Professional Documents
Culture Documents
Examination pq2018 Oefententamen 2018
Examination pq2018 Oefententamen 2018
Examination pq2018 Oefententamen 2018
In the low voltage network all houses will get PV-systems installed. There will be a problem with
overvoltages in the network. What is the worst solution to solve this overvoltage problem? The
R/X- ratio of the cable is high.
1b
B The phase shift between all voltages across the resistances is 120 degrees
D Connecting a neutral conductor will change the currents flowing in the resistances.
1c
In the MV-network there is a voltage dip in the line voltage VBC. What is the effect on the low
voltage voltages?
1d
Harmonic components in the voltage can have the same rotation direction as the fundamental
system (normal system), an inverse rotation direction or a zero-sequence system. For the 11th
harmonic this is a:
A Normal system
B Inverse system
C Zero-sequence system
1e
On board of a ship some VSD’s with high harmonic distortion are connected to the installation.
To prevent the occurrence of high voltage distortion active filtering of the harmonic current is
used. Which of the following statement is NOT true?
C Impedances of the conductors are less important compared to the impedance of the
generator(s)
In the factory connected to the POC there are sensitive devices which will fail when there is a
voltage dip at the POC. To get some information of the possible number of dips (including
duration and remaining voltage) calculations in the network has to be made.
… 4 more MV rings
… 4 more MV rings
Calculate:
a) Draw an equivalent circuit looking into the substation at the 7th harmonic (connected to
the public network)
b) Determine the parallel resonance frequency, when connected to the public network, and
the capacitor bank switched on.
c) What is the system impedance seen from the non-linear load at the resonance
frequency?
d) What will be the effect when the public network is disconnected and the installation is
supplied by the generator? Describe in general terms.
e) What will be the effect of switching off the 400 kW linear load? Recalculate point c) with
this change. Should the resulting distortion levels become greater or lower (or stay the
same)?
Two similar loads (400 V, Resistant of 10Ω) are connected to the Scott-transformer. At the
primary 3 phase side of the transformer the load is seen as a balanced three phase load.
Solar systems and EV-loads are connected to a MV-substation (10 kV line to line) using cables
between every station with the following impedances: (R=200mΩ/km, X=100mΩ/km). Each
cable section is 2 km long. The two feeders are operated as radial systems, but could be
connected, to operate as a ring system.
Every PV-system has a maximum power of 2 MW. Every EV-load is 3 MW. (PF can be assumed to
be 1).
a) Calculate the currents (I1, I2) and the voltages at each connection point when NOP is
open. Assume the voltage at the MV side of the transformer to be 10 kV (and constant in
all conditions).
b) What is the best setting of the transformer to get the average voltage at each customer
the closest to the nominal voltage of 10 kV. Assume available settings as 10 kV ± 5 %,
with steps of 1 % in both directions.
d) Calculate the currents (I1, I2) and the voltages at each connection point when NOP is
closed.
Formulas
1
Ih
HDh (%) = ⋅100% e I1 hmax q I h
2 2 2
I1 K = 1 + ∑ h
e + 1 I h = 2 I1
∞
∑I
2
h
n=2
THDI 1 (%) = ⋅100%
I1 2
h = hmax
I
∞ K= ∑ h h
2
∑I
2
h h=2 I
n=2
THDIrms (%) = ⋅100%
I rms
50
S = ∑U h • I h • 3
h =1
50
P = ∑ (U h • I h • 3 • cos ϕ h )
h =1
50
D = ∑ (U h • I h • 3 • sin ϕ h )
h=2
Q = S 2 − P2 − D2
∆U = U − U i = I ( RA + Rn ) cos ϕ + I ( X A + X n ) sin ϕ
1
∆𝑈𝑈
𝑃𝑃𝑠𝑠𝑠𝑠 = 0.337 ∙ 𝐹𝐹 ∙
𝑈𝑈
∙ 100 ∙ 𝑟𝑟 3.2 PQ1+ 2 = β PQ1β + PQ2β
1 12 3
Plt = 3 ∑ Pst ,tot ,i
12 i =1 Sx
Vdipx = 1 −
S0
n
Pst ,tot = 3 ∑P
i =1
3
st ,i