Project: Tag #:

Date: For: File Resubmit


PO No.: Approval Other
Architect: GC:
Engr: Mech:
Project Manager:

ARUV168BTE5 Multi V™5


Cooling Only 14 RT Outdoor Unit

Performance: Operating Range:


Cooling Mode: Cooling (˚C WB)** 14° ‐ 27°
Nominal Capacity (Btu/h) 168,000 Heating (˚C DB) ‐
Power Input¹ (kW) 12.39
Unit Data:
Heating Mode: Refrigerant Type R410A
Nominal Capacity (Btu/h) - Refrigerant Control EEV
Max Number of Indoor Units² 26
Power Input¹ (kW) -
Sound Pressure³ dB(A) 60.5
Nominal Capacity is outside the scope of AHRI Standard 1230 and based on the following conditions:
Indoor: 80°F DB / 67°F WB Indoor: 70°F DB Net Unit Weight (Kg) 263
Outdoor 95°F DB Outdoor 47°F DB / 43°F WB
: : Shipping Weight (Kg) -
Electrical:
Communication Cable⁴ (No x AWG) 2 x 18
Power Supply (V/Hz/Ø) 220/60/3
Heat Exchanger Coating Ocean Black Fin™
MFA (A) 60
Compressor:
MCA (A) 53.6
Type HSS SC Scroll
Rated Amps (A) 28.8
Quantity 1
Compressor A (A) 20.8
Compressor B (A) ‐ Oil/Type PVE/FVC68D

Fan (A) 8 Fan:

Piping: Type Propeller


Quantity 2
Refrigerant Charge (KG) 13.0
Motor/Drive DC Inverter
Liquid Line (in, OD) 5/8
Air Flow Rate (CFM) 11,301
Vapor Line (in, OD) 1 1/8
Notes:
Standard Features:
1.For AHRI ra ngs, refer to the AHRI website h p://www.ahridirectory.org.
•Advanced Smart Load Control •Fault Detec on and Diagnosis 2.For main pipe segment size, refer to the LATS Mul V tree diagram.
•Intelligent Heating •Active Refrigerant Control 3.The combina on ra o must be between 50‐130%.
4.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745 for the
•HiPOR (high pressure oil return) •Variable Path Heat Exchanger combination of outdoor units.
•Smart Oil Control •Subcooling and Vapor Injection 5.All communication cable to be minimum 18 American wire gage (AWG), 2‐conductor,
stranded, shielded or unshielded wire and must comply with applicable local and national
•Night Quiet Opera on Control code. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
•Liquid Cooled Inverter Controller 6.Nominal data is rated 0 above sea level, with 25 of refrigerant line per indoor unit and
Required Accessories: a 0 ft level difference between outdoor and indoor units. All capacities are net with a
combination ratio between 95‐105%.
ARCNB21 (frame connector Y‐branch) 7.Power wiring cable size must comply with the applicable local and na onal code. Cables
terminate at each frame.
ARCNB31 (frame connector Y‐branch)
8.Acceptable operating voltage: 187V ‐ 253V.
9.The order of each of these units on the submittal (i.e., a+b+c) do not represent the
Optional Accessories: installation order. Highest capacity unit is used as the Master, followed by the next
smaller size as Slave 1 and so on.
Air Guide ‐ ZAGDKA52A (3 required)
Hail Guard Kit ‐ ZHGDKA52A (3 Required)
Low Ambient Baffle Kit ‐ ZLABKA52A (3), Control Kit ‐ PRVC2 (1 per
system)
**(‐9.9°F achieved only when all IDU's are operating in cooling mode.
Does not impact synchronous operating range.)
LG Electronics Perú S.A. www.lg.com.pe / www.lgaircon.com
© LG Electronics PERÚ S.A., Av. República de Colombia 791 Piso 12 San Isidro / Lima - Perú

LGERP‐MultiV_IV_Cooling Only‐ARUV168BTE5_01-2018
Project:

GGGGn™ˆ› G—–•›
Outdoor Unit
ARUV168BTE5 Multi
V™5 Cooling Only 14 RT

LG Electronics Perú S.A. www.lg.com.pe / www.lgaircon.com


© LG Electronics PERÚ S.A., Av. República de Colombia 791 Piso 12 San Isidro / Lima - Perú
[mm(inch)]
System Cooling Only
Liquid Gas
RT
pipe pipe
12 Ø 12.7 (1/2) Ø 28.58 (1-1/8)
14~18 Ø 15.88 (5/8) Ø 28.58 (1-1/8)

20 Ø 15.88 (5/8) Ø 34.9 (1-3/8)

22~28 Ø 19.05 (3/4) Ø 34.9 (1-3/8)


30~48 Ø 19.05 (3/4) Ø 41.3 (1-5/8)
50~52 Ø 22.2 (7/8) Ø 44.5 (1-3/4)

54~80 Ø 22.2 (7/8) Ø 53.98 (2-1/8)


Tag #:

LGERP‐MultiV_IV_Cooling Only‐ARUV168BTE5_01-2018