ABE47 No.7 Service Entrance

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

ABE 47 Electrical System Design for 1/15/2014

Biosystems Structures

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE ENTRANCE & LOAD CENTERS
B B
Electric service Overhead Electrical Service
E E
- the conductors and equipment that deliver
electrical power from the electric power  overhead service
4 utility’s distribution system to the customers 4 connection uses type
7 being served 7 SE(service entrance)
cable
 can be with or
Service entrance
without protective
- the interface between the overhead or
conduit
underground cable from the local transformer
where the power utility’s responsibility ends
and the building owner’s electrical system
and responsibility begin

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE ENTRANCE & LOAD CENTERS
B B
Overhead Electrical Service Overhead Electrical Service
E E

4 3 to 4
8kV
7 120/240V 7
Grounding of electrical
service is required by
PEC
Service equipment
(inside)

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE ENTRANCE & LOAD CENTERS
B B
Underground Electrical Service Underground Electrical Service
E E

4 4
7 7
Pad-mounted
transformer

 underground service connection uses type USE


(underground service entrance) cable
 grounding is the same with overhead electrical service

Asst. Prof. Mark Keylord S. Onal 1


ABE 47 Electrical System Design for 1/15/2014
Biosystems Structures

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE ENTRANCE & LOAD CENTERS
B B Type USE cable
Grounding electrode can be any of the following:
E E - contains three insulated conductors because
(1) Metal underground water pipe with at least 10 ft (3 m) the neutral/grounding conductor must be
in the earth; insulated
4 (2) Metal frame of the building where effectively grounded;
4
- has moisture-resistant covering
7 (3) Concrete-encased electrode (an electrode encased in at 7
least 2 in. (50 mm) of concrete, located within or near the (cross-linked polyethylene insulator)
bottom of a concrete foundation);
(4) Ground ring encircling the building in direct contact
with the earth, consisting of at least 20 ft (6 m) of bare
copper conductor;
(5) Rod and pipe electrodes not less than 8 ft (2.5 m); and
(6) Plate electrodes not less than 2 ft2 (0.186 m2) of
surface to exterior soil.

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE ENTRANCE & LOAD CENTERS
B B Watthour Meter Base
E E
Overhead Underground
4 overhead pad-mounted 4
7 transformer transformer 7

service drop service lateral

type SE cable type USE cable Overhead service to a meter base Underground service to a meter base

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE ENTRANCE & LOAD CENTERS
B Type SE cable
B
Load Center
E E
- contains two insulated wire and a bare grounding cable - accepts the service entrance wires from the meter
- has flame-retardant, moisture-resistant covering base and distribute power to branch circuits within
4 U-style SE 4 home or building
- contains 2 insulated conductors and a - used interchangeably with main service panel and
7 multistranded braid that encloses the two insulated 7 panel board
conductors
- has flame-retardant, moisture-resistant and sun-  Panelboards are metal enclosures for mounting
resistant jacket overcurrent-protective devices such as fuses and circuit
R-style SE breakers positioned upstream of all branch circuits in the
- contains three insulated conductors and a distribution of power within the building for lighting,
grounding wire appliance, and other loads
- conductors are wrapped in a glass-reinforced tape
and enclosed in a PVC jacket

Asst. Prof. Mark Keylord S. Onal 2


ABE 47 Electrical System Design for 1/15/2014
Biosystems Structures

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE SYSTEM


B B
Panelboards classification Single-Phase Service System
E E
 Lighting and appliance panelboard
4 - a panelboard having more than 10 percent of its 4
o Two-wire single-phase service system
7 circuits assigned to lighting and branch circuits that are 7
protected at 30A or less, for which neutral connections  120V
are provided  240V
o Three-wire three-phase service system
Power panelboard  120/240V
- a panelboard having 10 percent or fewer of its
circuit assigned to lighting and appliance branch circuits
that are protected at 30A or more, for which neutral
connections are provided

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE SYSTEM


B B
Loadcenter Enclosure Three-phase service system
E E
- can be flush-mounted within a wall or surface-
mounted on a wall Where large quantities of electrical power are being
4 4 transmitted or used, three-phase AC power is
 flush-mounted loadcenter
7 7 generally provided.
- recessed within an opening in a wall, usually
fastened between joists Three-phase currents are generated by an alternator
having three identical armature coils spaced 120°
 surface-mounted loadcenter
- fastened to the outside of the wall, usually concrete from each other.
or cinder block, with masonry anchor bolts
Two configurations:
1. Three-phase Delta
2. Three-phase Wye

A SERVICE ENTRANCE & LOAD CENTERS A SERVICE SYSTEM


B B
Loadcenter Enclosure Common Power Service System
E E

4 4
o Single-phase, three-wire, 120/240V
7 7
o Three-phase, four-wire, 120/240V wye
connected
o Three-phase, four-wire, 120/240V delta
connected
Main breaker – a heavy-duty circuit breaker that limits the
total amount of current entering the building; located at the
top of the load center

Asst. Prof. Mark Keylord S. Onal 3


ABE 47 Electrical System Design for 1/15/2014
Biosystems Structures

A
Building Service Equipment A
Building Service Equipment
B Building Service Equipment B Plug-type Fuse (ratings not more than 30A)
E E
Main function:
supply power to each of the branch circuits within
4 the building from the service conductors 4
7 7
Specific functions:
 Supply a main switch or disconnect means
 Supply overcurrent protection for branch circuits Cartridge-type fuse (ratings more than 30A)
 Supply terminals for attachment of branch circuit
conductors including equipment grounding
conductors
 Supply a point of connection to earth or ground
the system.

A
Building Service Equipment A
Building Service Equipment
B Panel Board B Circuit Breaker
E - use to house the overcurrent devices E - device designed to open a circuit
automatically at a predetermined
Overcurrent protective devices overload current without damage to itself.
4 - are installed in series with the hot 4
7 conductors and are designed to open the 7 Most circuit breakers are of the inverse time type
circuit if a specified current level is exceeded. and have a bimetallic strip connected with the
contacts.
1. Fuse
a. Non-time delay
b. Time Delay
2. Circuit Breaker
a. Instantaneous
b. Inverse time

A
Building Service Equipment A
Building Service Equipment
B Fuses B
E - overcurrent devices of which a portion is E
destroyed when interrupting the circuit.
- are made with low melting point links that Inverse-time
4 are calibrated to melt when a specified current 4
Circuit Breaker
7 is reached 7
Time-delay fuse
Current passes through the bimetallic strip causing it
- a dual-element fuse
to heat up. Since the two metals expand at different
• continuous overload
rates, the strip bends. If the current level is too high,
• short circuit
the bend will be large enough so that the contact
- allow higher temporary overcurrent during
points will open. After the element has cooled, the
motor starting
circuit breaker can be reset.

Asst. Prof. Mark Keylord S. Onal 4


ABE 47 Electrical System Design for 1/15/2014
Biosystems Structures

A
Building Service Equipment
B Instantaneous Circuit Breaker
E
It contains an electromagnet.

4 When a short circuit occurs, the electromagnet trips


7 the breaker much more rapidly than is possible with a
bimetallic strip.

Combination thermal-magnetic circuit breakers are


also available.

Some are adjusted to trip at various values of current,


time, or both.

A
Building Service Equipment
B The standard ampere ratings for fuses and
E inverse-time circuit breakers are:

4 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90,
100, 110, 125, 150, 175, 200, 225, 250, 300,
7 350, 400, 450, 500, 600, 700, 800, 1000,
1200, 1600, 2000, 2500, 3000, 4000, 5000
and 6000 amperes

(Source: PEC 2000, Part 1 Article 2.40.1.6)

Asst. Prof. Mark Keylord S. Onal 5

You might also like