Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

RiTherm Summary

Project: - Calculation: New calculation


Company: -
Contact person: -
Contact info: -

Ambient parameters

Minimum temperature outside the enclosure Ta 10 °C


Maximum temperature outside the enclosure Ta 35 °C
Maximum temperature inside the enclosure Ti 20 °C
Mains voltage 230 V
Frequency 50 Hz

Enclosure set: Set 1

Enclosure no. 1 Custom enclosure


Dimensions (W x H x D) 1,500 mm x 2,200 mm x 800 mm
K-Factor of the enclosure 5.5
Power dissipation 600 W

Climate control calculation

Average temperature without climate control 47.77 °C


Heat loss 600 W
Heat exchange across surface -705 W
Heat to be dissipated 1,305 W
Cooling solution for set is needed, but no device had been selected

1/1
Rittal can not assume any liability for the calculation, dimensioning and selection. 4/16/2024