Condensing Unit - Selection

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Performance Summary For Cu_Selection

Project: Djibouti_21 Dec 2011_CU 12/21/2011


Prepared By: 06:10PM

System: 38APS030
Circuit: Single Circuit
System Quantity: 1
Altitude: 0.0 m
EER @ ARI Conditions: 11.5
EER @ Ambient Conditions: 8.2
IPLV: 15.9
Suction Pipe Connections: 1-5/8
Liquid Pipe Connections: 7/8
Suction Line Loss: 1.1 °C
Condensing unit is rated in accordance with ARI 365.

Liquid and Suction Line Sizing

Pipe Length Liquid Line Size Suction Line Size


0 - 25 5/8 1 3/8
26 - 50 5/8 1 5/8
51 - 75 7/8 1 5/8
76 - 100 7/8 1 5/8
101 - 125 7/8 2 1/8
126 - 150 7/8 2 1/8
151 - 175 7/8 2 1/8
176 - 200 7/8 2 1/8

Do NOT exceed 200 ft max linear separation or 75 ft vertical liquid lift. Oil management is critical on split systems for
compressor reliability. Refrigerant circuit warranty may be void beyond these limits.

Dual suction riser may be required, refer to PD.

Outdoor Unit Parameters


Unit Quantity: 1
PartNumber: 38APS03094-12050
Unit Model: 38APS
Unit Size: 30 Tons
Voltage: 380/415-3-50 V-Ph-Hz
Total Clg Cap.(Gross): 78.8 kW
SDT: 59.8 °C
Clg Ent Air DB: 46.0 °C
Saturated Suction Temp: 6.5 °C

Outdoor Electrical Data


Unit Voltage: 380/415-3-50 V-Ph-Hz
Unit#1 MCA: 67.1 Amps
Unit#1 MOCP: 90.0 Amps
Compressor Power: 30.70 kW
Voltage Range Min: 342 V
Voltage Range Max: 440 V
Compressor RLA: 26.9
Compressor LRA: 174
Compressor Quantity: 2
Fan Motors Qty: 2
Notice: Outdoor unit elect. data is based on 380-3-50

FIOPS and Accessories Information

FIOPS Quantity

MCHX
Digital Compressor 1

Commercial Split Systems Builder 1.19p Page 1 of 2


Performance Summary For Cu_Selection
Project: Djibouti_21 Dec 2011_CU 12/21/2011
Prepared By: 06:10PM

No Display - Navigator required


Accessories Quantity
Thermostat for Outdoor Unit 1

Liquid line check valve(s) prevent charge migration to compressor. These valves may be required for certain applications,
refer to PD.

Acoustic Information
A-Wgt Outdoor Sound Power Level: 92.0 dbA

An uncoated Novation condenser coil was selected for this product. This is based on an installed location that must be
analyzed and guidance provided by applications engineering and a non-corrosive localized environment.

Commercial Split Systems Builder 1.19p Page 2 of 2