Guard Lock Safety-door Switch/D4SL-N-mounting Slide Key

D4SL-N / D4SL-NSK10-LK@
Varied lineup of Guard Lock Safety-door
Switches
<Guard Lock Safety-door Switch D4SL-N>
• Wiring time is reduced with two types of wiring Guard Lock Safety-door Switch
methods capable of one-touch attachment and
removal.
• A wide variety of built-in switches can be used for
various devices.
(4-, 5-, and 6-contact models are available)
• Key holding force of 1,300 N.
• It is possible to change the operation key insertion
point without detaching the head.
• Drive solenoids directly from the Controller.
Slide Key
<Slide Key D4SL-NSK10-LK@> Terminal
Connector Type
Block Type
• Lockout key to prevent workers from becoming
trapped inside the hazardous area. For the most recent information on models that have been certified for
• The vertical D4SL-N Guard Lock Safety-door safety standards, refer to your OMRON website.

Switch can be easily mounted on 40 × 40 mm


aluminum frames.
• The plastic material makes the Slide Key suitable
for lightweight doors.

Be sure to read the “Safety Precautions”


on page 22.

Scan the 2D codes using the smartphone to see the D4SL-N promotional videos.
Reduction in time and effort Safe access application

1
D4SL-N / D4SL-NSK10-LK@
Model Number Structure
Model Number Legend
Switch (Standard type)

D4SL-N @@@@-@
(1) (2) (3) (4)
@@
(5) (6) (7)

(1) Conduit Outlet (4) Door Lock and Release


Contact Model Conduit Outlet Contact Model Door Lock and Release
4-contact Model 2: G1/2 4-contact Model
A: Mechanical lock/24VDC solenoid release
5-contact Model Common 3: 1/2-14NPT *1 5-contact Model Common
G: 24VDC solenoid lock/mechanical release
6-contact Model 4: M20 6-contact Model

(2) Built-in Switch (5) Indicator


Contact Model Built-in Switch Contact Model Indicator
Door monitor and Lock monitor are connected in series 4-contact Model −: None
internally.
5-contact Model Common
A: 1NC/1NO + 1NC/1NO D: 24VDC (orange LED indicator)
6-contact Model
B: 1NC/1NO + 2NC
C: 2NC + 1NC/1NO
D: 2NC + 2NC (6) Release Key Type
4-contact Model
Door monitor and Lock monitor are NOT connected in Contact Model Release Key Type
series internally.
S: 1NC/1NO + 1NC/1NO 4-contact Model −: Standard release key (metal)
T: 1NC/1NO + 2NC −: Standard release key (metal)
U: 2NC + 1NC/1NO 5-contact Model Common
4: Special release key (resin)
V: 2NC + 2NC 6-contact Model
(Note:Release keys are provided.)
E: 2NC/1NO + 1NC/1NO
5-contact Model
F: 2NC/1NO + 2NC (7) Connection Method
G: 3NC + 1NC/1NO
H: 3NC + 2NC Contact Model Connection Method
N: 2NC/1NO + 2NC/1NO 4-contact Model
−: Terminal block
P: 2NC/1NO + 3NC 5-contact Model Common
6-contact Model N: Connector *2
Q: 3NC + 2NC/1NO 6-contact Model
R: 3NC + 3NC

(3) Head Material


Contact Model Head Material
4-contact Model F: Resin
5-contact Model Common F: Resin
6-contact Model D: Metal

*1. 1/2-14NPT models (conduit outlet: M20) will come with an M20-to-1/2-14NPT conversion adapter.
*2. Connector cables are not included with the connector type and are to be purchased separately.

Operation Key

D4SL-N K@@
(1) (2)

(1) Operation Key Type (2) Key Type


1: Horizontal mounting −: No cushion rubber
2: Vertical mounting G: Cushion rubber
3: Adjustable mounting (horizontal) S: No cushion rubber, short type
5: Adjustable mounting (horizontal/vertical)

Slide Key
D4SL-NSK10-LK@-@
(1) (2)

(1) Inner Lever (2) Lockout key Type


Blank: No inner lever Lockout key can be created up to 30 types.
H: With inner lever Specify keys in order starting from 01.
Blank: 01
02 to 30: 02 to 30

2
D4SL-N / D4SL-NSK10-LK@
Ordering Information
List of Models
Contact configuration Conduit
Release Wiring Solenoid voltage/ Lock and
(door open/closed detection switch outlet Model
key type method Indicator release type
and lock monitor switch contacts) (See Note.)
6-contact Model G1/2 D4SL-N2@FA-DN
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-DN
into the blank @. M20 D4SL-N4@FA-DN
24VDC
(Orange) G1/2 D4SL-N2@FA-DN
5-contact Model
Connector Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-DN
into the blank @. M20 D4SL-N4@FA-DN

4-contact Model G1/2 D4SL-N2@FA-N


24VDC
Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FA-N
(without indicator)
T, U or V) into the blank @. M20 D4SL-N4@FA-N
Mechanical lock
Solenoid release G1/2 D4SL-N2@FA-D
6-contact Model
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-D
into the blank @. M20 D4SL-N4@FA-D
24VDC
(Orange) G1/2 D4SL-N2@FA-D
5-contact Model
Terminal
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-D
block
into the blank @. M20 D4SL-N4@FA-D
4-contact Model G1/2 D4SL-N2@FA
Standard 24VDC
(metal) Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FA
(without indicator)
T, U or V) into the blank @. M20 D4SL-N4@FA

6-contact Model G1/2 D4SL-N2@FG-DN


Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-DN
into the blank @. M20 D4SL-N4@FG-DN
24VDC
(Orange) G1/2 D4SL-N2@FG-DN
5-contact Model
Connector Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-DN
into the blank @. M20 D4SL-N4@FG-DN

4-contact Model G1/2 D4SL-N2@FG-N


24VDC
Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FG-N
(without indicator)
Solenoid lock T, U or V) into the blank @. M20 D4SL-N4@FG-N
Mechanical
release 6-contact Model G1/2 D4SL-N2@FG-D
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-D
into the blank @. M20 D4SL-N4@FG-D
24VDC
(Orange) G1/2 D4SL-N2@FG-D
5-contact Model
Terminal
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-D
block
into the blank @. M20 D4SL-N4@FG-D

4-contact Model G1/2 D4SL-N2@FG


24VDC
Insert the built-in switch (A, B, C, D, S, 1/2-14NPT D4SL-N3@FG
(without indicator)
T, U or V) into the blank @. M20 D4SL-N4@FG
Note: The recommended models for equipment and machinery being exported to Europe are those with an M20 conduit outlet, and for North
America, the recommended models are those with a 1/2-14NPT conduit outlet.

3
D4SL-N / D4SL-NSK10-LK@

Contact configuration Conduit


Release Wiring Solenoid voltage/ Lock and
(door open/closed detection switch outlet Model
key type method Indicator release type
and lock monitor switch contacts) (See Note.)

6-contact Model G1/2 D4SL-N2@FA-D4N


Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-D4N
into the blank @. M20 D4SL-N4@FA-D4N
Connector
5-contact Model G1/2 D4SL-N2@FA-D4N
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-D4N
into the blank @. M20 D4SL-N4@FA-D4N
Mechanical lock
Solenoid release G1/2 D4SL-N2@FA-D4
6-contact Model
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FA-D4
into the blank @. M20 D4SL-N4@FA-D4
Terminal
block G1/2 D4SL-N2@FA-D4
Special 5-contact Model
(resin) Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FA-D4
into the blank @. M20 D4SL-N4@FA-D4
24VDC
(Orange) G1/2 D4SL-N2@FG-D4N
6-contact Model
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-D4N
into the blank @. M20 D4SL-N4@FG-D4N
Connector
5-contact Model G1/2 D4SL-N2@FG-D4N
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-D4N
Solenoid lock into the blank @. M20 D4SL-N4@FG-D4N
Mechanical
release 6-contact Model G1/2 D4SL-N2@FG-D4
Insert the built-in switch (N, P, Q or R) 1/2-14NPT D4SL-N3@FG-D4
into the blank @. M20 D4SL-N4@FG-D4
Terminal
block G1/2 D4SL-N2@FG-D4
5-contact Model
Insert the built-in switch (E, F, G or H) 1/2-14NPT D4SL-N3@FG-D4
into the blank @. M20 D4SL-N4@FG-D4
Note: The recommended models for equipment and machinery being exported to Europe are those with an M20 conduit outlet, and for North
America, the recommended models are those with a 1/2-14NPT conduit outlet.

4
D4SL-N / D4SL-NSK10-LK@

Operation Keys
Type Model

Horizontal mounting D4SL-NK1

Horizontal mounting
(Short) D4SL-NK1S

Horizontal mounting
D4SL-NK1G
(Cushion rubber)

Vertical mounting D4SL-NK2

Vertical mounting
D4SL-NK2G
(Cushion rubber)

Adjustable
D4SL-NK3
(Horizontal)

Adjustable
D4SL-NK5
(Horizontal/Vertical)

Connector Cables
Cable length Model
1m D4SL-CN1
3m D4SL-CN3
5m D4SL-CN5
10 m D4SL-CN10

5
D4SL-N / D4SL-NSK10-LK@

Slide Key
Type Specifications Contents Model

Slide Key: 1 (not yet mounted)


Inner Lever: None D4SL-NSK10-LK *1
D4SL-N mounting plate: 1
Door Switch special mounting screws: 3
Weight: Approx. 0.6 kg
D4SL-NK1 (operation key): 1
Mechanical durability:
D4SL-NK1 special mounting screws: 2
20,000 operations min.
Lockout keys: 2
Lockout key strap: 1
Caution labels (stickers): 2 sheets D4SL-NSK10-LK-@ *2
(English and Japanese)

Weight: Approx. 0.1 kg Inner Lever: 1 D4SL-SK10H *3

Slide Key: 1 (not yet mounted)


Inner Lever: 1 D4SL-NSK10-LKH *1
D4SL-N mounting plate: 1
Door Switch special mounting screws: 3
Weight: Approx. 0.7 kg
D4SL-NK1 (operation key): 1
Mechanical durability:
D4SL-NK1 special mounting screws: 2
20,000 operations min.
Lockout keys: 2
Lockout key strap: 1
Caution labels (stickers): 2 sheets D4SL-NSK10-LKH-@ *2
(English and Japanese)

Note: 1. The Door Switch is not included. Select the Door Switch depending on the necessary number of contacts and the conduit outlet.
The contents are provided as a total set, individual contents cannot be ordered separately.
2. Perform risk assessment for the equipment in question, configure relay units and other safety circuits, and use properly.
*1. The number for the lockout key is 01.
*2. Replace the box with 02 to 30 (lockout key number). Ask your OMRON representative for delivery times.
*3. The inner lever for D4SL-NSK10 that can not be used for other products and applications.

Applicable Door Switches


D4SL-NSK10-LK

+ =

D4SL-NSK10-LK D4SL-N

D4SL-NSK10-LKH

+ =

D4SL-NSK10-LKH D4SL-N

6
D4SL-N / D4SL-NSK10-LK@
Features
The lockout key prevents workers from becoming trapped without using a padlock.
Note: Using LEDs of D4SL-N enables confirming whether the door is open or closed and locked or unlocked.

Close door
Locked (power not supplied to
solenoid) The slide handle is closed.

The handle-shaped fixture makes


it easy to use the Door Switch.

CAUTION
Lockout key Guard Lock Safety-door
Switch will not be unlocked
with Lockout Key.
Lockout Key may be damaged
by operating Lockout Key
when the door is closed.
Always carry lockout key
when entering the Hazardous
area.

Close door
No. 7467139-3A

Attach the supplied


Unlocked (power supplied to solenoid) caution labels for display.
The slide handle is closed.

Left door
Lockout Key Door Opening to the Left.

The slide handle can be pulled. Do not turn the key as in the figure above if the
slide handle is closed.

Open door Open door Open door


The slide handle is open. The slide handle is open. The slide handle is open.
The slide handle
does not move.

When the slide handle is open, the The slide handle is secured at the position If the lockout key is not mounted, the
lockout key can be pulled regardless of shown in the figure. slide handle will not move and the
whether power is being supplied to the A worker holding the lockout key will not be door will not close.
solenoid or not. trapped locked inside the hazardous area by
another person.

7
D4SL-N / D4SL-NSK10-LK@
Structure and Nomenclature
Structure
D4SL-N@@@@-D@N Connector Type D4SL-@@@@-D@ Terminal Block Type
Two operation key holes Two operation key holes

Can be mounted
Can be mounted from four directions.
from four directions.
4.5 dia. * 4.5 dia. *

The switch has an The switch has an


indicator on the back indicator on the back
The switch has of the switch as well. The switch has of the switch as well.
a release key a release key
on the back of on the back of * You can insert and secure a stud or
the switch as well. the switch as well. other projection in the 4.5-dia. hole to
make the installation even stronger.
For details, refer to “Switch and
Operation Key Mounting” on page 24.

Terminal Arrengement
Connector/Terminal
for D4SL-N@N@@-D@
9 E1 (+)

10 E2 (−)
4.5 dia. * 4.5 dia. *
2 42 41 12 11 1
<LED> 4 52 51 22 21 3
ORANGE
8 64 63 34 33 5

7 6

1 2 3 4 5 6 10
Note: Numbers inside the boxes are terminal
Notched side is No. 1 numbers printed on the product.
1 3 5 7 9
2 4 6 8 10

8
D4SL-N / D4SL-NSK10-LK@

Operating Cycle Examples for Standard Models


D4SL-N@@@A-@ (Mechanical Lock Models)
Door condition Turning the special
Condition 1 Condition 2 Condition 3
release key

Return to
condition 1
Door open. Door closed. Door closed. Door closed.
The door will lock The door is locked. The door can be No power is supplied
when the door closes. opened. to the solenoid.
Terminal No. and The door is unlocked
Contact No. Function manually.
9 E1- 10 E2 Solenoid ON
2 42- 1 11 (NC) Door open/closed detection
4 52- 3 21 (NC) and lock monitor contacts
3 21- 4 22 (NC) Door open/closed detection
5 31- 6 32 (NC) contact

5 33- 6 34 (NO) Door open/closed detection


contact
1 41- 2 42 (NC)
Lock monitor contact
7 61- 8 62 (NC)
7 63- 8 64 (NO) Lock monitor contact

D4SL-N@@@G-@ (Solenoid Lock Models)


Door condition Even when the door
is closed, it does not Door closed.
Door closed.
lock until power is The door can be
The door is locked.
Terminal No. and supplied to the opened.
Contact No. Function solenoid.
9 E1- 10 E2 Solenoid ON
2 42- 1 11 (NC) Door open/closed detection
4 52- 3 21 (NC) and lock monitor contacts
3 21- 4 22 (NC) Door open/closed detection
5 31- 6 32 (NC) contact

5 33- 6 34 (NO)
Door open/closed detection
contact
The shaded areas indicate
1 41- 2 42 (NC) the contact is closed and
Lock monitor contact
7 61- 8 62 (NC) power is supplied to the
7 63- 8 64 (NO) Lock monitor contact solenoid.

Door open/closed detection and lock monitor contacts: Can be used in safety circuits because of the direct opening mechanisms.
Door open/closed detection contact: Can be used to confirm whether the key is inserted and to monitor the open/closed status of a door.
Lock monitor contact: Can be used to confirm whether power is supplied to the solenoid and to monitor whether or not a door can be opened or closed.
Note: 1. The door open/closed detection and lock monitor contact configuration depends on the model.
2. For solenoid lock models, be sure to supply power to the solenoid after the door is closed (after the operation key is inserted).
If the door is closed after power is supplied to the solenoid, locking the operation key may not be possible.
For details, refer to “Solenoid Lock Models” on page 23.

9
D4SL-N / D4SL-NSK10-LK@
Specifications
Standards and EC Directives
Conforms to the following EC Directives:
• Machinery Directive
• Low Voltage Directive
• EMC Directive
• EN ISO 14119
• EN60947-5-1
• GS-ET-19

Certified Standards
Certification body Standard File No.
TÜV SÜD EN60947-5-1(certified direct opening) Consult your OMRON representative for details.
UL *1 UL508, CSA C22.2 No.14 E76675
CQC (CCC) GB/T 14048.5 Consult your OMRON representative for details.
KOSHA *2 EN60947-5-1 Consult your OMRON representative for details.
*1. Certification has been obtained for UL CSA C22.2 No. 14.
*2. Only certain models have been certified.

Certified Standard Ratings


TÜV (EN60947-5-1) CCC (GB/T 14048.5)
Utilization category AC-15 DC-13
1.5 A *1
Rated operating current (Ie) 0.22 A
1 A *2
Rated operating voltage (Ue) 120 V 125 V
Note: Use a 4 A fuse that conforms to IEC60127 as a short-circuit protection device. This fuse is not included with the switch.
*1. 11-42, 21-52, 21-22
*2. Other terminals

UL/CSA (UL508, CSA C22.2 No.14)


C150
Current (A) Volt-amperes (VA)
Rated voltage Carry current
Make Break Make Break
120 VAC 2.5 A 15 1.5 1,800 180

R150
Current (A) Volt-amperes (VA)
Rated voltage Carry current
Make Break Make Break
125 VDC 1.0 A 0.22 0.22 28 28

Solenoid Coil Characteristics


Item 24 VDC
Rated operating voltage (100% ED) 24 VDC +10%
−15%
Power ON:
6-contact type Approx. 6.4 W at 0.26 A
Current consumption *
4-contact/5-contact type Approx. 4.8 W at 0.2 A
Constant: Approx. 2.6 W (average) at 0.2 A (max.)
Insulation Class E (to 120°C)
* A starting current is applied to the solenoid for Approx. 10 seconds.
After this, the internal circuit switches to a constant current.
Note: For solenoid lock models, be sure to supply power to the solenoid after the door is closed (after the operation key is inserted).
If the door is closed after power is supplied to the solenoid, locking the operation key may not be possible.
For details, refer to “Solenoid Lock Models” on page 23.

Indicator
Item LED type
Rated voltage 24 VDC
Current consumption Approx.10 mA
Color (LED) Orange

10
D4SL-N / D4SL-NSK10-LK@

Characteristics
Interlock type Type 2 (EN ISO 14119)
Coding level Low level coded (EN ISO 14119)
IP67 *1
Degree of protection
TYPE 4X Indoor use only (UL, CSA)
Mechanical 1,000,000 operations min.
Durability *2
Electrical 150,000 operations min. (1 A resistance at 125 VAC) *3
Operating speed 0.05 to 1 m/s
4- and 5-contact Model: 30 operations minute max.
Operating frequency
6-contact Model: 5 operations minute max.
Direct opening force *4 60 N min. (EN60947-5-1)
Direct opening travel *4 15 mm min. (EN60947-5-1)
Holding force (Fzh) *5 1,300 N min.
Contact resistance 200 mΩ max.
Minimum applicable load *6 1 mA resistive load at 5 VDC (N-level reference value)
Rated insulation voltage (Ui) 150 V (EN60947-5-1)
Rated frequency 50/60 Hz

Protection against electric shock Class II (double insulation)

Pollution degree (operating environment) 3 (EN60947-5-1)

Impulse Between terminals of same polarity 1.5 kV


withstand voltage Between terminals of different polarity 1.5 kV
(Uimp) Between other terminals and
(EN60947-5-1) 2.5 kV
non-current carrying metallic parts
Insulation resistance 100 Ω min. (at 500 VDC)
Vibration resistance Malfunction 10 to 55 Hz, 0.35 mm single amplitude
Malfunction 80 m/s2 min.
Shock resistance
Destruction 1,000 m/s2 min.
Conditional short-circuit current 100 A (EN60947-5-1)
2.5A (11-42, 21-52, 21-22)
Conventional free air thermal current (Ith)
1A (Others)
Ambient operating temperature −10 to 55°C (with no icing)
Ambient operations humidity 95% max.
Head: Resin
Approx. 290 g (Connector model)
Approx. 330 g (Terminal block model)
Weight
Head: Metal
Approx. 370 g (Connector model)
Approx. 410 g (Terminal block model)
Note: 1. The above values are initial values.
2. The Switch contacts can be used with either standard loads or microloads.
Once the contacts have been used to switch a load, however, they cannot be used to switch smaller loads.
The contact surfaces will become rough once they have been used and contact reliability for smaller loads may be reduced.
*1. The degree of protection is tested using the method specified by the standard (EN60947-5-1).
Confirm that sealing properties are sufficient for the operating conditions and environment beforehand.
Although the switch box is protected from dust, oil or water penetration, do not use the D4SL in places where cutting chips, oil, water or
chemicals may enter through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
*2. The durability is for an ambient temperature of 5 to 35°C and an ambient humidity of 40% to 70%. For more details, consult your OMRON
representative.
*3. Do not pass the 1 A, 125 VAC load through more than 3 circuits.
*4. These figures are minimum requirements for safe operation.
*5. This figure is based on the ISO 14119 evaluation method.
*6. This value will vary with the switching frequency, environment, and reliability level.
Confirm that correct operation is possible with the actual load beforehand.

11
D4SL-N / D4SL-NSK10-LK@
Connection
Internal Circuit Diagram
Without indicator With indicator
24VDC D 24VDC D
9 E1 (+) 9 E1 (+)

R
Control Control
ZD D ZD D
circuit circuit
LED
10 E2 (−) 10 E2 (−)

Note: The numbers in boxes are the terminal numbers given on the Switch.

12
D4SL-N / D4SL-NSK10-LK@

Model and Contact Configuration


Indicates conditions where the Key is inserted and the lock is applied.
Contact Contact Form
(door open/ Door open/
Model Lock Operating pattern Remarks
closed detection closed
and lock monitor) monitor
detection

Door open/closed
Lock monitor detection
Lock position Only NC contacts 11-12 have a
2 1
42-11 certified direct opening
42 41 12 11
1NC/1NO+ 34-33 On mechanism.
D4SL-N@A@@-@
1NC/1NO 64-63 The terminals 42-11, 34-33, and
8 5
64 63 34 33 Stroke 64-63 can be used as unlike
7 6 Operation Key Insertion Extraction poles.
completion position completion position

Door open/closed Lock position


Lock monitor detection
Only NC contacts 11-12 have a
2 1 42-11 certified direct opening
42 41 12 11
34-33 On mechanism.
D4SL-N@B@@-@ 1NC/1NO+2NC 62-61 The terminals 42-11, 34-33, and
8 5
62 61 34 33 Stroke 62-61 can be used as unlike
Operation Key Insertion Extraction
7 6
completion position completion position
poles.

Door open/closed Lock position


Lock monitor detection Only NC contacts 11-12 and 31-
2 1 42-11 32 have a certified direct opening
42 41 12 11
32-31 On mechanism.
D4SL-N@C@@-@ 2NC+1NC/1NO 64-63 The terminals 42-11, 32-31, and
8 5
64 63 32 31
Stroke 64-63 can be used as unlike
Operation Key Insertion Extraction
7 6 completion position completion position
poles.

Door open/closed Lock position


Lock monitor detection Only NC contacts 11-12 and 31-
2 1 42-11 32 have a certified direct opening
42 41 12 11
32-31 On mechanism.
D4SL-N@D@@-@ 2NC+2NC 62-61 The terminals 42-11, 32-31, and
8 5
62 61 32 31
Stroke 62-61 can be used as unlike
Operation Key Insertion Extraction
7 6 completion position completion position
poles.

Lock position
Door open/closed
Lock monitor detection Only NC contacts 21-22 have a
42-41
2 1 certified direct opening
42 41 22-21
1NC/1NO+ On mechanism.
D4SL-N@S@@-@ 4 3 34-33
1NC/1NO 22 21 64-63
The terminals 42-41, 22-21, 34-
8
64 63 34 33
33, and 64-63 can be used as
Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 21-22 have a
42-41
2 1 certified direct opening
42 41 22-21
On mechanism.
D4SL-N@T@@-@ 1NC/1NO+2NC 4 3 34-33
22 21 62-61
The terminals 42-41, 22-21, 34-
8
62 61 34 33
33, and 62-61 can be used as
Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 21-22 and 31-
42-41
2 1 32 have a certified direct opening
42 41 22-21
On mechanism.
D4SL-N@U@@-@ 2NC+1NC/1NO 4 3 32-31
22 21 64-63
The terminals 42-41, 22-21, 32-
8
31, and 64-63 can be used as
64 63 32 31 Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 21-22 and 31-
42-41
2 1 32 have a certified direct opening
42 41 22-21
On mechanism.
D4SL-N@V@@-@ 2NC+2NC 4 3 32-31
22 21 62-61
The terminals 42-41, 22-21, 32-
8
31, and 62-61 can be used as
62 61 32 31 Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

13
D4SL-N / D4SL-NSK10-LK@

Contact Contact Form


(door open/ Door open/
Model Lock Operating pattern Remarks
closed detection closed
and lock monitor) monitor
detection
Lock position
Door open/closed
Lock monitor detection Only NC contacts 11-12 and 21-
42-11
2 1 22 have a certified direct opening
42 41 12 11 22-21
D4SL-N@E@@-@ 2NC/1NO+ 34-33
On mechanism.
4 3
1NC/1NO 22 21 64-63
The terminals 42-11, 22-21, 34-
8
33, and 64-63 can be used as
64 63 34 33 Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection
Only NC contacts 11-12 and 21-
42-11
2 1 22 have a certified direct opening
42 41 12 11 22-21
On mechanism.
D4SL-N@F@@-@ 2NC/1NO+2NC 4 3 34-33
22 21 62-61
The terminals 42-11, 22-21, 34-
8
62 61 34 33
33, and 62-61 can be used as
Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 11-12 ,21-22
42-11
2 1 and 31-32 have a certified direct
42 41 12 11 22-21
On opening mechanism.
D4SL-N@G@@-@ 3NC+1NC/1NO 4 3 32-31
22 21 64-63
The terminals 42-11, 22-21, 32-
8
31, and 64-63 can be used as
64 63 32 31 Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 11-12 ,21-22
42-11
2 1 and 31-32 have a certified direct
42 41 12 11 22-21
On opening mechanism.
D4SL-N@H@@-@ 3NC+2NC 4 3 32-31
22 21 62-61
The terminals 42-11, 22-21, 32-
8
31, and 62-61 can be used as
62 61 32 31 Stroke
7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 11-12 and 21-
42-11
2 1 22 have a certified direct opening
42 41 12 11 52-21
2NC/1NO+ On mechanism.
D4SL-N@N@@-@ 4 3 34-33
2NC/1NO 52 51 22 21 64-63
The terminals 42-11, 52-21, 34-
33, and 64-63 can be used as
64 63 34 33 Stroke
8 7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 11-12 and 21-
42-11
2 1 22 have a certified direct opening
42 41 12 11 52-21
On mechanism.
D4SL-N@P@@-@ 2NC/1NO+3NC 4 3 34-33
52 51 22 21 62-61
The terminals 42-11, 52-21, 34-
62 61 34 33
33, and 62-61 can be used as
Stroke
8 7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

Lock position
Door open/closed Only NC contacts 11-12 ,21-22
Lock monitor detection 42-11 and 31-32 have a certified direct
2 1
42 41 12 11 52-21 opening mechanism.
On
D4SL-N@Q@@-@ 3NC+2NC/1NO 4 3 32-31 The terminals 42-11, 52-21, 32-
52 51 22 21 64-63 31, and 64-63 can be used as
64 63 32 31 Stroke unlike poles.
8 7 6 5 Operation Key Insertion Extraction
completion position completion position

Lock position
Door open/closed
Lock monitor detection Only NC contacts 11-12 ,21-22
42-11
2 1 and 31-32 have a certified direct
42 41 12 11 52-21
On opening mechanism.
D4SL-N@R@@-@ 3NC+3NC 4 3 32-31
52 51 22 21 62-61
The terminals 42-11, 52-21, 32-
31, and 62-61 can be used as
62 61 32 31 Stroke
8 7 6 5 Operation Key Insertion Extraction unlike poles.
completion position completion position

14
D4SL-N / D4SL-NSK10-LK@
Dimensions and Operating Characteristics (Unit:mm)

Switches
D4SL-N@@@@-@N (Connector Type)
29.2
Head cap 29.2

9
Pre-travel distance

B
Operation Key 39
A
37 Side mounting
Front-side mounting
26.3 26.3 22±0.2 Three, 4.3 dia.
Two, 4.3 dia. 39
Mounting hole 10 Mounting hole

Spacers
4.5 dia. 42.9
22±0.2 4 31.5 38.7±0.2 38.5
(depth: 1.6)

41.7±0.2 41.7±0.2 41.7±0.2 41.7±0.2


(62.75) (155) (62.75)
(73.5) (73.5)
112.1±0.8
4.5 dia. Label
(depth: 1.6) 4.5 dia.
(depth: 1.6) LED indicators
LED indicators 4.5 dia.
Release key (depth: 1.6)
Release key
(10.85) (10.85) (1) (8)

B-B A-A B
26 dia.
A
Conduit cap Conduit outlet

Model
D4SL-N@@@@-@N
Operating characteristics
* You can insert and secure a stud or
Key insertion force 15 N max. other projection in the 4.5-dia. hole to
Key extraction force 30 N max. Two, Cover mounting screw make the installation even stronger.
Pre-travel distance 15 mm max. For details, refer to “Switch and
Movement before being locked 3 mm min. Operation Key Mounting” on page 24.

D4SL-N@@@@-@ (Terminal Block Type)


29.2
Head cap 29.2

9
Pre-travel distance

B
39
Operation Key
A 37
Front-side mounting 22±0.2 Side mounting
26.3 26.3 Two, 4.3 dia. Three, 4.3 dia.
39 10
Mounting hole Mounting hole

Spacers
4.5 dia. 42.9
22±0.2 4 31.5 38.7±0.2 38.5
(depth: 1.6)

41.7±0.2 41.7±0.2 41.7±0.2 41.7±0.2


(62.75) (62.75)
(73.5) (179.9) (73.5)

4.5 dia. 4.5 dia. 137±0.8 4.5 dia.


(depth: 1.6) (depth: 1.6)
(depth: 1.6)
LED indicators Release key LED indicators
Release key

(10.85) (10.85) (1) (8) B

B-B A-A A 26 dia.


Conduit cap Conduit outlet

Model
D4SL-N@@@@-@
Operating characteristics
* You can insert and secure a stud or
Key insertion force 15 N max.
Two, Cover mounting screw other projection in the 4.5-dia. hole to
Key extraction force 30 N max.
make the installation even stronger.
Pre-travel distance 15 mm max. For details, refer to “Switch and
Movement before being locked 3 mm min. Operation Key Mounting” on page 24.

Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.

15
D4SL-N / D4SL-NSK10-LK@

Operation key

D4SL-NK1 D4SL-NK1S

28 29 19.5
21.5 29
7 13
7

35 15 22.7
35 15 22.7

7
4.3 7
Four, R2.15 4.3
Four, R2.15

2
2

D4SL-NK1G D4SL-NK2
28 29
21.5 15.6 14.5
29
8
7
35 20 12 22.7
35 22.7 15

Two, 4.3 dia. Two, 9 dia.


7
4.3
(5.2) Four, R2.15

2 2
Mounting rubber

D4SL-NK2G D4SL-NK3

17.2 14.5
29
8

35 22.7 12 20
17.7
29
4.5 dia. 15 Angle adjustment bolt
4
Two, 4.3 dia. Two, 9 dia.
8 dia.

9 dia.
22.7 30 40 56
2
20°
Mounting rubber

D4SL-NK5
Angle adjustment bolt
21.4 24.4
29 Mounting Holes
4 22.5 (Enlargement)
17
15
4.5
15°
41 30 43 55 8
22.7

41 43
6.5 (7)
8
1
18°

Note: Unless otherwise specified, a tolerance of ±0.4 mm applies to all dimensions.

16
D4SL-N / D4SL-NSK10-LK@

Connector Cables
D4SL-CN@
(30) L ±40 (150) Model L size
10
9
8 dia. (5)
8
7
6
D4SL-CN1 1m
5
4
3 D4SL-CN3 3m
2
1 *
Cable
AWG22, 10 conductors
D4SL-CN5 5m
Connector pin No. Connector (Cross section of conductor: 0.3mm2 /Insulator diameter: 1.45mm) D4SL-CN10 10 m
* All 10 lead wires laid bare.

Connector No. Lead wire color Connector No. Lead wire color
1 Black 6 Green/White
2 Black/White 7 Yellow
3 Red 8 Yellow/White
4 Red/White 9 Brown
5 Green 10 Brown/White

Slide Key
D4SL-NSK10-LK
Open door Close door

10
40×40

12.5

Lockout key

(26.8)
(314) (232.2) (81.8) (71.8)
(35) (30.2)
(147) (112) 19.1
(35) 107 8
15+10
−5 (Between Slide Key)
(20)
11.5
B B Shot bolt

(56.5) SLIDE
LOCK
SLIDE
LOCK
17
50 (64)
SLIDE SLIDE
FREE FREE
20 (90.4)
(76.2)
Guide
38.7 (32.5)
Four, M6
Slide base mounting holes
D4SL-NK1S Three, M4
22 Operation Key
(330)

Cross-sectional view A-A


4

17 Guard Lock Safety-door Switch


A A D4SL-N
Cross-sectional view B-B
(19.5)

11.5

Two, M6 11.6
12.5 mounting holes Switch base

17
D4SL-N / D4SL-NSK10-LK@

D4SL-NSK10-LKH
Open door Close door

10
Aluminum frame
40×40

12.5

Lockout key

(323) (71.8)
(35) (26.8)
(147) (121) (241.2) (81.8) 19.1
(35) 107
15+10
−5 (Between Slide Key)
(39.2)
(20) 8
40
11.5
B B Shot bolt
(115)
(56.5) SLIDE
LOCK
SLIDE
LOCK (78)
17
SLIDE
50 (64) SLIDE
FREE FREE
20 90.4
12 dia.
(76.2) 40 dia.
38.7 (32.5) Guide Inner Lever
Four, M6
Slide base mounting holes
D4SL-NK1S
22 Operation Key Three, M4
330 4

Cross-sectional view B-B


4

Cross-sectional view A-A


17 A A
(19.5)

11.5 Guard Lock Safety-door Switch


D4SL-N@@@@-@@ 11.6
Guard Lock Safety-door Switch Two, M6 Switch base
D4SL-N@@@@-@@N 12.5 mounting holes

With Operation Key Inserted

D4SL-N + D4SL-NK1
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
59 min. insertion radius
(37) >180
61.5 max. R=
Operation key
insertion position
(15)
Center tolerance of Horizontal Vertical
key hole: ±0.8 insertion radius insertion radius Center tolerance of
R>=180 Center tolerance of
R=>200 key hole: ±0.8
(15) key hole: ±0.8 9
Vertical
insertion radius
59 min. (37) >200 60.5 min.
R= 60.5 min.
61.5 max. 63 max. 63 max.
Operation key Operation key
(38.5) Operation key
insertion position insertion position (38.5)
insertion position
31.5

Center tolerance of
key hole: ±0.8

* Insertion radii apply when the rotational center of the Operation Key is in line with a line extending from the front or top Head surface.

18
D4SL-N / D4SL-NSK10-LK@

D4SL-N + D4SL-NK1S
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
50.5 min. insertion radius
(37) >180
53 max. R=
Operation key
insertion position
(15)
Center tolerance of Horizontal Vertical
key hole: ±0.8 insertion radius Center tolerance of
insertion radius
R=>180 Center tolerance of >200 key hole: ±0.8
R=
(15) key hole: ±0.8
Vertical 9
insertion radius
50.5 min. (37) >200
R=
53 max.
52 min. 52 min.
Operation key 54.5 max.
54.5 max.
insertion position Operation key
(38.5) Operation key (38.5)
insertion position insertion position
31.5

Center tolerance of
key hole: ±0.8

D4SL-N + D4SL-NK1G
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
59 min. insertion radius
(37)
61.5 max. Pitch 12 mm R> =120
Pitch 20 mm R= >170
Operation key
insertion position

Horizontal
insertion radius
(Pitch 12 mm) Center tolerance of >120 Center tolerance of Vertical Center tolerance of
Pitch 12 mm R=
(Pitch 20 mm) key hole: ±0.8 key hole: ±0.8 insertion radius key hole: ±0.8
Pitch 20 mm R> =170
(Pitch 12 mm) R=>140
(Pitch 20 mm) 9
Vertical (6.4)
59 min. insertion radius
(37)
61.5max. R>=140
60.5 min. 60.5 min.
Operation key 63 max. 63 max.
insertion position Operation key Operation key
(38.5) (38.5)
insertion position insertion position
(28.9) 31.5

Center tolerance of
key hole: ±0.8

D4SL-N + D4SL-NK2
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
53.1 min. insertion radius
(37) >180
55.6 max. R=
Operation key
insertion position

(15) Center tolerance of Horizontal Vertical


insertion radius Center tolerance of
key hole: ±0.8 >180 Center tolerance of
insertion radius
key hole: ±0.8
R= R>=200
(15) key hole: ±0.8
(17)
Vertical
9
53.1 min. insertion radius
(37) R>
55.6 max =200
54.6 min. 54.6 min.
Operation key 57.1 max.
57.1 max.
insertion position Operation key
(38.5) Operation key (38.5)
insertion position insertion position
31.5 (39.5)

Center tolerance of
key hole: ±0.8

* Insertion radii apply when the rotational center of the Operation Key is in line with a line extending from the front or top Head surface.

19
D4SL-N / D4SL-NSK10-LK@

D4SL-N + D4SL-NK2G
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
insertion radius
54.7 min. (37) >120
Pitch 12 mm R=
57.2 max. >170
Pitch 20 mm R=
Operation key
insertion position

Horizontal
(Pitch 12 mm) Center tolerance of insertion radius Center tolerance of
>120 Vertical Center tolerance of
(Pitch 20 mm) key hole: ±0.8 Pitch 12 mm R= key hole: ±0.8 insertion radius key hole: ±0.8
Pitch 20 mm R> =170 (Pitch 12 mm) R>=140
(Pitch 20 mm) (21.5)
Vertical
9
54.7 min. insertion radius
57.2 max. (37) >140
R=
Operation key 56.2 min. 56.2 min.
insertion position 58.7 max. 58.7 max.
Operation key Operation key
(38.5) (38.5)
insertion position insertion position
31.5 (39.5)

Center tolerance of
key hole: ±0.8

D4SL-N + D4SL-NK3
With Front-inserted Operation Key With Top-inserted Operation Key

Horizontal
55.2 min. insertion radius
57.7 max. (37)
R>=50
Operation key
insertion position

(40±0.15)
(40±0.15) Center tolerance of
Horizontal
Center tolerance of key hole: ±0.8 Vertical
insertion radius
key hole: ±0.8 >50 insertion radius Center tolerance of
R= key hole: ±0.8
R>=200

Vertical (9)
55.2 min. insertion radius
(37) >200
57.7 max. R=
Operation key 56.7 min. 56.7 min.
insertion position 59.2 max. 59.2 max.
(38.5) Operation key (38.5) Operation key
insertion position insertion position
31.5

Center tolerance of
key hole: ±0.8

D4SL-N + D4SL-NK5
With Front-inserted Operation Key With Top-inserted Operation Key
(37) Center tolerance of
58.7 min.
key hole: ±0.8
61.2 max.
Operation key
insertion position *
(41 or 43)
55

(41 or 43)
21.4 Horizontal
Horizontal Vertical Center tolerance of
insertion radius insertion radius
insertion radius
R> >50 key hole: ±0.8
=50 Center tolerance of R=
R>=50 (9)
key hole: ±0.8
58.7 min.
61.2 max. (37)
Operation key Vertical 60.4 min. 60.4 min.
insertion position * insertion radius 62.9 max. 62.9 max.
R=>50 Operation key Operation key
(38.5) (38.5)
31.5 insertion position insertion position
Center tolerance of
key hole: ±0.8

*1. Insertion radii apply when the rotational center of the Operation Key is in line with a line extending from the front or top Head surface.
*2. If you use the D4SL-NK5 turned over, the operation key insertion position is 60.3 min. and 61.2 max.

20
D4SL-N / D4SL-NSK10-LK@
Application Example
Highest achievable PL/
Model Stop category Reset
safety category
Guard Lock Safety-door Switch D4SL-N@E@A-@ (Mechanical Lock Type)
PLe/4 equivalent Safety Limit Switch D4N/D4F/D4B-N 0 Manual
Safety Relay Unit G9SE-201 (24 VAC/VDC)
Note: The above PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming
the usage conditions.

●Application Overview
• After the opening of the guard is permitted by turning ON of the lock release enable signal, the guard is opened by operating the lock release
switch S4.
• The guard status is monitored by the Safety Limit Switch S1 and Guard Lock Safety-door Switch S2, and a state in which the power supply to
the motor M is turned OFF must be maintained while the guard is open.
• When the guard is closed, lock status is ensured, and the reset switch S3 is pressed, the power supply to the motor M is permitted.

Lock release
enable signal

S4
9 10
S2 S1: Safety Limit Switch with direct opening mechanism
S2: Guard Lock Safety-door Switch D4SL-N@E@A-@
S3: Reset switch
42 64
S4: Lock release switch
41 63 KM1 and KM2: Magnetic contactor
M: Motor
12 22 34

11 21 33

1 2 3 4 5 6 7 8
Condition monitoring of
Guard Safety-door Switch

Feedback loop

S1 S3 KM1

KM2
open

A1 T11 T12 T31 T32 T33 13 23


KM1

KM2
Safety Reset/
Input1 Feedback Safety
Power Input Output
24 V supply (Instant M
circuit Safety aneous)
Input2 Auxiliary
output

A2 T21 T22 X1 14 24

PLC etc. KM1 KM2

Timing Chart
Guard opens Guard closes

Safety Limit Switch S1

Guard Lock Safety-door Switch S2


Door open/closed monitor contact

Guard Lock Safety-door Switch S2


Lock monitor contact

Lock release enable signal

Lock release switch S4


Guard can be opened
Reset switch S3

KM1 and KM2 (NO) Note: The lock release enable signal must be configured so that
it should turn ON after dangerous movement is stopped
Motor M rotation and safety is ensured for the door to open.

21
D4SL-N / D4SL-NSK10-LK@
Safety Precautions
Be sure to read the precautions for All Safety Door Switches in the website at:http://www.ia.omron.com/.

Indicates an imminently hazardous Precautions for Safe Use


situation which, if not avoided, is likely to
DANGER result in serious injury or may result in D4SL-N
death. Additionally there may be severe Operating Environment
property damage. Do not use the Switch submersed in oil or water or in locations
continuously subject to splashes of oil or water. Doing so may result
Indicates a potentially hazardous situation in oil or water entering the Switch. (The IP67 degree of protection of
CAUTION which, if not avoided, may result in minor the Switch specifies the amount of water penetration after the Switch
or moderate injury or in property damage. is submerged in water for a certain period of time.)

Precautions Supplementary comments on what to do Wiring


for Safe Use or avoid doing, to use the product safely. • Do not switch circuits for three or more standard loads (125 VAC,
1A). Doing so may adversely affect insulation performance.
Precautions Supplementary comments on what to do • Do not allow the load current to exceed the rated value.
or avoid doing, to prevent failure to • For metal cable glands, use a cable gland with the screw length of
for Correct operate, malfunction or undesirable effect 9 mm or less. Otherwise it may result in electric shock.
Use on product performance. • Do not use metal conduits. Damage to the conduit outlet may result
in an improper seal or electric shock.
• Do not a use metal cable gland for the conduit outlet of 1/2-14NPT.
DANGER In the event of damage to the conversion adapter, this may cause
seal failure and may result in electric shock.
Injury may occasionally occur. Always check to make • Always attach the cover after completing wiring and before using
sure that the safety functions operate correctly before the Switch. Do not supply power when the cover is not attached.
using the machine. The safety functions may not Electric shock may occur if the Switch is used without the cover
attached.
operate correctly because of wiring mistakes, setting
• When using the terminal block type, make sure that foreign
mistakes, or Switch malfunction, causing some
material does not adhere to the terminal block board. Otherwise a
machines to continue operating in situations where
short circuit may occur between terminals and safety functions
they should be stopped.
may fail to work properly.

Installation
CAUTION • Make sure the Switch is mounted securely to prevent it from falling
off. Otherwise injury may result.
D4SL-N
• Do not use a Switch as a stopper. Head Stopper
Injury may occasionally occur. When the Switch Be sure to install a stopper as shown in the
function is damaged, some machines may continue following illustration so that the Operation
operating in situations where they should be stopped. Key does not touch the head.
Do not subject the Switch to a shock that
Do not impose a force exceeding the key holding
exceeds the Switch's shock resistance of
force. Operation Key
1,000 m/s2.
Always provide a lock separate from the Switch,
attach a warning seal to avoid excessive force applied Switch
to the Switch, or provide an indicator lamp to show the
locked/unlocked status of the door.

D4SL-NSK10-LK@
Do not use this product mounted so that it slides
D4SL-NSK10-LK@
• Do not drop the Product. Doing so may prevent the Product from
vertically.
functioning to full capacity.
This may cause malfunction, resulting in personal
• Mount the Product securely to prevent it from falling. Otherwise,
injury.
injury may occur.
• Do not attempt to disassemble or modify the Switch. Doing so may
Do not insert the operation key with the door open. cause the Switch to malfunction.
Devices may start to operate, resulting in injury. • Make sure that the gap between the shot bolt and the guide is ±0.5
mm.
Otherwise, excessive wear or damage may cause malfunction.
• To ensure safety, do not operate the Switch with anything other
than the Slide Key Unit.
• Your hand may be injured by being pinched between the Operation
Key and Switch when closing the door with your hand on the
Product.

22
D4SL-N / D4SL-NSK10-LK@

• Be careful to avoid pinching your hand when operating the Slide Release Key
Handle. • The release key is used to unlock the Switch in case of emergency
• Do not impose a force of exceeding 1 N•m when operating the or if the power supply to the Switch stops.
Lockout Key. • If the release key setting is changed from LOCK to UNLOCK, the
Otherwise, the Product may be damaged and may not operate lock will be released and the safety door can be opened
properly. (mechanical lock models only).
To prevent damage, attach the supplied labels for display near the Å@

Front
Product.
D4SL-N@@@@-@ D4SL-N@@@@-@4
• Do not force the slide handle to move when the lockout key is not
inserted. Doing so may damage the product and make operation LOCK LOCK
impossible.
• Do not force the slide handle to move when the door is locked.
Doing so may damage the product and make operation impossible.
• Do not close the door with the shot bolt removed. Doing so may
damage the product and make operation impossible.
• Turn the Lockout Key to the "SLIDE LOCK" position and remove it
when opening the door to prevent a third party from operating the
Slide Handle.
• The durability of the Switch varies considerably depending on the
switching conditions. Always confirm the usage conditions by using UNLOCK UNLOCK
the Switch in an actual application, and use the Switch only for the
number of switching operations given in the performance Back
specifications. D4SL-N@@@@-@ D4SL-N@@@@-@4
• The user must not maintain or repair equipment incorporating the
Switch. Contact the manufacturer of the equipment for any LOCK LOCK
maintenance or repairs required.
• Refer to the D4SL-N Guard Lock Safety-door Switch Instruction
Sheet about storage conditions, ambient conditions,
Switch details, and handling methods.
• Do not apply excessive force in the direction of the slide. This may
damage the product and cause it to malfunction.
• Do not force the switch or cable. This may SLIDE
LOCK

damage the product. The cable should be fixed at SLIDE


FREE

a point separate from the switch.

UNLOCK UNLOCK

• When a Switch with a solenoid lock is in a locked state (i.e., when


the solenoid is ON), do not change the release key from the LOCK
to the UNLOCK position. Internal parts may be damaged.
Precautions for Correct Use • After setting the release key to UNLOCK to, for example, perform
D4SL-N maintenance, be sure to return it to LOCK setting before resuming
operation.
Solenoid Lock Models
• The release key is set in the unlock position at the factory for the
• For solenoid lock models, be sure to supply power to the solenoid D4SL-N@@@A and to the lock position for the D4SL-N@@@G.
after the door is closed (after the operation key is inserted). If the • In the unlock position, even when the door of large machines or
door is closed after power is supplied to the solenoid, locking the stamping machines is closed during preliminary adjustment, the
operation key may not be possible. (The solenoid carry current is door will remain unlocked and the machines will not be activated.
applied for Approx. 10 seconds, after which the internal circuit • Do not use the release key to start or stop machines.
switches to a constant current. The lock may not operate properly • The auxiliary lock must be released only by authorized personnel.
while the constant current is applied.) • Do not impose a force exceeding 0.2 N•m on the release key
• The solenoid lock locks the door only when power is supplied to the screws. The release key may be damaged and may not operate
solenoid. Therefore, the door will be unlocked if the power supply properly.
to the solenoid stops. Therefore, do not use solenoid lock models • To prevent the release key from being used by unauthorized
for machines that may be operating and dangerous even after the personnel, set it to LOCK and seal it with sealing wax.
machine stops operating.

23
D4SL-N / D4SL-NSK10-LK@

Mounting Covers Securing the Door


Confirm that the seal rubber has no defects before use. If the seal When the door is closed (with the
rubber is displaced or raised, or has foreign particles adhered to it, the Operation Key inserted), the Operation
sealing capability of the seal rubber will be adversely affected. Key may exceed the set zone because
of, for example, the door's own weight,
Hinged Door machine vibration, or the door cushion
Set zone *
(0.5 to 3 mm)
• If the Switch is mounted too close to the hinge, the force imposed rubber.
on the lock will be much larger than for locations far from the hinge Secure the door with a stopper (hook)
and the lock may be damaged. Mount the Switch close to the so that the Operation Key remains Operation key
handle. within the set zone.
* If you use the D4SL-NK5 with the
Mounting front key hole oriented in the
direction shown in the right diagram,
Appropriate Tightening Torque
the set zone will be 2.1 to 3.0 mm.
Loose screws may result in malfunction. Be sure to tighten each
screw of the Switch properly.
Cover mounting
0.4 to 0.5 N·m Spacer
screw
2.4 to 2.8 N·m (D4SL-NK@ and -NK@S) Do not remove a spacer. Rotate the spacer in accordance with the
Operation Key
mounting screw Switch mounting direction. Use of the Switch without spacer will
0.75 to 1.15 N·m (D4SL-NK@G)
reduce the lock strength.
Switch mounting
0.75 to 1.15 N·m
screw
1.8 to 2.2 N·m (except 1/2-14NPT)
Cable gland
1.4 to 1.8 N·m (1/2-14NPT)
Mounting side
Terminal screw
* Terminal block type 0.5 to 0.6 N·m (D4SL-N@@@@-@@)
only
Spacer
Switch and Operation Key Mounting
• Mount the Switch and Operation Key securely to the applicable Wiring
tightening torque with M4 screws. Always use washers. • DC solenoids have polarity. (E1: +, E2: −) Confirm terminal polarity
• The switch can be fastened more firmly by a stud (4 mm dia., 1.5 before wiring.
mm max height) inserted from back side at the hole of the switch. • The current of the 24 VDC solenoid is different from when it is first
Switch mounting Operation Key mounting turned ON as to when it is in operation. To take into account
Front D4SL-NK1/-NK2 possible voltage drops, it is important to apply a rated operation
22±0.1 Two, M4
Two, M4 voltage.
• To enable the 24 VDC solenoid, it is necessary to select the
41.7±0.15 appropriate power supply capacity.
15±0.1 • The ON and OFF contact operation will not engage
simultaneously.
D4SL-NK1G/-NK2G
Stud: 4±0.1 dia., height: 1.5 max.
Two, M4 Be sure to confirm operation under actual operating conditions.
Side 10±0.1
• If a lock is required for safety, design the system so that the closing
of the NC contacts on both the door open/closed detection switch
12±0.1 or 20±0.1
22±0.1
and the lock monitor switch is detected.
38.7±0.1 Three, M4

D4SL-NK3 Two, M4

41.7±0.15

40±0.1

Stud: 4±0.1 dia., height: 1.5 max.


D4SL-NK5 Two, M4

41±0.1 or 43±0.1
• Do not impose excessive force on the key top while the operation
key is inserted into the switch body or drop the switch with the
operation key inserted to avoid the deformation of the key or the
breakage of the switch body.
• Do not use the operation key other than dedicated OMRON's
(D4SL-NK@). Otherwise switch may be damaged.
• Do not use the operation key D4SL-K@. A lock will not be closed
and a machine will not be activated.
• Be sure that the operation key can be inserted properly to key hole
with a tolerance of ±0.8 mm.
• Insert the operation key into the key hole according to the specified
“operation key insertion radius in horizontal direction”.
• When mounting at the side of switch body, mount the switch with 3
points including the head.
• Attach cap heads to any operation key holes that are not being
used.

24
D4SL-N / D4SL-NSK10-LK@

Wiring Precautions for D4SL-N@@@@-@@ • Do not forcibly insert the wired socket at the cable side into the
• Do not wire the Switch while power is being supplied. Doing so may connector or D4SL-N’s conduit outlet. Doing so may cause cable
result in electric shock. break.
• Do not let particles, such as small pieces of lead wire, enter the Be sure to insert the cable into the connector or D4SL’s conduit
switch body when wiring. outlet before performing wiring to the socket, or insert the cable
• Do not directly wire the stranded wire to the terminal block. into the connector or conduit outlet from the opposite side of the
• When connecting to the terminals via insulating tube and bar socket.
terminals, arrange the bar terminals so that they do not rise up onto Applicable socket for cable side
the case or the cover.
• Applicable lead wire size: AWG22 to AWG18 (0.3 to 0.75 mm2). Manufacturer Name Model
• Use lead wires of an appropriate length. Not doing so may result in Housing XHP-10
excess length causing the cover to rise and not fit properly.
J.S.T. Mfg Co. Contact
• Remove the terminal block board out of the unit to perform wiring. (applicable wire lead: SXH-001T-P0.6
Be sure to insert the connector properly. AWG24 to AWG22)
• Do not pull on the lead wires with excessive force. Doing so may
disconnect them. Processing the Conduit Outlet
1 3 5 7 9
• Use a recommended cable gland and tighten it with the appropriate
40±3 mm tightening torque. The case may be damaged if an excessive
7 9
tightening torque is applied.
1 3 5
• Use a cable conforming to the diameter of the cable gland to be
used.
8 10 • For the 1/2-14NPT conduit, mount a provided conversion adapter
4 6
2 and wrap the seal tape around it to use the cable gland.
30±3 mm
2 4 6 8 10 Cable Gland
• Use a commercially available cable gland.
Recommended Crimp Terminals • Use a cable gland with a screw section not exceeding 9 mm to
Manufacturer Model Applicable wire lead ensure wiring properties.
AI0.34-8 TQ AWG22
PHOENIX
AI0.5-8 WH AWG20
CONTACT
AI0.75-8 GY AWG18
L1: 14 mm max. L1
L2: 8 mm max. L2

Wiring Precautions for D4SL-N@@@@-@@N


• Do not wire the Switch while power is being supplied. Doing so may
result in electric shock.
• Do not let particles, such as small pieces of lead wire, enter the
switch body when wiring.
• Applicable lead wire size: AWG24 to AWG22 (0.2 to 0.3 mm2).
Do not apply a current of 2 A or more when using AWG24.
• Use lead wires of an appropriate length. Not doing so may result in
excess length causing the cover to rise and not fit properly.

1 2 3 4 5 6 10

1 2 10

30±3 mm

• Do not pull on the lead wires with excessive force. Doing so may
disconnect them.

25
D4SL-N / D4SL-NSK10-LK@

D4SL-NSK10-LK@ Differences between Lockout Key and Trapped Key


• Use this product for a lightweight door (20 kg max). Otherwise the (Reference)
product may be damaged. Trapped key
• This product is for D4SL-N Guard Lock Safety-door Switch only. Lockout key (Refer to information on the
This product cannot be used with any other manufacturer's door D4JL-@@@A-@7-@@)
switches. The door cannot be closed The door cannot be closed
• Use the Slide Handle in the direction A or B in the following figure. Closing unless the lockout key is unless the trapped key is
the door inserted in the slide and inserted in the Door Switch
turned. and turned.
SLIDE
LOCK
FREE
SLIDE
SLIDE
FREE
The door can be opened by The door can never be opened
LOCK
SLIDE
Opening supplying power to the Door without both supplying power
the door Switch solenoid without to the Door Switch solenoid
operating the lockout switch. and operating the trapped key.
B A
• When mounting the operation key, line up the inside edges of the
• Loose screws may result in malfunction. Use washers and tighten long operation key holes with the outer edges of the slide handle
the screws to the specified torques. Mount the Slide Base at four as in the following figure to ensure easy position adjustment.
points with screws. Adding adhesive is recommended for
preventing the screws from loosening.
Also, when mounting the Product to a door for disable-prevention
purposes, purchase and use tamper-resistant screws.

Approriate Tightening Torque


Slide Key mounting screw (M6) 6.0 to 7.0 N·m • Use the supplied special screws to mount the operation key and
D4SL-N Guard Lock Safety-door Switch.
Operation key special mounting screw • To tighten the screws, use the tip of a flat-head screwdriver on the
2.4 to 2.8 N·m
(screws supplied)
screw heads as shown in the following figure.
Switch special mounting screw
0.75 to 1.15 N·m
(screws supplied)
Note: The special screws are
Inner Lever 9 to 10 N·m designed so that they cannot
be turned counter-clockwise
Technical Specifications using a flat-head
screwdriver.
Ambient operating temperature −10 to 55°C (with no icing)
• The special screws cannot be removed once they are tightened.
Ambient operating humidity 95% max.
Mechanical durability 20,000 operations min. Mounting of innner lever
• Do not store the Switch where corrosive gases (e.g., H2S, SO2, Mounting method
NH3, HNO3 or Cl2) or dust is present, or in locations subject to high 1) Detaching of mounting screw
temperature or humidity. Remove the handle mounting screw with TORX screwdriver (T30).
• Perform maintenance inspections periodically.
Handle
• When the lockout key is attached to your wrist, be careful that the
strap does not get stuck in equipment.

Nomenclature
Hexagonal nut (M6)
Slide Key Unit Handle mounting screw
Spring washer (TORX_T30/M6)
Guide (M6)
Shot Bolt Fig.1
Slide Base
2) Mounting of inner lever
Tighten A portion of the inner lever to a suitable torque with wrench
(width across flat: 10mm).

Lockout key Slide Handle Tightening Torque

Inner lever (M6) 9 to 10 N.m


Operation Key
A
Release Key Inner lever
Spring washer
(M6)
D4SL-N Guard Lock Safety-door Switch
Fig.1

• This product is for Omron, the D4SL-NSK10 only. This product


cannot be used with any other products.
• Do not operate the handle with the handle mounting screw
removed. Doing so may result in malfunction.
• Be careful not to lose the spring washer and hexagonal nut when
remove the handle mounting screw. (Fig.1)
• Loose inner lever may result in malfunction. Use washers and
tighten the inner lever to the specified torque. (Fig.2)

26
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.

Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.

Limitation on Liability; Etc.


OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.

Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.

Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.

Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.

Errors and Omissions.


Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation Industrial Automation Company Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V. OMRON ELECTRONICS LLC
Wegalaan 67-69, 2132 JD Hoofddorp 2895 Greenspoint Parkway, Suite 200
The Netherlands Hoffman Estates, IL 60169 U.S.A.
Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2012-2020 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_8_5
Tel: (65) 6835-3011/Fax: (65) 6835-2711 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200 Cat. No. C146-E1-05 1120 (0412)

You might also like