Professional Documents
Culture Documents
(YOKOGAWA) AMS Introduction R0
(YOKOGAWA) AMS Introduction R0
Solutions
주요 산업 재해
수익성
공장에 • 셧다운
규제의 압박 자원 & 전문성
갑작스러운 • 속도 저하
변수에 대응 • 품질 문제
Mechanical failure
Operational error
32% 42% Unknown
Process upset
Sabotage / Arson
0 25 50 75 100
People Process Equipment $M
Source: ARC white paper, January 2010 Source: J & H Marsh & McLennan, Inc.
AMS 국제 표준
• Alarm Overload
• Alarm Flood
• Nuisance Alarms
▪ Chattering Alarms ▪ Bad Actors
▪ Standing Alarms ▪ Frequently Occurring
Typical problems ▪ Stale Alarms ▪ Redundant Alarms
include….
• Alarms with No Response
“
• ISA-18.2 Standard 준수
• 제어 시스템과의 긴밀한 통합
• 작업자 지침이 필요
“
• 프로세스 안전 및 알람 관리가 중복됨
소프트웨어와 서비스의 결합
S O F T WA R E • Alarm Program
80% 66%
Petrochemical Plant in Asia Gas Plant in Europe
Philosophy
Alarm Master
Alarm Master Identification
Database (AMD)
Database (AMD)
Rationalization
Management
of Change
Detailed Design Audit
Alarm Reporting
Implementation and Analysis (ARA)
CAMS Operation
Monitoring &
Assessment Sequence of Events
Maintenance Recorder (SER)
AMS Power BI
Exaquantum/SER
Exaquantum/ARA
Exaquantum/AMD
1 2 3
Annunciated alarms per time Target value: Very likely to be acceptable Target value: Maximum manageable
Annunciated alarms per day per operating position 150 alarms per day 300 alarms per day
Percentage contribution of the top 10 most frequent <1% to 5% maximum, with action plan to address deficiencies
alarms to the overall alarm load
Quantity of chattering and fleeting alarms Zero, develop action plans to correct any that occur
Annunciated priority distribution If using three priorities: 80% low, 15% medium, 5% high
If using four priorities: 80% low, 15% medium, 5% high, <1% ‘highest’
Other special-purpose priorities are excluded from the calculation
Unauthorised alarm suppression Zero alarms suppressed outside of controlled or approved methodologies
Unauthorised alarm attribute changes Zero alarm attribute changes outside of approved methodologies or management of change (MOC)
IDENTIFY
IMPLEMENT RATIONALISE/APPROVE
Workshop
• 조치일(2020.01.13)일 이후 FC-D321 LO
Alarm 미발생
✓ 전체 알람 관리 라이프사이클을 포함
Questions?