10 CON TR-133
104-08655-440-DSH-E-001
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
0000 GENERAL
0001 Supplier By Vendor
0002 Manufacturer By Vendor
0003 Location of assembly plant By Vendor
0004 Primary Standard
a ANSI: C.37 series YES
b NEMA: SG series YES
3000 RATINGS
3001 Rated MaximumVoltage Fase-Fase 25 kV
3002 Nominal Voltage Class 23 KV
3003 Rated BIL @ meters above sea level according site condition 170 kV
3004 Frecuency 60 Hz
3005 Rated Short Circuit Current 40 kA simmetrical
3006 At Rated maximum KV closing and latching capability 107 kA Crest
3007 Tree Second Rating 40
1 KA
3008 Nominal 3 phase MVA class MVA
3009 Rated Interrupting Time 3 Cycles
3010 Bus Bracing 40
1 kA simmetrical
4-08655-440-DSH-E-001-Rev1 Page 1 of 6
104-08655-440-DSH-E-001
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
4000 SWITCHGEAR BUS, BUS JOINTS AND CABLE TERMINATIONS
4001 Material
a copper YES
b aluminum
4002 Main Horizontal Bus & Connections
a Insulated at factory YES
b Rated Continuous Current 600 A
4003 Vertical Bus & Connections
a Insulated at factory YES
b Rated Continuous Current 1200 A
4004 Neutral Bus 1
a required NO
b insulated
c Rated Continuous Current
4005 Ground Bus
a Rated Continuous Current 400 A
b insulated NO
c Position
c.1 Top
c.2 Bottom YES
4006 Insulators
a porcelain
b epoxy
c manufacturer's standard YES
4007 Power Circuit Bus Joints and Cable Terminations:
a Silver plated joints, lugs, and terminals required YES
Seller to furnish non-flammable insulating boots for bus joints at shipping
b YES
splits and outgoing bus connections
85°C max. operating temp. for lugs or terminals furnished for Buyer's
c YES
cables
Seller to furnish terminals with NEMA standard 2 hole drilling for each
d Buyer's cable; for more than two cables per phase, one cable at each YES
position may be connected on each side of a terminal
Seller to provide cable bending space inside enclosures for Buyer's cables
e YES
Seller to provide space for stress relief terminations without bends for all
f cables operating above 2000 V; the length to be allowed for stress relief YES
terminations beyond the lugs or terminals in enclosures is:
f.1 for 2001 through 8000 V cables 10 ( 254 ) INCH (mm)
f.2 for 8001 through 15000 V cables 16 ( 400 ) INCH (mm)
f.3 for 15001 through 25000 V cables 22 ( 560 ) INCH (mm)
f.4 for 25001 through 35000 V cables 31 ( 780 ) INCH (mm)
5000 INCOMING
5001 Incoming Line
a Cable 350 MCM
b Bus Duct
c Top Entry
d Bottom Entry YES
e Cable/Bus material (copper/aluminum) COPPER
f Lugs by Manufacturer
5002 Partial discharge monitoring system YES
4-08655-440-DSH-E-001-Rev1 Page 2 of 6
104-08655-440-DSH-E-001
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
b continuous & load interrupting current
b.1 600 amp A
b.2 1200 amp
b.3 2000 amp
b.4 Other
c Momentary Current kA Asymmetrical.
d Short time current: two seconds. kA Symmetrical
6006 fuse type
a Current Limiting
b Boric Acid (Expulsion Type)
c Nonfused
6007 Fuse rating A
a continuous current rating range A
b interrupting rating kA Symmetrical
6008 sswitch
tc mounting
ou t g type
a clip
b clip-lock
c bolt-on
d clamp-on
e other
6009 Control Voltage
6010 Auxiliary Contacts
a N.O.
b N.C.
6011 Key Interlock
6012 Push Button Manual Close
6013 Push Button Manual Open
Each disconnector switch shall be mechanically interlocked with its compartment
6014 to prevent the use of a disconnector switch with a lower rating or different
connections in that compartment
4-08655-440-DSH-E-001-Rev1 Page 3 of 6
104-08655-440-DSH-E-001
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
7019 Control Voltage 125 V dc
7020 Auxiliary Contacts
a N.O. 4
b N.C. 4
7021 Key Interlock YES
7022 Circuit Breaking stacking
a One high YES
b Two high
7023 Push Button Manual Close YES
7024 Push Button Manual Open YES
7025 Local Remote selector YES
7026 Electrically separate MOC Stationary Auxiliary Contacts (device 52S) operated by
a N.O.
b N.C.
7027
0 Electrically
ect ca y separate
sepa ate TOC
OC Switch
S tc cocontacts
tacts (de
(device
ce 552H)) S
YES
Each circuit breaker shall be mechanically interlocked with its compartment to
7028 prevent the use of a circuit breaker with a lower rating or different connections in YES
that compartment
7029 Resistance Grounded
4-08655-440-DSH-E-001-Rev1 Page 4 of 6
104-08655-440-DSH-E-001
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
f Microprocessor-Based Multifunction Metering System YES
g Network Communication Modbus TCP
Refer to Oneline Diagram for individual Breaker details, Relaying, Metering and 1
10004 YES
other accessories
13000 NAMEPLATES
13001 Engraved lamicoid plastic nameplates, black letters with white background YES
13002 Stamped stainless steel nameplates with paint filled letters
13003 Equipment nameplates mounted with machine screws only YES
Nameplates with Buyer's equipment tag number required for each item of
13004 YES
equipment
Nameplates required for each compartment, control switch, terminal board,
13005 YES
instrument, relay, meter, or other device
19000 ACCESORIES
Remotely controlled electrically operated ground and test device with a self
contained bus and line selector switch, a 3phase ground switch, plugs for testing
19001
cables and six circuit stabs for bus and line connections for use in place of each
type of circuit breaker.
19002 One set of special tools required for the installaton and maintenance of YES
switchgear
4-08655-440-DSH-E-001-Rev1 Page 5 of 6
104-08655-440-DSH-E-001
GENERAL
Vendor's Contact Name Client's Contact Name
Information: Phone Information: Phone
E-mail E-mail
(Nota 1)
No. DESCRIPTION REQUIRED QUOTED UNITS
19003 One closing device for manually closing circuit breaker YES
19004 Two sets of test plugs for test switches, drawout meters and relays YES
19005 One wall mounted test cabinet for each type of breaker YES
19006 One coupling cable for testing a circuit breaker in the drawout position YES
19007 One complete circuit breaker lifting and handling device (if required) YES
4-08655-440-DSH-E-001-Rev1 Page 6 of 6