Description: Module Options
Description: Module Options
Description: Module Options
1 Orden-753
2
LCD Indicators
LCD Description
1 Generator Available Lit Generador Disponible
2 Common Warning Lit Alarma de Advertencia
3 Common Shutdown Lit Alarma de Apagado
Miscellaneous Options
Application
Engine Options
about:blank 01-12-2023
6120 MPU Configuration Page 2 of 14
Inputs
Oil Pressure
Input Type
VDO 10 Bar
Shutdown Disabled
Trip 1,03Bar, 14,94 PSI, 103 kPa
Coolant Temperature
Input Type
VDO 120 °C
Shutdown
108 °C, 226 °F
Flexible Sensor
Flexible Sensor Alarms
Sensor Description
Input Type
Sensor Alarms
about:blank 01-12-2023
6120 MPU Configuration Page 3 of 14
Enable No
On 25 %
Off 75 %
Digital Inputs
Digital Inputs A - C
Digital Input A
Digital Input B
Digital Input C
about:blank 01-12-2023
6120 MPU Configuration Page 4 of 14
Digital Inputs D - F
Digital Input D
Digital Input E
Digital Input F
Digital Outputs
Output Configuration
Source Polarity
Output A Fuel Relay Energise
Output B Start Relay Energise
Output C Close Mains Output De-Energise
Output D Close Gen Output Energise
Output E Audible Alarm Energise
Output F Preheat During Preheat Timer Energise
about:blank 01-12-2023
6120 MPU Configuration Page 5 of 14
Timers
Start Timers
Start Timers
Load/Stopping Timers
Load Timers
Stopping Timers
Return Delay 2m
Cooling 3m
ETS Solenoid Hold 0s
Fail to Stop Delay 30s
Generator Transient Delay 0,0s
Module Timers
Interface Timers
Page 5m
Scroll 5s
about:blank 01-12-2023
6120 MPU Configuration Page 6 of 14
Generator
Generator Options
Generator Options
Shutdown Yes
Trip 259V PhPh 65,2 %
Loading Voltage
358V PhPh 90,0 %
Nominal Voltage
398V PhPh
Shutdown
Trip 479V PhPh 120,4 %
about:blank 01-12-2023
6120 MPU Configuration Page 7 of 14
Shutdown Yes
Trip 40,0 Hz 80,0 %
Loading Frequency
45,0 Hz 90,0 %
Nominal Frequency
50,0 Hz
Shutdown Yes
Trip 57,0 Hz 114,0 %
about:blank 01-12-2023
6120 MPU Configuration Page 8 of 14
Generator Current
Generator Current Options
Overcurrent Alarm
about:blank 01-12-2023
6120 MPU Configuration Page 9 of 14
Mains
Mains Options
Mains Options
Mains Alarms
Voltage Alarms
Frequency Alarms
about:blank 01-12-2023
6120 MPU Configuration Page 10 of 14
Engine
Engine Options
Engine Options
Sensing Options
Startup Options
Start Attempts 3
Loss of Sensing Signal Shutdown
Choke 2s
Gas on Delay 2s
Ignition Off Delay 2s
Crank Disconnect
Options
Crank Disconnect
about:blank 01-12-2023
6120 MPU Configuration Page 11 of 14
Speed Settings
Under Speed
Shutdown No
Trip 1200 RPM
Over Speed
Shutdown
Trip 1710 RPM
Plant Battery
Voltage Alarms
Shutdown Enabled
Trip 4,0 V DC
Delay 5s
Warning Enabled
Trip 6,0 V DC
Delay 5s
about:blank 01-12-2023
6120 MPU Configuration Page 12 of 14
Enable No
Threshold 18,0 V DC
Engine Run Duration 1h
Delay 5s
Maintenance Alarm
Maintenance Alarm
Enable Yes
Description Maintenance Alarm
Action Shutdown
Engine Run Hours 10 hrs
Scheduler
Exercise Scheduler
Enabled No
Scheduled run is On Load No
Day Start Time Duration
Monday 00:00 00:00
about:blank 01-12-2023
6120 MPU Configuration Page 13 of 14
Display Strings
Support Strings
Page 1
Page 2
Line 1
Line 2
Line 3
Page 3
Line 1
Line 2
Line 3
Page 4
Line 1
Line 2
Line 3
Page 5
Line 1
Line 2
Line 3
Page 6
Line 1
Line 2
Line 3
Page 2
Line 1
Line 2
Line 3
Alternative Configurations
Alternative Configuration Options
Alternative Configuration Options
about:blank 01-12-2023
6120 MPU Configuration Page 14 of 14
about:blank 01-12-2023