Professional Documents
Culture Documents
2.1.5.7.3 - 1000481 GG 01 61 12 004
2.1.5.7.3 - 1000481 GG 01 61 12 004
Horn/Beacon Tags:
Black
RSHT-:
F01
1. 6010-HA/BA-7472
Red
Blue
2. 6015-HA/BA-7474
Flow Switch terminal adn Colour code
52
53
HSGP-:
11 - C - Black
12 - NC - Red
1. 8027-XA/Xb-0501
13 - NO - Blue
12
13
11
+ 03 NC NO
Input Power supply, 24V DC ¨C
From DCS room digital Output 24 VDC
- 04 F01 SPDT Flow Switch
NC connection to the DCS room, when the Shwer or Eye wash is activated the signal brakes
PE
Connection to be made as such when NC contact breaks from Flow switch to DCS room,
(i.e) when the Shower or eye was is activated
BH01
22
When signal from DCS room is on the beacon and hon is activated.
1
WIRING DIAGRAM FOR JUNCTION BOX
X01
Cabels coming from the DCS room to be connected dierectly to the Flow Switch
Black Black 51
11
Blue Blue 53
Signal to DCS room Digital Input 13 EKKS 3x1,5
W1018
Red Red 52
12
X02
Brown Brown 21
03
Blue Blue
04
EKK 3G2,5
W1015 BH01
Gr/Yl Gr/Yl 22
01 +
From DCS room Digital Output 24V DC
02 -
01 and 02 Digital Output from DCS room 0 10.11.20 ISSUED FOR CONSTRUCTION GA PK JKR