Miniature Circuit Breakers
Range and applications – Saudi Arabia
S 800,
A whole range for S 800 PV S 200
every electrical
C/I R/C/I
installation
§ Rated current:
0,1A to 125A
§ Breaking capacity: SH 200
5 to 50kA S 200 80A & 100A
R
§ Tripping Curve: C/I
B, C, D, K, Z, K-M,
UC-B, UC-K
§ International Residential (R) Commercial (C)
standard approval
(IEC, UL, CCC, …) SU 200 M
§ Accessories: C/I
for every
application!
S 200 M
R/C/I
Industrial (I)
S 200 P
R/C/I
S 200 M UC
C/I
© ABB Group
July 16, 2018 | Slide 3
How to select circuit breaker (MCB)
The following FIVE questions need to be answered correctly.
1. Required Voltage
§ 1 phase or 3 phase
§ AC or DC
§ 24, 60, 72,125, 133, 230, 227, 400, 480V
2. Required Ampere rating
§ 0.5 to 125A
3. Required KA rating
§ 3kA to 50KA
4. Number of Poles
§ 1P, 2P, 3P, 4P, 1P+N & 3P+N
5. Applications
§ Distribution, DC traction, cascading, motor starting etc.
§ Required tripping curve B/C/D/K/Z
© ABB Group
July 16, 2018 | Slide 4
Miniature Circuit Breakers range
Products made for worldwide use
© ABB Group
July 16, 2018 | Slide 5
System pro M compact®
Range benefits
© ABB Group
July 16, 2018 | Slide 6
Uncompromising safety
Clear contact position indication
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 7 | Slide 7
Uncompromising safety and comfort
The improved terminal
left:
terminal closed
§ Increased terminal opening for higher
right:
wire gauges up to 35mm²
terminal opened
§ For conductors with or without
connector sleeves
§ Fulfills still the requirements for
protection degree IP20 (finger safe)
acc. to IEC/EN 60529
10 mm 2
25 mm 2
25 mm 2
2 x 16 mm 2
35 mm 2
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 8 | Slide 8
Uncompromising safety and comfort
The improved terminal
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 9 | Slide 9
System pro M compact®
Benefit from an established system
Maximum safety
§ Error proof terminals avoid the use of
free cable seats.
Space saving
§ Use the bottom fixed auxiliary contact
for space saving installation. Existing
installations can be easily upgraded to
include auxiliary switch functionality.
© ABB Group
July 16, 2018 | Slide 10
System pro M compact®
Benefit from an established system
Comfort connection
§ Connection busbars at the back of
patented twin-terminals guarantees
easier wiring even when device is
already fixed.
Maximum flexibility
§ Two terminal spaces on top or bottom
can be used for cables with different
cross-sections or combination of cables
and busbars.
© ABB Group
July 16, 2018 | Slide 11
System pro M compact®
Benefit from an established system
Uncompromising comfort
§ Special quick fastening system for
an easy removal of the devices
from the assembly, both for MCBs
S 200, S 200 M and RCCBs F 200.
Table of
contents
© ABB Group
July 16, 2018 | Slide 12
Approvals
Certification marks printed on dome
Example
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 13| Slide 13
State-of-the-art product marking
Laser printing
Front side printing
§ Laser marking for reliable readability
§ Scratch and solvent resistant
§ Non-abrasive
§ High contrast
§ Clear typeface
§ Similar marking as other
EAN code
ABB DIN rail products (e.g. RCDs)
§ EAN code
§ Quick identification of each device
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 14| Slide 14
State-of-the-art product marking
Individual identification code
Examples
§ Individual identification code for each
MCB on the front
§ Visible in mounted position
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 15| Slide 15
State-of-the-art housing material
Latest generation of thermoplastics
§ Recyclable
§ Halogen-free
§ High material stability
§ Minimized housing breakage
§ RoHS and REACH compliant
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 16| Slide 16
Miniature Circuit Breakers range
Quality made by ABB
§ Every single device that leaves our facilities is checked three times for
quality and performance reasons. Our completely automated test
methods such as thermal test, electro-magnetic test and isolation test
guarantee best results and to provide you with highest quality in your
daily business.
© ABB Group
July 16, 2018 | Slide 17
Miniature Circuit Breakers range
Quality made by ABB
© ABB Group
July 16, 2018 | Slide 18
Miniature Circuit Breakers S200 /S200 M/S200 P range
S 200
§ 6 up to 25 kA
© ABB Group
July 16, 2018 | Slide 19
The S2* series
MCBs of System pro M compact®
S 200
6000 acc. to IEC/EN 60898
n 10 kA acc. to IEC/EN 60947-2
n compliance to UL 1077 / CSA 22.2 No. 235
n K-characteristic: 0.5 – 63 A
n Z-characteristic: 0.5 – 63 A
© ABB Group
July 16, 2018 | Slide 20
The S2* series
MCBs of System pro M compact®
S 200 M
10000 acc. to IEC/EN 60898
n 15 kA acc. to IEC/EN 60947-2
© ABB Group
July 16, 2018 | Slide 21
The S2* series
MCBs of System pro M compact®
S 200 P
up to 25000 acc. to IEC/EN 60898
n up to 25 kA acc. to IEC/EN 60947-2
n compliance to UL 1077 / CSA 22.2 No. 235
n K-characteristic: 0.2 - 63 A
n Z-characteristic: 0.5 - 63 A
© ABB Group
July 16, 2018 | Slide 22
The next generation of UL 489 MCBs: SU 200 M
General data (New) Replaced S 200 U, S 200 UP & S 200 UDC
UL 489,
Standards CSA 22.2 No. 5,
IEC/EN 60947-2
Rated current In 0.2 … 63 A
Rated frequency 50 / 60 Hz
Rated voltage
277 V AC up to 40 A for C, Z characteristics,
277 V AC up to 35 A for K characteristics,
1P
240 V AC
48 V DC
480 Y / 277 V AC up to 40 A for C, Z char.,
2P, 3P, 4P 480 Y / 277 V AC up to 35 A for K char.,
240 V AC
Rated interrupting capacity 10 kA
Pole dimensions (H x D x W) 111 mm x 69 mm x 17.5 mm
© ABB Group
July 16, 2018 | Slide 24
The new universal current MCB range S 200 M UC
Benefits
© ABB Group
July 16, 2018 | Slide 25
The new universal current MCB range S 200 M UC
Product range
Type
IEC/EN 60898-2*
IEC/EN 60947-2 Rated current
UL1077**
CSA 22.2 No. 235**
B-type characteristic 6 … 63 A
© ABB Group
July 16, 2018 | Slide 26
System pro M compact®
MCB Accessories Overview
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 27| Slide 27
The next generation of MCBs: S 200 / S 200 M
Fully compatible to existing range of accessories
H Auxiliary contact
(changeover contact)
S/H Signal/Auxiliary contact
S/H (H) Signal/Auxiliary contact
used as auxiliary contact
ST Shunt trip
UR Undervoltage release
OR Overvoltage release
MOD-S (*) Motor operating device
H-L Auxiliary contact to be mounted
on the left
H-R Auxiliary contact to be mounted
on the right (2 contacts)
H-BF Auxiliary contact, bottom fitting
(1 per pole)
BP Mechanical tripping device
NT Neutral disconnector
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 28| Slide 28
Fitting of additional devices
S 200 / S 200 M, 1-pole
1-pole MCB
-left-
Left side
§ Breakout for auxiliary contact
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 29| Slide 29
Fitting of additional devices
S 200 / S 200 M, multipole
multipole MCB
-left-
Left side
§ Breakout for auxiliary contact
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 30| Slide 30
Bottom mounted auxiliary switch S 2C-Hxx
A space and cost saving solution
Early make
§ ON position, before the MCB
has closed the circuit
Late break
§ OFF position comes when the
MCB has opened the circuit
© ABB Group
July 16, 2018 | Slide 31
The next generation of MCBs: S 200 / S 200 M
Accessories
Auxiliary contact
Description Type code
§ To be mounted on §1 changeover contact § S 2C-H6R
the right side § 1 NO contact + 1 NC contact § S 2C-H6-11R
§ 2 NO contacts § S 2C-H6-20R
§ 2 NC contacts § S 2C-H6-02R
§ Tobe mounted on § 1 NO contact + 1 NC contact § S 2C-H11L
the left side § 2 NO contacts § S 2C-H20L
§ 2 NC contacts § S 2C-H02L
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 32| Slide 32
The next generation of MCBs: S 200 / S 200 M
Accessories
Undervoltage release
Description Type code
§ 10 types for different § 12, 24, 48, 110, 230 V DC § S 2C-UA .. DC
voltage levels
§ To be mounted on § 24, 48, 110, 230, 400 V AC §S 2C-UA .. AC
the right side
Overvoltage release
Description Type code
§ 2 types with different § 275 V AC § S 2C-OVP1
maximum tripping voltages
§ To be mounted on § 290 V AC §S 2C-OVP2
the right side
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 33| Slide 33
The next generation of MCBs: S 200 / S 200 M
Accessories
Neutral disconnector
Description Type code
§ No common switch-off with main device § S 2C-Nt
§ To be mounted on the left side
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 34| Slide 34
The next generation of MCBs: S 200 / S 200 M
Accessories
RCD-blocks
Description Type range
§ To be assembled with a MCB to provide protection against earth- § DDA 200 series
leakage currents and overcurrents in one single device
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 35| Slide 35
The next generation of MCBs: S 200 / S 200 M
Accessories
ATT-GSM module
Description Type range
§ For the peripheral control of electric loads via § ATT-…
the mobile network
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 36| Slide 36
© ABB Group
July 16, 2018 | Slide 37
The next generation of MCBs: S 200 / S 200 M
Accessories
Other accessories
§ Shock-protection caps
§ Identification labels
§ Locking devices
§ Terminal covers
§ Casing of insulating material
§ Rail connectors, auxiliary contact bridges, DIN rails
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
153| Slide
N0201 38| Slide 38
BU LPED – Enclosures and DIN-Rail Products DESTO/LM
®
Compact Home
Protection and comfort for your home
© ABB Group
July 16, 2018 | Slide 40
Miniature Circuit Breakers SH 200
Benefits at a glance
Contact position indication
All Compact® Home MCBs are suited with a contact
position indication (CPI) on the toggle. You can easily
identify, if the MCB is in the ON or the OFF position –
easy and safe maintenance work is possible.
Laser printing
All printings, like approvals on the dome, the product
identification, are printed by a laser.
© ABB Group
July 16, 2018 | Slide 41
Miniature Circuit Breakers SH 200
Benefits at a glance
Connection of SH and S
Compatibility with System pro M compact®
is given in all kind of variations like insertion of one
System pro M compact® MCB into an installation with
Compact® Home components and Compact® Home
busbars. Also the combination of one Compact® Home
MCB with System pro M compact® components and
System pro M compact® busbars is possible.
Terminals
The Compact® Home MCBs are equipped with 25 mm2
cage terminals. The cross wiring can easily be done by
inserting the Compact® Home busbars and then the
incoming wires into one of the MCB’s terminals. The
terminals accept Compact® Home busbars and
conductors up to 16 mm2 together.
© ABB Group
July 16, 2018 | Slide 42
Two Product Strategy
Compact Home / Pro M Compact - Performances
S200 SH 200
Tripping characteristics B, C, D, Z, K B, C
IEC/EN 60947-2 &
Standard acc. to : IEC/EN 60898-1
120
IEC/EN 60898-1
60
40
60
40 20
20 10
T = 3 kA
Minutes
L = 4.5 kA 10
6
6
Breaking capacity „“ = 6 kA 2
2
L = 4.5 kA
1
1 40
40
M =10 kA 20
20
„“ = 6 kA
6
P = 25 kA 6
4
2
4
2
Seconds
B: 6 … 63 A,
0.2 Z B C DD B: 6 … 40 A
0.2 B C
~ ~ ~ ~
C: 0.5 … 63~A C: 6 … ~40~ A
0.1 0.1
K
0.02 0.02
Rated current D: 0.5 … 63 A 1 1.5 2 3 5 10 20 30
1 1.5 2 3 4 5 6 8 10 14 20 30
Z: 0.5 … 63 A Multiple of rated current Multiple of rated current
K: 0.5 … 63 A
1, 2, 3, 4 1, 2, 3, 4
Poles
1 + NA, 3 + NA 1 + NA, 3 + NA
© ABB Group
July 16, 2018 | Slide 43
Auxiliaries Availability Yes No
ABB CMC Low Voltage Products
© ABB Group
July 16, 2018 | Slide 44
S800 – Portfolio
© ABB Group
July 16, 2018 | Slide 45
S800S
Technical Data
Rated voltage Ue 230 / 400 - 690VAC
250VDC / pole
Rated current In 6* / 10 - 125A
(*acc. to B, C, D, K-characteristic)
Rated breaking capacity Icu 50kA (240 /415VAC)
50kA (250/500/750VDC)
Characteristics B, C, D, K,
KM up to 80A
UCB, UCK
Number of poles 1-4
Standards IEC 60947-2
EN 60898-1 up to 80A
Approvals electrosuisse, CCC, GOST-R,
LR, GL, DNV, RINA, RMRS
© ABB Group
July 16, 2018 | Slide 46
S800N
Technical Data
Rated voltage Ue 230 / 400 - 690VAC
Rated current In 6 - 125A
Rated breaking capacity Icu 36kA (240 /415VAC)
Characteristics B, C, D
Number of poles 1-4
Standards IEC 60947-2
EN 60898-1 up to 80A
Approvals electrosuisse, CCC, GOST-R
© ABB Group
July 16, 2018 | Slide 47
S800C
Technical Data
Technical data
Rated voltage Ue up to 254/440 VAC
Rated current In 10 - 125A
Rated breaking capacity Icu 25kA (240 /415VAC)
Characteristics B, C, D, K
Number of poles 1-4
Standards IEC 60947-2,
EN60898-1 (up to D100)
Approval electrosuisse
© ABB Group
July 16, 2018 | Slide 48
S800B
Technical Data
Technical data
Rated voltage Ue 230/400 VAC
Rated current In 32 – 100 / 125A
Rated breaking capacity Icu 16kA
Characteristics B, C (up to 125A)
D, K (up to 100A)
Number of poles 1-4
Standards IEC 60947-2
EN60898-1
Approval electrosuisse
© ABB Group
July 16, 2018 | Slide 49
S800U
Technical Data
Rated voltage 240 VAC
Rated current In 10 - 100A
Rated breaking capacity 30kA, 50kA (multipole)
Characteristics Z, K
Number of poles 1-4
Standards IEC 60947-2
UL489
Approval UL489
© ABB Group
July 16, 2018 | Slide 50
S800PV-S
Technical Data
Rated voltage Ue 2-pole 800VDC (600VDC for I>80A)
3-pole 1200VDC (1000VDC for I>80A)
4-pole 1200VDC
Rated current In 10 - 125A
Rated breaking capacity Icu 5kA (800VDC); 5kA (1200VDC)
Characteristic based on UC-B
Calibration temp. 30°C
Ambient temperature -25…70°C
Utilization category A
Number of poles 2–4
Standard IEC 60947-2
Approval VDE
© ABB Group
July 16, 2018 | Slide 51
S800PV-M
Technical Data
Rated voltage Ue 2-pole 800VDC
3-pole 1200VDC
4-pole 1200VDC
Rated current In 32, 63, 125A
Rated short time withstand Icw 1.5kA (800VDC)
1.5kA (1200VDC)
Characteristic none
Switch-disconnector
Ambient temperature -25…60°C
Number of poles 2–4
Standard IEC 60947-3
Approval VDE
© ABB Group
July 16, 2018 | Slide 52
© ABB STOTZ-KONTAKT
Group GmbH
July
2CDC 16,002
2018
154| Slide
N0201 53| Slide 53