Professional Documents
Culture Documents
Meter&Control - ST300 - Modular Meter
Meter&Control - ST300 - Modular Meter
Meter&Control - ST300 - Modular Meter
ST300
ST300 is three-phase modular smart meter designed for measure- module (CMxyS - PLC or GPRS/3G communication) and switching
ment of active and reactive energy of commercial and industrial module (SD30S) via M-Bus connection. Both plug-in modules are
consumers, with direct, semi-indirect and indirect grid connection. simply mounted under the terminal cover. ST300 is compliant with
ST300 can also be used in single-phase networks. AMI system inte- all relevant standards and regulations.
gration is enabled by connecting optional plug-in communication
Key features
Measurements connection; 40 000 imp/kWh (kvarh) i.e. 15-minute average load profile (1 Firmware update
• Measurement of power and energy in for VT connection channel) is stored for 45 days • Enabled locally or remotely with no
both directions and absolute values • 2 push buttons on the meter cover impact on accuracy, parameter config-
(A+, A-, |A|, R+, R-, optionally R1, R2, • OBIS data ID code: IEC62056-61 Log books uration or billing data
R3, R4) • Standard log book with up to 200 logs
• Active energy measurement – Index Optical port and states
classes 0.2s, 0.5s or 1, reactive energy • Physical layer according to IEC 62056-21 • Quality event log book No-power reading
measurement - class 2 or 3 • DLMS/COSEM communication • Fraud detection log book • Local reading via display or optical
• Measurement of voltages and cur- protocol • Disconnector control log book port
rents by phases, frequency and power
factor Electrical ports (physical layer) Energy quality measurement Integration into AMI system
• Port A: RS 485 for communication with • Maximum and minimum voltage Communication with AMI system
Maximum demand AMI Center (active) registration • ST100 is ready for addition of plug-in
• Programmable maximum demand • Port B: M-Bus master for communi- • Voltage variation registration communication module (PLC or
integration period is generated by cation with the switching module and • Maximum current registration GPRS/3G) on port A
internal clock (typically 5, 10, 15, 30 or other energy meters compliant with • Outage registration (short outage – Load management
60 minutes) EN 13757-2 Event counter, long outage – Long • ST100 is ready for addition of plug-in
power interruption log) switching device on port B
Multi-rate registration and TOU Inputs and outputs (optional) • Under-voltage and over-voltage meas- • Switching device in accordance with
• Programmable tariff structure • 2 control inputs for tariff control urement and registration in Quality IEC 62055-31, UC2/UC3
(up to 4 tariffs) • 2 tariff outputs (100 mA) Event log book
• Up to 4 seasons and 4 weekly • 2 pulse outputs Data protection
changeovers • 1 control output with bi-stable relay (6A) Fraud detection • Local parameterization is protected
• Up to 9 day types and 32 holidays • Detection of meter cover opening / by multi-level passwords and push
• Up to 10 daily changeovers Communication protocol closing button positioned under terminal
• Optical port and port A: DLMS • Detection of terminal block cover block cover
Internal Real-time clock with DST (IEC 62056-46) opening / losing
• In accordance with IEC 62054-21 • Port B: M-Bus (EN 13757-3) • Detection of wrong authorization for Meter quality
• Automatic DST switching (optional) meter parameterization • High accuracy and long term stability
• Battery backup supply, optionally Billing profiles • Detection of strong magnetic field of metering elements. No recalibra-
super-capacitor • Billing profiles (registered energy and • Detection of neutral conductor tion required during meter lifetime
maximum demand values by tariffs) interruption • High meter reliability
Visual communication with meter are generated and stored for the last • Recording of events in the Fraud • High immunity to EMC
• LCD and display modes according to 18 billing intervals event log book
VDEW specifications Current terminal block
• Programmable selection of data and Load profiles Power limiting (optional) • For current up to 60 А: for all types of
display sequence • 4 load profiles with 7 channels each • Power or current limiting of electricity conductors up to 16 mm2
• LED: 1000 imp/kWh/kvarh; 10 000 • Independent, programmable registry consumers by defining the limit value • For current up to 120 А: for all types
imp/kWh/kvarh for direct and CT intervals (5-60 minutes, 1-24 hours) of power or current in the dedicated of conductors up to 35 mm2
• Sufficient memory (4 320 registries, meter register
• Dedicated log book (10 switching Compact meter case
Accuracy class module disconnections / connections) • High quality, transparent, reinforced,
active energy 0.2s, 0.5s or 1 self-extinguishing polycarbonate case
Code Red (optional) • IP54 protection against water and
reactive energy 2 or 3 • Enables synchronous power limiting dust (in accordance with IEC 60529)
Nominal and maximum current of groups (large number) of users in
direct connection 5 (60) A, 5 (120) A case of irregular situation on distribu-
tion network (e.g. lack of power)
transformer connection 1 (6) A, 5 (6) A
Minimum current Imin 0.05 In
Nominal voltage, Un 3x230/400 V, 3x400 V, 3x57,7/100 V, 3x100V,
230 V
Voltage range 0.8 Un – 1.15 Un
Frequency 50 Hz
Ports and protocols
optical port IEC 62056-21 (physical layer)
IEC 62056-46 (DLMS) communication protocol
154,5
RS485
142
electrical port A
IEC 62056-46 (DLMS) communication protocol