1 Kva 45 Min

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

11/7/23, 2:35 PM sizing.sunlight.gr/cgi-bin/exec_sizing.

cgi

BATTERY SIZING REPORT

Project ID: 1 kva 45 min Full Sizing


Username: thomas@gpeskw.com Calculation Mode: Power
Date: 2023-11-07, 13:35:26 Software Version: 1.0.1

PRE-SELECTION
Battery Range: SPA
Charging Voltage: Float
Max Number of Parallel Strings: 4

USER INPUTS
Discharge Time [min]: 45.0
Pre-set No of Cells Factors
Max no of cells: 36 Temperature [C]: 25.0
Min no of cells: 36 Temperature factor: 1.000
Final voltage (Vpc) [V]: 1.8 Aging factor: 1.0
Voltage range [V]: 64.80 - 81.72 Margin factor: 1.0
Total factor: 1.000
Apparent Power [kVA]: Power [kW]: 1.0
Cosphi: Battery Power [kW]: 1.042
Efficiency [%]: 96.0 Battery Power (with factors) [kW]: 1.042

OUTPUT

Optimal Battery Sizing: Based on Capacity


Battery Range SPA Number of Cells 36 Vpc [V] 1.8

Battery Model SPA 12-9 Blocks per string 6 Voltage Range [V] 64.80 - 81.72
(6.3mm)
SAP Reference 0313157 Parallel Strings 3 T exploitation 66.85%
Total Blocks 18 E exploitation 74.47%

There are variations in the SAP codes based on different characteristics of the batteries. SAP codes are subject to updates by Sunlight Group.
Please contact Sunlight Group for the correct SAP codes before proceeding to order.

Thank you for choosing Sunlight

https://sizing.sunlight.gr/cgi-bin/exec_sizing.cgi 1/2
11/7/23, 2:35 PM sizing.sunlight.gr/cgi-bin/exec_sizing.cgi

https://sizing.sunlight.gr/cgi-bin/exec_sizing.cgi 2/2