Connect load to the three + and - terminals paralleled for your

convenience.

PS25
Supervised Bus
Power Supply
EVO/MG/SP 7 to 14Ah
Rechargeable
Installation Manual Battery
Version 1.10 and higher

Introduction Transformer: Input 110 or 230 Vac, 50 - 60 Hz


The PS25 is a 2.8A supervised switching power supply that connects to the Output: 16 Vac, 40 VA
Paradox control panel’s bus or may work as a standalone power supply. Note: Only one supervised power supply is supported on MG/SP panels.

The PS25 provides a maximum of 2.5A (13.8VDC) continuous auxiliary Box Installation
power output and charge battery with 300mA. Battery charging current may
Mount the PS25 in a metal box using the appropriate mounting holes, as
increase up to 1.2A if auxiliary current is reduced accordingly.
shown below.

Compatibility
• EVO192, EVOHD v7.14 and higher
• MG5050, SP5500, SP6000, SP7000 v6.80 and higher
• BabyWare v5.1 and higher
• Infield v5.1 and higher

Connections
Connect the 4-wire (RED BLK GRN YEL) to the panel keypad bus. Please
note that the RED (+) terminal is not providing power nor is it connected in
any way to the PS25; it is provided for convenience only.

Connect the battery (7Ah to 14Ah) and a 40VA transformer. Connect the
tamper switch, no enrollment is needed, it will auto detect the tamper once Upgrading Firmware
the terminal is shorted and it will follow panel configuration. The PS25’s firmware can be upgraded in Infield via BabyWare using a
307USB Direct Connect Interface.
Note: As the battery ages, its capacity diminishes like all rechargeable
components. The minimum acceptable battery capacity is 90%. Any lower LED
value will result in a battery trouble.
LED OFF ON
BUS No connection to panel Panel online
CHARGE Not charging Battery charging
Aux 10.5V - 14.0V
AUX No power
RED: Voltage below 10.3V
paradox.com PS25-EI02 06/2021
Programming EVO Programming MGSP
1. Enter section [3038]. 1. Enter section [700].
2. Select option [7] to enable or disable Tamper supervision on the bus 2. Select option [7] to enable or disable Tamper supervision on the bus
module. Default is disabled. module. Default is disabled.
3. Enter section [3034]. Select option [5] and [6] to define Keypad/Bus 3. Enter section [705]. Select option [3] and [4] to define Keypad/Bus
Module Tamper Recognition options. Refer to the table below. Module Tamper Recognition options. Refer to the table below.
Options Description
Options Description 3 4
5 6 OFF OFF Disabled
OFF ON Trouble only
OFF OFF Disabled
When armed: Audible alarm
OFF ON Trouble only ON OFF
When disarmed: Trouble only
When armed: Follows zone types for zone tamper; ON ON Audible alarm
ON OFF generates trouble for module tamper
When disarmed: Trouble only 4. Enter section [839]. The value programmed in this section represents
When armed: Follows zone types how long the Power Supply Module will wait before reporting an AC
ON ON power failure.
When disarmed: generates audible alarm
5. Enter a three-digit decimal value (000 to 255 minutes). Default is set
4. Enter section [4003]. 30 minutes.
5. Enter the PS25’s eight-digit module serial number.
6. Enter the three-digit module section number you wish to program. Technical Specifications
7. Enter section [002]. The value programmed in this section represents
AC Power Input* 100 Vac 0.4A or 230 Vac 0.2A, 50 - 60 Hz
how long the Power Supply Module will wait before reporting an AC
power failure to the control panel. The trouble and trouble restore will 13.8 Vdc ±5% when AC present
be generated after the AC fail delay of the module. Auxiliary Power Output 12.8 Vdc when on battery
8. Enter a three-digit decimal value (000 to 255 minutes). Default is set 2.5A max
30 minutes. Power Consumption
117 mA at 16.5 Vac
(without load)
Type of Power Supply Type A
Battery 12 Vdc, 7 Ah to 14 Ah
Low Battery 10.7 Vdc, battery disconnect at 9.5V
300 mA min to 1200 mA (redirect from
Charging
auxiliary if less than 2.5A)
-20 to +50 C
Operating Temperature

Humidity 95% maximum


Bus Supervision AC, Aux voltage, Battery
Dimensions (H x W x D) 5.6 x 14 x 2.5 cm (2.2 x 5.5 x 0.9 in.)
and Weight 0.1 kg (0.2 lbs.)
EN 50131-1, EN 50131-6, Grade 2 Class II
Certifications Certification Body: Applica Test and
Certification
* When AC power is disconnected and the power supply is operating on
battery, the Auxiliary Output is 12.8V ±16%
Warranty
For complete warranty information on this product, please refer to the Limited Warranty Statement is found on the website:
www.paradox.com/terms or contact your local distributor. Specifications may change without prior notice.
Patents
US, Canadian and international patents may apply. Paradox is a trademark or registered trademark of Paradox Security Systems (Bahamas) Ltd.
paradox.com PS25-EI02 06/2021