Application of IEC 60079-10-1 Edition 2.0 For Hazardous Area Classification

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/321930442

Application of IEC 60079-10-1 Edition 2.0 for Hazardous Area Classification

Article in IEEE Transactions on Industry Applications · December 2017


DOI: 10.1109/TIA.2017.2785258

CITATIONS READS
6 23,400

1 author:

Allan Bozek
EngWorks
11 PUBLICATIONS 32 CITATIONS

SEE PROFILE

All content following this page was uploaded by Allan Bozek on 14 September 2020.

The user has requested enhancement of the downloaded file.


APPLICATION OF IEC 60079-10-1 EDITION 2.0 FOR HAZARDOUS AREA
CLASSIFICATION
Copyright Material IEEE
Paper No. CA-086

Allan Bozek, P.Eng. MBA


Senior Member, IEEE
EngWorks Inc.
th
1620 49 Avenue S.W.
Calgary, AB T2T 2T7
Canada
abozek@engworks.ca

opportunity to participate. IEC National Committees may then


Abstract – This document provides guidance on the elect to use IEC publications within the context their national
application of IEC 60079-10-1 Edition 2.0: Explosive and regional standards publications. The development of
Atmospheres – Part 10-1: Classification of areas – Explosive IEC 60079-10-1 is the result of the efforts of the SC 31J
gas atmospheres. The IEC 60079-10-1 Ed. 2.0 document subcommittee responsible for the preparation and
incorporates significant revisions from previous editions in maintenance of IEC standards relating to the classification of
both technical content and design approach to classifying hazardous areas and their installation requirements.
hazardous locations where flammable gas or vapours may Edition 1.0 of IEC 60079-10-1 [2] evolved from IEC 79-10
be present. The design concepts incorporated into the [3] first published in 1972. The original publication consisted
document are introduced with application guidance provided of 13 pages of guidance addressing the classification of
in the context of real world examples. locations where flammable gas/vapour atmosphere may
exist. In 2008, the flammable gas/vapour and combustible
Index Terms — IEC 60079-10-1, Hazardous Area dust standards were amalgamated under the 60079 series of
Classification, Explosive gas atmospheres. standards. The subsequent revision of the IEC 60079-10
standard was renumbered to IEC 60079-10-1 Ed.1.0 to
address the classification of locations where flammable
I. INTRODUCTION gas/vapour hazards may exist. The former IEC 61241-10
standard was renumbered to IEC 60079-10-2 to address
IEC 60079-10-1 [1] is the core document used within the combustible dust hazards.
IEC system of standards for classifying locations where The IEC 60079-10-1 document is considered an objective
flammable gas or vapour hazards may be present. The based standard meaning that the requirements and
document supports the proper selection and installation of objectives that are important to health, safety, and the
equipment using the “zone” method of hazardous area technical integrity of a design are addressed. Every
classification. Edition 2.0 of IEC 60079-10-1 incorporates requirement is related to at least one of the standards stated
significant changes to address the shortcomings of previous objectives. The standard will state why an objective is
editions and provides several new evaluation methods for important and it may provide guidance on how to achieve an
determining the degree and the extent of a hazardous objective, but how a solution is implemented is left up to the
location. user. For this reason, the IEC standards for hazardous area
This paper describes the most significant changes classification do not incorporate application diagrams to
incorporated into IEC 60079-10-1 Ed. 2.0 and provides define a hazardous location. This is in contrast to such
guidance on how the document may be used to classify a publications as API RP 505 [4], NFPA 497 [5] and EI15 [6]
location. Several examples are presented with a discussion where “classification by example” diagrams are often used to
on how the results compare with API and NFPA designate the degree and extent of a hazardous location.
recommended practices. There was general industry consensus that the edition 1.0
of IEC-60079-10-1 required a revision to address several
shortcomings. While the body of the document addressed
II. EVOLUTION OF IEC 60079-10-1 the objectives required of a hazardous area classification, the
guidance provided in the supporting annexes did not always
A. History result in an acceptable solution. This prompted the
development of a new approach supported by scientific
The IEC is a world organization that publishes international research and experimental data. The calculation methods
standards for electrical, electronic and related technologies. incorporated into Edition 2.0 of IEC 60079-10-1 provide an
IEC standards publications form the basis of improved method of assessment that better reflects real
recommendations for international use and uniformity. The world applications.
standards are developed on a consensus bases with all
member countries interested in their development given the

1
III. TECHNICAL REVISIONS INCORPORATED in Fig. 2. A low pressure gas release in contrast will be
INTO IEC 60079-10-1 ED. 2.0 influenced more by material vapour density and atmospheric
conditions. The shape of the hazardous area would likely be
The technical changes incorporated into IEC 60079-10-1 as illustrated in Fig. 3. In contrast, a liquid hydrocarbon
Ed. 2.0 with respect previous editions include: release would likely form a pool near the vicinity of the
release. The extent of the hazardous area and its shape will
A. Recognition of Alternative Area Classification Standards be influenced by vapour pressure of the flammable fluid as it
and Recommended Practices evaporates under ambient conditions. The shape of the
hazardous area would be as illustrated in Fig 4.
IEC 60079-10-1 Ed. 2.0 recognizes the use of other The standard also provides recommended hazardous area
standards and recommended practices where they provide shapes for liquefied flammable gas release scenarios and
guidance or examples appropriate to the application and discusses how aerosol and hybrid mixtures incorporating
comply with general principles of the IEC standard. flammable gas and combustible dusts may be handled.
Historically, the IEC standard has relied on “source of
release” evaluation methodologies where release scenarios
were modelled using calculations to assess a situation and
determine an appropriate classification. The standard now
recognizes the use of “simplified methods” where the zone
classification and extent are determined using typical
diagrams sourced from a variety of publications including API
RP 505, NFPA 497 and EI15. IEC 60079-10-1 cautions
Users that where a standard is selected as a preferred base
for a site or application, examples from another standard
should not be selected to achieve a less rigorous
classification without due justification. An extensive list of
industry codes and national standards for hazardous area
classification are included for reference in Annex K of the Fig. 1 High Velocity Jet Release
document. Where such industry codes or national standards
are used, they shall be quoted as the basis for classification
and not IEC 60079-10-1.
The IEC standard also describes a “combination of
methods” approach where “simplified methods” are used to
classify facilities in the early stages of a design and then later
optimized using “source of release” methods when detailed
process information becomes available as the project
evolves. The “source of release” methodology is described in
detail in a series of schematic flowcharts incorporated into
Annex F of the document.
The standard now recognizes the value of prior experience
when classifying facilities. Clause 5.5.4 from NFPA 497 was
paraphrased within the standard allowing for the evaluation of
same or similar installations to be used as a basis for
classifying new facilities. It also implies that existing facilities Fig. 2 High Pressure Gas/Vapour Jet Release Hazardous
may be reclassified based on operating experience. This Area Shape
allows for experience and documented evidence to be
incorporated into a hazardous area classification design with
proper justification.

B. Forms of Release

IEC 60079-10-1 Ed. 2.0 incorporates a detailed discussion


of material properties as they apply to a potential source of
release and how it influences a hazardous area classification
design. The characteristics of a gaseous release, a gas
liquefied by pressure, or by temperature, or a liquid pool
release are discussed in the context of release behavior and
their influence on the shape of hazardous area. For
example, a high pressure gaseous release may be self-
diluting under certain conditions with the shape of the
hazardous area influenced primarily by the release velocity Fig. 3 Low Pressure Gas/Vapour Release Hazardous Area
as illustrated in Fig. 1. The suggested shape of the Shape
hazardous area under such conditions would be as illustrated

2
D.1 (Fig. 5) of the standard then suggests an appropriate
zone classification for the location. It should be cautioned that
the zone classification suggested by the table should be
evaluated against the formal definitions for a zone
classification. For example, the standard defines a zone 2
location as one where a flammable gas atmosphere is “not
likely to occur” and if it does, “exists for a short time only”. If
the “short time only” criteria cannot be achieved, which may
the case in remote unattended or unmonitored facilities; the
assignment of the zone classification may warrant further
evaluation.

Fig. 4 Flammable Liquid Pool Release Hazardous Area


Shape

C. Source of Release Calculation Methods

Annex B of IEC 60079-10-1 Ed. 2.0 provides calculation


methods for evaluating a source of release based on its form
of release.
1) Release rates of gas or vapours: The standard
provides a method for determining the release rate of low
pressure subsonic releases and high pressure sonic
releases. The calculation methods for gas releases are very
similar to the methods described in 60079-10-1 Ed. 1.0 with
the addition of a coefficient of discharge factor added to the
equations which serves to model the viscosity properties of a Fig. 5 IEC 60079-10-1 Ed 2.0 Table D.1 – Zones for Grade
liquid or gas with respect to a release opening. The standard of Release and Effectiveness of Ventilation
provides some guidance on selecting an appropriate
coefficient of discharge factor if no other information is E. Introducing the Concept of Dilution for Ventilation
available to the User. Assessment
The standard also incorporates a new table in Annex B that
recommends suitable hole cross sectional diameters for Previous editions of IEC 60079-10 evaluated enclosed
secondary grades of release. Previous editions of the locations based on the hypothetical volume Vz. Vz was
standard omitted this information and it was left up to the user defined as a volume in which a gas/vapour concentration was
to determine an appropriate hole size for a given situation. equal to a certain Lower Flammable Limit (LFL) safety
The hole size had a large influence on the calculation threshold depending on the intended zone classification. A
resulting in a wide variation of potential solutions. The new Zone 2 classification incorporated a 50% LFL (2X safety
table provides consistency in modelling similar situations factor) safety threshold. A Zone 0 or 1 location incorporated
which should help to achieve more uniform design solutions. a 25% LFL (4X safety factor) threshold. The Vz calculation
2) Release rate of liquids: The formula from 60079-10- was used to differentiate between “high”, “medium” and “low”
1 Ed. 1.0 with the addition of coefficient of discharge factor ventilation in enclosed spaces which subsequently influenced
(Cd) has been incorporated into the standard. The intent is to the zone classification for the area.
use the liquids release calculation to determine an The use of Vz as a basis for determining a zone
appropriate pool size for determining the release rate of an classification was controversial as there was no scientific
evaporative pools. basis for the formulae. The calculation of Vz often resulted in
3) Release rates of evaporative pools: A new very large volumes up to 3 orders of magnitude greater than
calculation model for evaluating the evaporation rate of a pool what was observed through Computational Fluid Dynamic
release is provided. This is a very common scenario in (CFD) modelling and real world experimental testing [7][8][9].
many facilities handling flammable liquids where a release There was general consensus among users that a new
scenario usually results in a pool formation adjacent the leak scientifically validated approach was needed to better reflect
source. The standard also provides a diagram to assist in reality.
determining the volumetric evaporation rate of a pool release. IEC 60079-10-1 Ed. 2.0 replaces Vz with the concept of
dilution. Dilution is a measure of the ability of ventilation or
D. Determining the Zone Classification of a Location atmospheric conditions to dilute a release to a safe level. It is
influenced by the release rate of the flammable material and
Annex D of the standard provides a structured method for ventilation velocity. Ventilation velocity is a measure of
selecting the appropriate zone classification for both indoor turbulence which is necessary to dilute a gas or vapour
and open air locations based on the “grade of release”, release. Air movement is required to promote a turbulent
“availability” of ventilation and the “effectiveness” of boundary layer between the release source and surrounding
ventilation within an area. Using these parameters, Table atmosphere. This allows air to mix with the release reducing

3
the LFL of the gas/air mixture and transporting it away. stopped. A low dilution environment typically leads to a Zone
Ventilation turbulence may be caused by momentum of the 1 or even Zone 0 classification based on Table D.1 (Fig. 5).
gas/vapour leak itself, by buoyancy of the release in air or by
wind flow interacting with the release.
For indoor situations, ventilation velocity is calculated by
determining the volumetric flow of the ventilation system
accounting for any release sources and dividing the value by
the cross sectional area perpendicular to the flow. This
results in an average flow velocity (Uw) that can be used for
assessing the ability of a ventilation system to control a
release.
To perform an assessment, the “ventilation velocity” is
determined by the design of the ventilation system or by
outdoor atmospheric conditions and plotted against the
“release characteristic” which describes the flammable
source of release in the context of the size and rate of
release. The standard provides a method for determining the
ventilation velocity of open areas using Fig. 6. The release
characteristic of a source of release may be calculated using
the following formula:
Fig. 7 IEC 60079-10-1 Ed 2.0 Figure C.1 – Chart for
Wg (m3/sec) (1) Assessing the Degree of Dilution
(ρg x k x LFL)
where For enclosed areas, both the ventilation velocity and the
background concentration of flammables entrained in the air
Wg mass release rate of flammable must be assessed. Dilution in an enclosed area may result
substance (kg/s) from the exchange of fresh air from outside the enclosure or
ρg Density of gas or vapour (kg/m3) by the enclosure itself having sufficient volume to allow the
k Safety factor attributed to LFL release to disperse. This makes it possible for large
LFL Lower flammable limit (vol/vol) enclosed areas to have minimal interior/exterior air exchange
rates while still maintaining sufficient ventilation effectiveness
to disperse a release.
To assess the background concentration of an enclosed
location, the flow rate from the flammable release source
must be compared to the fresh air introduction rate
accounting for mixing inefficiencies. The standard
incorporates a calculation formula to estimate the
background concentration as follows:
f x Qg (vol/vol) (2)
Xb = Qg + Q1
where
Fig. 6 IEC 60079-10-1 Ed 2.0 Table C.1 – Indicative
Xb Background concentration (vol/vol)
Outdoor Ventilation Velocities
Qg Volumetric flow of flammable gas from
the source of release (m3/sec)
The degree of dilution may then be determined using Fig.
Q1 Volumetric flow rate of air entering the
7. “High dilution” refers to situations where the
room through aperatures (m3/sec)
concentration near the source of release can be quickly
f Degree to which the air inside the
reduced and there will be no persistence after the release is
enclosure is well mixed
stopped. Under the appropriate conditions, this will permit a
f = 1 where the background
“NE” negligible extent that may be used as a basis to
concentration is uniform thoughout the
designate an area “non-hazardous”. “Medium dilution”
enclosure
applies to situations where the concentration of the release is
f ˃ 1 where inefficient mixing inside the
controlled resulting in a stable boundary when the release is
enclosure results in gradients of
in progress and the explosive gas atmosphere does not
background concentration
persist after the release has stopped. For most secondary
grade source release applications, a medium dilution
The criteria for assessment is Xb << Xcrit where Xcrit is the
environment will lead to a Zone 2 classification. “Low
maximum acceptable gas concentration determined by the
dilution” applies to situations where there is a significant
user. Xcrit would normally be the LFL alarm setpoint for gas
concentration while the release is in progress and the
detectors in the area.
flammable atmosphere will persists after the release is

4
For artificially ventilated enclosures, the ventilation  properties of flammable materials
velocity used for evaluation is the average flow velocity  identification and location of sources of release
caused by the ventilation system accounting for any Area classification design documentation should also
inefficiencies or flow obstructions. For naturally ventilated include plans, elevations or three dimensional models that
enclosures, the ventilation velocity will be a function of the indicate the type and extent of zones as well as the
thermal stack effect, wind effects on the enclosure and the appropriate group classification, ignition temperature and/or
combination effects of both. The concept of dilution and temperature class. The standard also discusses the option to
background concentration is further developed in the context indicate equipment protection levels (EPLs) on drawings to
of several application scenarios in Annex C of the standard. assist with the selection of equipment in hazardous locations.
The standard provides examples of data sheets that may be
F. Estimating the Extent of a Hazardous Zone used for documenting flammable material substances,
Annex D of IEC 60079-10-1 Ed. 2.0 incorporates a sources of release and hatching symbols for designating
structured method for determining the extent of a hazardous hazardous locations on drawings.
zone in outdoor locations. This is a welcome addition to the
standard as previous editions did not provide a means of H. Examples
assessing appropriate extents. The hazardous distances
suggested are based on release characteristic formulae (1) Annex E of the standard provides several examples
discussed earlier. Fig. 8 provides a graphical means of illustrating the use of concepts described. They are not
determining an appropriate extent based on the type of intended to be used as a basis for design but to illustrate the
release expected. Release behavior is characterized as a means of assessment as described in the annex sections of
heavy gas release, typical of a liquid pool release, a diffusive the standard. Examples include:
release resulting from a low velocity gas/vapour release or a  pump application in open air
jet release characteristic resulting from a high velocity gas  pump application within an enclosed location
release. As always, the distances calculated must be  process vessel in open air
evaluated using engineering judgement and an appropriate  control valve in a congested location
safety factor applied to account for facility layout and site  process piping in an enclosed location
conditions. The method described is for open air situations
 compressor facility handing natural gas
and does not apply to indoor low dilution applications.
The compressor facility example is fully documented to
illustrate the level of documentation expected for a given
application. It should be noted that the examples are
intended to show application of the evaluation methods and
are not intended to be used as representative examples for
classification purposes.

IV. APPLICATION OF IEC 60079-10-1 ED. 2.0

IEC 60079-10-1 Ed. 2.0 is intended to be used by


competent personnel who are well versed in the properties of
flammable materials (chemistry knowledge), able to identify
potential release sources (process and mechanical
knowledge), assess ventilation requirements (mechanical
knowledge) as well as understand the implications of a
classification design as it applies to the selection of electrical
equipment (electrical knowledge). The standard encourages
the use of a multidisciplinary team who possess competency
in each of these areas to participate in the design process.
Fig. 8 IEC 60079-10-1 Ed 2.0 Figure D.1 – Chart for The methodologies described in the Annex sections of IEC
Estimating Hazardous Area Distances 60079-10-1 Ed. 2.0 require detailed process information to
perform an assessment. Often, this information is not
G. Documentation available in the early stages of a project when preliminary
area classification design information is needed for long lead
IEC 60079-10-1 Ed. 2 recommends all area classification item purchases. This is where the use of other recognized
designs be fully documented. This is important in capturing documents such as API RP 505, NFPA 497 and EI15 may
the rationale used to classify a facility and to maintaining the have value. The documents provide conservative
integrity of the design over the life of the facility. Information classification by example diagrams that may be used to
to be incorporated into a documented design includes: determine the degree and extent of a classification based on
 sources of information used (code, national standard preliminary process information. The properties of the
or calculation) flammable materials handled must be considered to ensure
 gas a vapour dispersion calculations the diagram used is appropriate for the application.
 study of ventilation characteristics with consideration As additional process information becomes available, the
given to position of openings in buildings for ventilation hazardous area classification may be optimized using the
calculation methods described in the Annex sections of IEC

5
60079-10-1 Ed. 2.0. This provides the opportunity for the 2) Zone Classification: To determine the appropriate
hazardous area classification design to be optimized to reflect zone classification, the ventilation velocity and the release
the true nature of the hazard. characteristic must be determined. The ventilation velocity
can be determined from Table C.1 of IEC 60079-10-1 (Fig.
A. Natural Gas Release 6). For a lighter than air release in an unobstructed area, a
A hazardous area classification is required for a pressure ventilation velocity of 0.5 m/s at grade would be appropriate.
vessel located in an outdoor location in an upstream gas The release characteristic would then be determined
processing facility. The vessel handles natural gas at a using formula (1). This requires the LFL of natural gas be
pressure of 4500 kPA. Fig. 48 of API RP 505 recommends a determined as well as an appropriate safety factor applied
Zone 2 classification extent of 3 meters as illustrated in Fig. based on the LFL. Given that the LFL of natural gas
9. (methane) is relatively high at 5%, a k = 1.0 safety factor
would be appropriate. In other situations where the LFL is
less than 5%, a k safety factor of between 0.5 and 1.0 would
be applied. Based on the information provided, the
characteristic of release would be 0.042. Applying the results
of the release characteristic calculation to the expected
ventilation velocity as illustrated in Fig. 10, the application
results in a medium dilution situation.

0.5m/s

Fig. 9 API RP 505 Figure 48

To assess this situation using the methods incorporated


into the annex sections of IEC 60079-10-1 Ed. 2.0 requires
several steps as follows:
1) Calculation of the release rate: The first step is to model
a typical release scenario. This would be done by applying
the appropriate formulae provided in Annex B of the 0.042
standard. For this particular example, a choked gas velocity Fig. 10 Degree of Dilution
(sonic gas) release scenario using the following formulae
would be applicable. The zone classification for the application may then be
determined from table D.1 from IEC 60079-10-1 based on a
(3) secondary grade of release, good availability of ventilation
(typical of most outdoor locations) and medium degree of
dilution. Fig. 11 indicates a Zone 2 classification would be
appropriate. Typically, most secondary release applications
Table B.1 from the standard recommends a hole cross in open areas result in a Zone 2 classification unless there
2
sectional area of 0.25mm be applied. Additional process are significant impediments to the flow of natural ventilation in
information required to complete the calculation include: the area.
Once the appropriate zone classification has been defined,
 Operating pressure: P = 4500 kPA the extent of the Zone 2 classification may then be
 Process temperature: T = 25°C = 303.15K determined. Given that the release is sonic, a jet release
 Mole weight of Natural gas: 19 kg/kmole would be most likely warrant a 1 meter Zone 2 classification
 Specific heat at constant pressure: Cρ = 2.22 (kJ/kg K) as illustrated in Fig. 12.
 Polytropic Index of expansion : ɣ = 1.32 The results of the IEC source of release calculation would
 Compressibility Factor : Z = 1.0 indicate that a 1 meter Zone 2 classification surrounding the
 Coefficient of Discharge; Cd = 0.75 vessel flange connections would be appropriate for the
 Atmospheric Pressure; pa = 101kPA application. This compares to a 3 meter classification extent
 Universal Gas Constant; R = 8314 recommended by API RP 505.
 Gas density, ρg = 0.764 kg/m3 The difference can be attributed to the nature of the
Using the process information provided, the calculated release. The behaviour of a natural gas jet release is such
-3
release rate would be 1.6 X 10 kg/s. that the momentum of the gas release will mix turbulently
with the surrounding air as illustrated in Fig. 1. This would

6
limit the extent of the hazardous radii to a fairly short
distance. From an applications perspective, electrical and
instrumentation equipment mounted on the vessel would
need to be certified for a Zone 2 hazardous location.
Electrical and instrumentation equipment on process
equipment adjacent the vessel may not require a hazardous
location certification if they do not handle flammable materials
and are outside of the 1 meter Zone 2 classification.
Fig. 13 Mechanically Ventilated Building handing Natural
Gas

API addresses such situations based on the presence of


“adequately ventilation” which is defined as “Ventilation
(natural or artificial) that is sufficient to prevent the
accumulation of significant quantities of vapour-air or gas-air
mixtures in concentrations above 25% of the LFL”. API also
recognizes that locations ventilated at 6 air changes per hour
may be designated “adequately ventilated”. The ventilation
fan provides approximately 4 ACPH of ventilation which is
below the 6 ACPH default API adequate ventilation criteria.
To determine if the building is adequately ventilated in
accordance with API recommendations, a fugitive emission
calculation as described in Appendix B of API RP 505 would
be required.
Fig. 11 Zone Classification The IEC standard evaluates the zone classification based
on Fig. 5 by evaluating the grade of release, the availability of
ventilation and the effectiveness of the ventilation system.
Given that the application incorporates a secondary grade of
release, the zone classification will be determined by the
availability and the effectiveness of the ventilation system.
The availability of the ventilation system is categorized
using the following criteria from the standard:
Good: ventilation that is present continuously. Artificially
ventilated locations with power systems redundancy would
meet these criteria.
Fair: ventilation that is expected to be present during
normal operation with discontinuities occurring infrequently
and for short periods.
Poor: ventilation that does not meet the standard of fair or
good, but discontinuities are not expected to occur for long
periods.
1.0m The application was assessed to meet the criteria of “fair”
ventilation.
0.042 The effectiveness of the ventilation system requires
evaluation of the “degree of dilution” and determination of the
Fig. 12 Extent of Zone Classification – Gas Release expected background concentration for the application. The
assessment of the degree of dilution is based on Fig. 7. The
ventilation flow velocity may be calculated based on the
B. Natural Gas Release in an Enclosed Location volumetric flow of the gas/air mixture divided by the cross
sectional area perpendicular to the flow using the following
The same natural gas release scenario is evaluated for a formula:
6m long x 4m wide x 3.5m high enclosed location as
illustrated in Fig. 13. The location is mechanically ventilated Qa
3 Uw =(L L x H (m/sec) (4)
at 0.09 m /sec (200 CFM). What would be an appropriate
zone classification for the enclosed area? where

Uw Ventilation velocity (m/sec)


Qa Air flow rate (m3/sec)
L Length of the enclosed area (m)
H Height of the enclosed area (m)

7
The calculated ventilation velocity was determined to be for the application would consist of a small amount of leakage
0.004 m/sec. Applying the characteristic of release and the from the pump seal under normal operating conditions. The
ventilation velocity information to Figure C.1 from the IEC pump is surrounded by a 2m x 3m fluid containment dyke
standard results in a medium degree of dilution as illustrated designed to contain any leakage. The standard API diagram
in Fig. 14. used to classify refinery sources of release is illustrated in
Fig. 16. Given that pentane has a vapour density of 2.5 as
compared to air, the application requires a transient vapor
zone. A Zone 2 classification extending 15m in addition to a
15m transient vapour zone would apply.

0.004m/s

0.042
Fig. 16 API RP 505 Figure 20

Fig. 14 Enclosed Location Degree of Dilution Assessing this situation using the IEC source of release
calculation method requires examining the nature of a
Applying the information derived from the calculations to Fig. hypothetical release under normal conditions. A pentane
15 suggests a Zone 2 classification for the building. This release from a pump seal would likely result in some
however requires that the background concentration be flammable material flashing to atmosphere with the bulk of
checked using formulae (3). To do so, a suitable value of f is the release collecting in a pool formation within the
required which is a safety factor applied to account the containment dyke. The pentane fluid within the dyke would
degree of inefficiency of air mixing due to equipment then flash to atmosphere at a rate determined by the ambient
congestion and variable air flow patterns. Since the building air temperature and the vapour pressure of the pentane fluid.
layout is relatively open, an f factor of 2 was selected. The The release rate from an evaporative pool may be
background concentration Xb was then determined to be determined by calculation or by Figure B.2 of IEC 60079-10-1
4.5% LFL which is much less than the Xcrit value defined as as illustrated in Fig. 17. The values obtained from the figure
the 20% LFL gas detection alarm setpoint. Based on this are based on the assumption that the liquid temperature of
result, a Zone 2 classification would be appropriate for the the fluid is equal to the ambient temperature with a wind
application as illustrated in Fig. 15. speed of 0.5 m/sec. Pentane has a vapour pressure of 57
kPA at 20°C and a mole weight of 72 kg/kmole. Referencing
the chart, the volumetric evaporation rate would be
-3 3
approximately 0.5 x 10 m /sec for a pool surface area of 1.0
2
m . Given that the dimensions of the containment dyke in the
2
application is 6.0 m the value obtained from the chart must
be multiplied by the actual surface area yielding an estimated
volumetric evaporation rate of 3.0 x 10-3 m3/sec.
Calculating the release characteristic using formula (1)
yields a value of 0.4 based on a k safety factor of 0.5
(Pentane has a LFL of 1.5%) and a wind speed of 0.25 m/sec
sourced from table C.1 (Fig. 18) for a heavier than air release
in an unobstructed area at ground level. Using Figure D.1
from the standard (Fig. 19) for a heavy gas release yields a
hazardous location extent of approximately 6 meters. This is
in contrast the to the 30m extent recommended by API.
The extents determined by the IEC calculations are a
starting point and should be viewed with engineering
Fig. 15 Zone Classification for Enclosed Building judgement. Other factors such as below grade locations
within the classified area and other natural obstacles may
C. Pentane Fluid Release also influence the extent of the classification.
A pump in a refinery process handles pentane at 3000 kPA
at an operating temperature of 20°C. A typical leak scenario

8
V. CONCLUSIONS

The IEC 60079-10-1 Edition 2.0 standard is a significant


update to previous editions. It addresses many of the
shortcomings of previous editions and the rationale and
design approaches are based on scientific analysis
supported by testing and verification. The new document
acknowledges the use of alternative publications including
API RP 505, NFPA 497, EI 15 to classify locations and
recognizes the value in observing the behavior of existing
facilities when classifying new or re-classifying existing
facilities.
The classification methods described in the annexes of IEC
60079-10-1 Ed. 2.0 standard require a high level of
competency to perform a hazardous area classification. The
calculations require detailed process information to perform
an analysis which may not available in the early stages of a
project. While employing the methods described will help to
achieve an optimized design, the results should always be
applied with good engineering judgement taking into account
the nature of the flammable release, the working environment
Fig. 17 Volumetric Evaporation Rate Estimate and the potential consequences of an ignition event.

VI. REFERENCES

[1] IEC 60079-10-1/Ed:2, 2015, Explosive atmospheres –


Part 10-1: Classification of areas – Explosive gas
atmospheres, International Electrotechnical
Commission, Geneva, Switzerland.
[2] IEC 60079-10-1/Ed:1, 2009, Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas
atmospheres, International Electrotechnical
Commission, Geneva, Switzerland.
[3] IEC 79-10, 1972, Electrical Apparatus for Explosive
Fig. 18 Outdoor Ventilation Velocity for a Pentane Pool
Gas Atmospheres – Part 10 Classification of Hazardous
Release at Ground Level Areas, International Electrotechnical Commission,
Geneva, Switzerland.
[4] ANSI/API RP 505, 1997, Recommended Practice for
Classification of Locations for Electrical Installations at
Petroleum Facilities Classified as Class I, Zone 0, Zone
1, and Zone 2, American Petroleum Institute,
Washington, DC.
[5] EI 15, 2015 Model code of safe practice Part 15: Area
classification code for installations handling flammable
fluids, Energy Institute, London, UK.
[6] ANSI/NFPA 497, Recommended Practice for the
~6.0m Classification of Flammable Liquids, Gases, or Vapors
and of Hazardous (Classified) Locations for Electrical
Installations in Chemical Process Areas, National Fire
Protection Association, Quincy, MA.
[7] D.M. Webber, M.J. Ivings and R.C. Santon, “Ventilation
theory and dispersion modelling applied to hazardous
area classification”, Journal of Loss Prevention in the
Process Industries”, September 2011, 612-621.
0.4 [8] HSL Research Report RR630, “Area classification for
secondary releases from low pressure natural gas
systems”, Health and Safety Executive (HSE) UK 2008.
Fig. 19 Extent of Zone Classification – Pentane Release [9] P Persic, “Hypothetical Volume of Potentially Explosive
Atmosphere in the Context of IEC Standard 60079-10-
1, Ex-Bulletin, Croatia 2012. Vol 40, 1-2.

9
[10] Rangel Jr., Estellito, Luiz, Aurélio M. and Madureira Jr.,
Hilton – “Area classification is not a copy-and-paste
process: performing reliable hazardous area
classification studies”. IEEE IAS Industry Applications
Magazine, Jan/Feb 2016, p. 38 – 49.

[11] Bozek, Allan J. “Application of IEC 60079-10-1 Edition


2.0 For Hazardous Area Classification” in IEEE PCIC
Conference Record, 2017, pp 451 – 460.

VII. VITAE
Allan Bozek, P.Eng., MBA, graduated from the University
of Waterloo in 1986 with BSc in Systems Design Engineering
and a MBA from the University of Calgary in 1999. He is a
Principal with EngWorks Inc. providing hazardous location
consulting services to industry. He is a registered
professional engineer in the provinces of Alberta, Ontario,
Saskatchewan and British Columbia, Canada and has been
a member of the IEEE since 1989. Allan’s areas of expertise
include hazardous area classification design, application of
hazardous location codes and standards to facilities and the
design and certification of equipment in hazardous locations.

10

View publication stats

You might also like