ELECTRICAL DRAWINGS
ROMO/24-6-VOL
TH-1037
TECHNICAL
DOCUMENTATION
ROMO/24-6-VOL
TH-1037
INPUT EXPLANATIONS FOR ARMA SOAP & DETERGENT
ROMO/24-6-VOL (TH-06-15-1037)
1
INPUT CARD 3 X20DI9371
I:3/1 PB1 Machine Cycle Interrupt (Main & Rem. Panel)
I:3/2 PB2 Machine Inching (Rem. Panel)
I:3/3 PB3 Screen Calibration (Inside Main)
I:3/4 PB4 Filling Conveyor Start – Stop (Main)
I:3/5 PB5 Machine Start – Stop (Main)
I:3/6 PB6 Caps Belt Conveyor Start – Stop (Rem. Panel)
I:3/7 PB7 Caps Feeder Start - Stop (Rem.)
I:3/8
I:3/9
I:3/10
I:3/11
I:3/12
2
INPUT CARD 5 X20DI9371
O:5/1 LS51 Filling Main Motor AC Drive Faulted
O:5/2 LS52 Filling Conveyor AC Drive Faulted
O:5/3 LS53 Caps Feeder AC Drive Faulted
O:5/4 LS54 Volumetric Motor AC Drive Faulted
O:5/5
O:5/6 LS56 Filling Cam Secured (Front Piston)
O:5/7 LS57 Filling Cam Secured (Back Piston)
O:5/8
O:5/9
O:5/10 LS510 Tank is Low
O:5/11 LS511 Tank is Empty
O:5/12 LS512 Tank is Full
3
OUTPUT EXPLANATIONS FOR ARMA SOAP & DETERGENT
ROMO/24-6-VOL (TH-06-15-1037)
4
OUTPUT CARD 8 X20DO9322
O:8/1 LIGHT1 Machine on Auto Mode
O:8/2 LIGHT2 Caps Feeder on Auto Mode
O:8/3 LIGHT3 Caps Belt Conveyor is Running
O:8/4
O:8/5
O:8/6
O:8/7
O:8/8 SV88 Filling Cam Secured
O:8/9 SV89 Cap Release For Capping
O:8/10 SV810 Caps Feeder Air Valve Open
O:8/11 SV811 Rotary Valve Open
O:8/12 SV812 Hopper Valve Open
5
PARAMETERS EXPLANATION FOR ARMA SOAP ROMO/24-6-VOL
(TH-06-15-1037)
PARAMETER PARAMETER
PARAMETER PURPOSE
NUMBER VALUE
N:0 FUTURE USE 0
COUNTER COUNTER
COUNTER PURPOSE
NUMBER VALUE
C:0 0 FUTURE USE
1
TIMERS EXPLANATION FOR ARMA SOAP
ROMO/24-6-VOL (TH-06-15-1037)
TIMER TIMER
TIMER PURPOSE
NUMBER VALUE (ms)
T: 0 0 FUTURE USE
1
TIMERS EXPLANATION FOR ARMA SOAP
ROMO/24-6-VOL (TH-06-15-1037)
TIMER TIMER
TIMER PURPOSE
NUMBER VALUE (ms)
T: 29 0 FUTURE USE
2
AC DRIVES PARAMETER / ARMA SOAP ROMO 24-6 VOL (TH-06-15-1037)
(B&R 8174T )
MAIN FILLING CAPS
PARAMETER DESCRIPTION
MOTOR CONVEYOR FEEDER
COnF ->FULL-> SIM- ([CONFIGURATION]-> [FULL]-> [SIMPLY START])
nPr [Rated motor power] (kW) 5.5 0.37 0.37
UnS [Rated motor voltage] (v) 400 400 400
nCr [Rated motor current] (A) 11.1 1.1 1.1
COnF ->FULL-> SEt- ([CONFIGURATION]-> [FULL]-> [SETTINGS])
Inr [Ramp Increment] 0.1 0.1 0.1
ACC [Acceleration] (s) 3 0.5 0.5
dEC [Deceleration] (s) 0.7 0.5 0.5
LSP [Low Speed] (Hz) 10 20 10
HSP [High Speed] (Hz) 52 65 40
ItH [Mot. Therm. Current] (A) 11.1 1.2 1.2
*SdC1 [Auto DC injection level 1](A) 5.5 1.6 1.6
tdC1 [Auto DC injection time 1] (s) 0.5 0.5 0.5
CLI [Current Limitation] (A) 11.1 1.9 1.9
*JGF [Jog Frequency] (Hz) NO NO NO
JGt [Jog Delay] (s) NO NO NO
*SP2 [Preset Speed 2] (Hz) NO NO NO
COnF ->FULL-> drC- ([CONFIGURATION]-> [FULL]-> [MOTOR CONTROL])
[Standard motor frequency]
50Hz 50Hz 50Hz
BFr(50) IEC
tFr [Max Frequency] (Hz) 60 70 60
COnF-> FULL-> I_O- ([CONFIGURATION]-> [FULL]-> [INPUTS / OUTPUTS CFG])
tCC [2/3 wire type] (2C/3C) (2C) Selected (2C) Selected (2C) Selected
Frd-> L11
[Forward]->[LI1] Logical input of forward Selected Selected Selected
bSP-> bSd
[Reference Template]-> [Standard] Selected Selected Selected
A11- [AI1 CONFIGURATION]
A11t [AI1 Type] Voltage Voltage Voltage
U1L1 [AI1 min value] (v) 0 0 0
U1H1 [AI1 max value] (v) 10 10 10
A01- [AO1 CONFIGURATION]
(UOp)Motor (OFr) Motor
A01 [A01 ASSIGNMENT] NO
Voltage Frequency
A01t [A01 TYPE] (I0U)Voltage (I0U) Voltage
Current
UOL1 [A01 min OUTPUT] (v) 0 0 0
UOH1 [A01 max OUTPUT] (v) 10 20 10
ASL1 [Scaling A01 min] (%) 15 0100
ASH1 [Scaling A01 max] (%) 60 100100
*SP2 - TO ENABLE/DISABLE PRESET SPEED GO CONFIGURATION->FULL->APPLICATION
FUNCTION-> PRESET SPEEDS (COnF ->FULL ->Fun ->PSS)
1
VOLUME
PARAMETER DESCRIPTION ADJUSTING
MOTOR
COnF ->FULL-> SIM- ([CONFIGURATION]-> [FULL]-> [SIMPLY START])
nPr [Rated motor power] (kW) 0.75
UnS [Rated motor voltage] (v) 400
nCr [Rated motor current] (A) 2
COnF ->FULL-> SEt- ([CONFIGURATION]-> [FULL]-> [SETTINGS])
Inr [Ramp Increment] 0.1
ACC [Acceleration] (s) 0.5
dEC [Deceleration] (s) 0.5
LSP [Low Speed] (Hz) 20
HSP [High Speed] (Hz) 100
ItH [Mot. Therm. Current] (A) 2
*SdC1 [Auto DC injection level 1](A) 1.6
tdC1 [Auto DC injection time 1] (s) 0.5
CLI [Current Limitation] (A) 3.4
*JGF [Jog Frequency] (Hz) NO
JGt [Jog Delay] (s) NO
*SP2 [Preset Speed 2] (Hz) NO
COnF ->FULL-> drC- ([CONFIGURATION]-> [FULL]-> [MOTOR CONTROL])
[Standard motor frequency]
50Hz
BFr(50) IEC
tFr [Max Frequency] (Hz) 100
COnF-> FULL-> I_O- ([CONFIGURATION]-> [FULL]-> [INPUTS / OUTPUTS CFG])
tCC [2/3 wire type] (2C/3C) (2C) Selected
Frd-> L11
[Forward]->[LI1] Logical input of forward Selected
bSP-> bSd
[Reference Template]-> [Standard] Selected
A11- [AI1 CONFIGURATION]
A11t [AI1 Type] Voltage
U1L1 [AI1 min value] (v) 0
U1H1 [AI1 max value] (v) 10
A01- [AO1 CONFIGURATION]
A01 [A01 ASSIGNMENT] (UOp) NO
A01t [A01 TYPE] (I0U)Current
UOL1 [A01 min OUTPUT] (v) 0
UOH1 [A01 max OUTPUT] (v) 20
ASL1 [Scaling A01 min] (%) 0
ASH1 [Scaling A01 max] (%) 100