Installation Instructions

IQ3../.../LAN/...
Controller/Interface

Important: Retain these instructions

CONTENTS
1 Installation - Mounting 1 3 Insertion/Replacement of battery 3
2 Installation - Configuration 2 4 Disposal

1 Installation - Mounting

1 Install

Install according to IQ3xact or IQ3xcite installation instructions


section 3 steps 1 to 11
IQ3xact Installation Instructions TG200766
IQ3xcite Installation Instructions TG200626

2 Connect IQ System Current Loop Network


Cable 9k6 b au d 19k2 b au d No. of Wires
Network Engineering Manual, 1000 m 700 m
Belden 9182 2
92-1735 (1090 yds) (765 yds)
1000 m 500 m
Belden 9207 2
(1090 yds) (545 yds)
2 off 2 part connectors with 4 screw terminals for 0.5 to 2.5 mm2 cross Trend
700 m 350 m
section area (14 to 20 AWG) cable TP/1/1/22/HF/200 2
(765 yds) (380 yds)
(Belden 8761)
Trend
500 m 250 m
TP/2/2/22/HF/200 4
polarity independent (545 yds) (270 yds)
(Belden 8723)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

+
1 0 +
2 0 +
3 0 +
4 0 +
5 0 +
6 0 +
7 0 +
8 0 +
9 0 +
10 0

TX RX
OK

100-240 V A 11 12 13 14 15 16
P 0 P 0 P 0 P 0 P 0 P 0
24 V

24 V

OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
0V

Using 2 wire method Using 4 wire method


IQ LAN IQ LAN

T- T+ R- R+ T- T+ R- R+ T- T+ R- R+ T- T+ R- R+
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4

OUT IN

earth (ground) screen to


convenient input channel
screen terminal OUT IN

25 26 27
N
earth (ground) screen to convenient
+ 0
input channel screen terminal

25 26 27

+
N 0

IQ3../.../LAN/... Installation Instructions TG200916 Issue 1/C 01/05/07 1


IQ3../.../LAN/... Installation Instructions

1 Installation - Mounting (continued)

3 Continue Installation

Install according to IQ3xact installation instructions from section 4 step 1 to section


4 step 19, or IQ3xcite installation instructions from section 3 step 13 to section 4
step 20.
IQ3xact Installation Instructions TG200766
IQ3xcite Installation Instructions TG200626

2 Installation - Configuration

1 Continue Installation

Complete section 1 above and IQ3xact installation instructions up to section


4 step 19, or IQ3xcite Installation Instructions up to section 4 step 20.
IQ3xact Installation Instructions TG200766
IQ3xcite Installation Instructions TG200626

2 Set current loop Network Baud Rate and Address 1

+
2
1
3

0
4

+
5
2
6

0
7

+
8
3
9

0
10 11 12

+
4 0
13 14 15 16 17 18

+
5 0 +
6 0
19 20 21 22 23 24

+
7 0 +
8 0
25 26 27 28 29 30

+
9 0 +
10 0

a, Set address switch TX RX


OK

0 100-240 V A
P
11
0 P
12
0 P
13
0 P 0 P
14
0 P
15
0
16

24 V

24 V
OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

0V
1 SET

1 2 4 8 16 32 64 Address = A
e.g. Address = 2 + 16 = 18 =A*
NOT SET
IQ3../.../LAN/...

address =A
/ =A
/

1, 4 to 9, 11 to 119
=A
/
0, 2, 3,10 or >119
*Note that the IQ3../.../LAN/... may also use addresses for
its virtual CNC, and for its local supervisor CNC which
should also be unique on the Lan.
b, Set baud rate switch
IQ system Lan baud rate = B
0
19k2 =B
1
19K2
9K6

9k6 =B =B
e.g. Baud Rate = 19k2

=B

2 IQ3../.../LAN/... Installation Instructions TG200916 Issue 1/C 01/05/07


Installation Instructions IQ3../.../LAN/...

2 Installation - Configuration (continued)

3 Check network
a TX
IQ3../.../LAN/...
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

+
1 0 +
2 0 +
3 0 +
4 0 +
5 0 +
6 0 +
7 0 +
8 0 +
9 0 +
10 0

TX RX ?
TX RX
OK

OK
100-240 V

24 V
A
P
11
0 P
12
0 P
13
0 P 0 P
14
0 P
15
0
16
b RX
24 V
OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

0V
IQ3../.../LAN/...

c OK

Network Address
0,2,3 or >119

OK
IQ3../.../LAN/...
Check network cabling for
OK short circuits with a
IQ LAN IQ LAN
multimeter (NOT Megger)
T- T+ R- R+ T- T+ R- R+ IQ Faulty T-
1
T+
2
R-
3
R+
4
T-
1
T+
2
R-
3
R+
4
1 2 3 4 1 2 3 4
Check baud rate. Switch on
other nodes until faulty
node is found (OK ).
O
Correct fault.
I

4 Continue Installation

Continue installation according to IQ3xact installation


instructions section 4 step 22 on, or IQ3xcite installation
instructions section 4 step 22 on IQ3xact Installation Instructions TG200766
IQ3xcite Installation Instructions TG200626

3 Insertion/Replacement of Battery (if battery required)

Switch Off Isolate I/O


1 2 O

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

+
1 0 +
2 0 +
3 0 +
4 0
5 +
6 0

WARNING: The
+ 0

O connecting leads
may be connected
to supplies. Isolate before
I
100-240 V A
P
11
0 P
12
0 P
13
0 P
14
0 P
15
0 P
16
0
touching.
24 V

24 V

OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
0V

Open Panel
3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

+
1 0 +
2 0 +
3 0 +
4 0 +
5 0 +
6 0 +
7 0 +
8 0 +
9 0 +
10 0

WARNING: Opening the panel may expose


100-240 V A A
P
11
0 P
12
0 P
13
0 P
14
0 P 0 P
15
0
16
dangerous voltages.
24 V

24 V

OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
0V

417-IEC-5036

IQ3../.../LAN/... Installation Instructions TG200916 Issue 1/C 01/05/07 3


IQ3../.../LAN/... Installation Instructions

3 Insertion/Replacement of Battery (continued)

Remove Auxiliary Board Cover Remove battery


4 5 (if replacing battery)

a
b

c Warning: The lithium battery must not be


d + recharged, disassembled, burnt or
short circuited. Misuse may cause
explosion or fire. Dispose of carefully
(see section 4, Disposal, below).
Refer to Health and Safety Executive Guidance
Note GS43.

Insert new battery Replace Auxiliary Board Cover


6 7
CR2032 3 V a b
CR 2032
CR 2032

Close Panel Reconnect Supply to I/O Switch On


8 9 10
O
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

+
1 0 +
2 0 +
3 0 +
4 0 +
5 0 +
6 0 +
7 0 +
8 0 +
9 0 +
10 0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

+
1 0 +
2 0 +
3 0 +
4 0 +
5 0 +
6 0
A
100-240 V A 11 12 13 14 15 16
P 0 P 0 P 0 P 0 P 0 P 0
24 V

24 V

OK RX 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
0V

I
IQ3.../.../XNC/.../USA/UL/24 is 100-240 V A
P
11
0 P
12
0 P
13
0 P
14
0 P
15
0 P
16
0
24 V

24 V

OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
0V

O
UL rated as ‘UL916 listed open I

energy management
equipment’.

4 Disposal

WEEE Directive :
At the end of their useful life the packaging,
product, and any battery should be disposed
of by a suitable recycling centre.
Do not dispose of with normal household waste.
Do not burn.

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content
hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems Limited


P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com

4 IQ3../.../LAN/... Installation Instructions TG200916 Issue 1/C 01/05/07