumes at ducting. This would protect the equipment and keep smoke
from being disturbed to the staircase
3. Once FDAS is activated, the damper actuator will be fully open and after a few seconds the exhaust
fan will open to extract the smoke in the area
4. Once the smoke is extracted the devices are back to normal operation
Carbon Monoxide and Temperature
Control & Monitoring System
- Designed to protect the building tenants / public from being expose to CO; since
Carbon Monoxide is colorless, odorless gas it cannot be easily detected.
- It also monitors Temperature on each zone to minimize high temperature reading for
comfort.
The system shall automatically operate the transfer jet fans, exhaust and supply fans to satisfy the set
points (32-50 ppm for carbon monoxide and 32°C for temperature)
For efficiency and energy saving, the basement shall be divided into zones and only the specific zones
with high concentration of carbon monoxide or high temperature shall be activated.
Advance features which are also available in the system are as follows:
1. Native BACnet for future BMS connection
2. LCD display and control functions at the central panel per floor
3. TCP/IP connection for laptop
4. USB connections to export / save data stored in the controller
5. Also based on the carbon monoxide and temperature set points and upon sensing that transfer
fans are activated, the exhaust and supply fans shall also be activated.
6. Tolerance, set points can be changed and reprogrammed at site if a better sequence, energy saving
and operation protocol shall be decided based on actual operation as per instruction and approval
of the owner / consultants.
Carbon Monoxide and Temperature
Control & Monitoring System
BMS Ready Stand-Alone
Carbon Monoxide and Temperature
Control & Monitoring System
BMS Ready Stand-Alone (Components)
Carbon Monoxide and Temperature
Control & Monitoring System
BMS Ready Centralized
Carbon Monoxide and Temperature
Control & Monitoring System
BMS Ready Centralized (Components)
Carbon Monoxide and Temperature
Control & Monitoring System
BMS Ready Centralized (Components)
Carbon Monoxide and Temperature
Control & Monitoring System
BMS Ready Centralized (Components)
Carbon Monoxide and Temperature
Control & Monitoring System
Sequence of Operation
1. The area is divided into zones, which have one carbon monoxide (CO) and temperature sensor each and transfer
fan/s. Exhaust and supply fan are installed to maintain proper ventilation and to displace CO concentration and
the hot temperature.
2. The system shall monitor the presence of carbon monoxide (CO) concentration in PPM (parts per million) and
temperature (°C) for each zone coverage.
3. Initially the system shall have a CO set point ranging to 35ppm and 30°C for temperature (can be overridden /
adjusted through the DDC controller).
4. Once the set points are reached by the carbon monoxide sensors and temperature sensor, the DDC shall run the
transfer fan/s that is in the coverage of the carbon monoxide and temperature sensor/s that worked.
5. Upon detection and the operation of transfer fan/s, the DDC shall energize the supply fan after 15 seconds of the
operation of the transfer fan/s.
6. Upon the operation of supply fan, the DDC shall energize the exhaust fan after 15 seconds thus making a
complete loop of ventilation and avoidance of peak power amplitude.
7. After reaching the cut-off level of carbon monoxide sensor 35ppm (can be adjusted through the DDC) the DDC
shall de-energize the interlocking fans such as the transfer fan, supply fan, exhaust fan.
8. The DDC will monitor, and display all received data and processes it to necessary actions.
Carbon Monoxide and Temperature
Control & Monitoring System
Sequence of Operation
9. In the event that CO sensor detects concentration of CO gas within the area of coverage, or the temperature set
points are reached, it will transmit a signal to the controller. The controller now decides whenever to turn-on or
turn-off the controlled fans and it also depends on what the set point is.
10. If the signal received by the DDC from the CO and temperature sensor is much higher than the declared set
point, then DDC will activate the Jet Fan, Exhaust Fans, Supply fan which is nearer to the activated CO and
temperature sensor.
11. FDAS general fire alarm connection that automatically turn off the supply fan and turn on all exhaust fans and jet
fans (note: this can be changed as per consultants / owners' instructions during fire mode)
Water Leak Detection & Alarm
System
Application
The installation of water leak detection systems is installed more commonplace in most
new commercial office construction schemes along with the more obvious targets of
Mainframes, Servers, Control Rooms, Data Centers and Computer Rooms.
Water Leak Detection & Alarm
System
Schematic Diagram
Water Leak Detection & Alarm
System
Sample Installation
Water Leak Detection & Alarm
System
System Components
Water Leak Detection & Alarm
System
System Components
II. Water Leak Detector
Water Leak Detection & Alarm
System
Sequence of Operation
1. Once the water touches the tape normally open contact, output will triggered and give
a signal to controller.
2. Upon the detection of water leak, alarm will turn on to notify nearby personnel.
Enyecontrols Billing System
(EC Bills)
- is the first real web-based online automated metering/billing system in the market.
• Automate billing, invoicing and payment collection of tenants (space rental, KWHR,
water, BTUH, etc.)
• Collect data for performance analysis
• Provide all tenants with all their consumption and energy usage online
• Provide tenants the actual value of the current (KWH, water, BTUH, etc.) consumption
online
• Building administrators can customize billings and invoicing processes fitted to
individual tenants
• Provide online payment options to tenants based on their comfort thru improving
customer relationship
Enyecontrols Billing System
(EC Bills)
Schematic Diagram
Enyecontrols Billing System
(EC Bills)
System Components
Enyecontrols Billing System
(EC Bills)
System Components
Enyecontrols Billing System
(EC Bills)
System Components
Enyecontrols Billing System
(EC Bills)
Sequence of Operation
1. Water Meter is for reading cubic meter consumption. Applicable in residential, commercial and
malls.
2. BTU Meter is for reading cooling consumption of tenants, condos and malls. The unit used is
BTU/hr.
3. Power Meter is for reading power consumption in all mechanical equipment (i.e. pumps, AHU,
Chiller). The unit used is kWh.
4. Omni Controller will receive all the data from devices to monitor the readings, trendlogs and
logging reports in excel file and graphical form.
5. The controller is connected to a router with internet.
6. EC BillS workstation is connected to a router. Also, the data will be saved to SQLdatabase.
7. The Xampp Software will collect all data from the SQL database and will reflect the actual reading
of all devices.
8. Tenant/Admin can login to ECBillS account to monitor the daily, weekly and monthly consumption
of the devices.
9. All reports can be printed or emailed to the recipient.
10. The admin can send memos or announcements to tenants.
Enyecontrols Billing System
(EC Bills)
Sequence of Operation
11. Tenants can view actual data on meter/performance of the device.
12. Tenants can view consumption and performance data.
13. EC BillS can perform online transactions.
14. ECBillS can send billing/online notifications on paid, unpaid, due dates on rental, kwHr, CUSA,
Water, BTUh, etc.
15. Tenants can make payments to ECBillS
Enyecontrols Billing System
(EC Bills)
Summary
Tenants/Customers
1. Very simple yet highly efficient & effective system
2. Automated receipt of Billing Statement
3. Can view actual data, history, consumptions
4. Easy payment options
- is designed for indoor and outdoor use wherever diesel fuel or other hydrocarbon-
based liquids are stored or pumped. There are no special tools needed for installation
and the system is designed for immediate and simple operation & maintenance by the
user.
Fuel Leak Detection and
Alarm System
Schematic Diagram
Fuel Leak Detection and
Alarm System
System Application
The fuel leak sensors are designed to be placed on the concrete floor, in a drip pan or within a mini
containment where leaking fuel will accumulate
Detection and alarm occur when the puddle of leaking fuel reaches the base of the sensor.
• Simple monitoring options with Relay Unit or as normally closed dry contact input to
DDC
• No moving parts
• Sensor will typically reset once removed from the spill and the fuel evaporates.
• Valves
• Pumps
• Flexible coupling and others fittings
• Fuel Level Indicator
Fuel Leak Detection and
Alarm System
Sequence of Operation
• When there is no fuel leak detection the sensor resistance is less than 100 Ohms
• Once there is a fuel leak detection the resistance will rise which will trigger the relay unit.
The pumps can be shutdown and the Solenoid valve will be fully closed
• The relay unit will give a signal to the digital controllers that will give an alarm to the BMS
or similar monitoring systems
“Committed to be your
business partner of choice!!”