Professional Documents
Culture Documents
Witness Test Proc For QSK With MCRS
Witness Test Proc For QSK With MCRS
Purpose
Introduction
The demonstration of the Alarm and Safety systems is required by most all of
the agencies that regulate marine engines (e.g. CG, ABS, and DNV). The
intent of this procedure is to demonstrate the alarm functions of the Cummins
supplied Alarm and Safety systems for QSK Series Engines with MCRS.
The Cummins supplied Alarm and Safety systems consist of three basic parts:
1. Engine mounted sensors monitored by the engine ECM and displayed
on all C Command alarm panels
2. Engine mounted sensors monitored directly by the C Command Elite
Plus Alarm System module (not the ECM) and displayed by the C
Command Elite Plus alarm panel only
3. Engine mounted sensors monitored directly by the C Command Elite
Plus Safety System module (not the ECM) and displayed by the C
Command Elite Plus alarm panel only
Table of Contents
Purpose ................................................................................................................1
Introduction ...........................................................................................................1
Table of Contents..................................................................................................2
Required Tools ..................................................................................................3
ECM Monitored Sensors................................................................................3
Alarm and Safety System Monitored Sensors: ..............................................3
Discussion ............................................................................................................3
Important: ..........................................................................................................4
Procedure .............................................................................................................7
I. Alarms Demonstration Using Calterm III .......................................................7
Example Alarm Demonstration Procedure:....................................................8
Demonstration of Engine Overspeed Protection (ECM Controlled): ............10
II. Alarms Demonstration Using INSITE™.......................................................12
Summary of Engine Protection Settings ......................................................13
Example Alarm Demonstration Procedure Using INSITE: ...........................13
III. Alarms Demonstration Using External Sources..........................................15
A. Fuel Leakage from High Pressure Fuel Lines Alarm Demonstration......16
B. Sea water Cooling System Pressure Alarm Demonstration ..................17
C. Intake Manifold Temperature
Alarm Demonstration (QSK38 IMT 2/3/4) .............................................19
D. Lube Oil Temperature Alarm Demonstration (QSK19 Only)...................21
E. Low Coolant Pressure Alarm Demonstration (QSK19 Only) ..................22
IV. Alarm and Shutdown Demonstration Procedure
for Sensors Monitored by the Safety System ............................................24
A. Low Lube Pressure LSR (Low Speed Range)
Shutdown Demonstration [SDU Switch 3 input].....................................25
B. Low Lube Pressure HSR (High Speed Range)
Shutdown Demonstration [SDU Switch 4]..............................................28
C. Low Coolant Pressure Switch
Shutdown Demonstration [SDU Switch 2]..............................................30
D. High Coolant Temperature Switch
Shutdown Demonstration [SDU Switch 1].............................................32
E. Overspeed Shutdown ............................................................................34
Attachments ........................................................................................................37
Discussion
There are a maximum of 24 sensor inputs to the alarm & safety system that can
trigger an alarm indication that can be demonstrated during a surveyor witness
test, depending on the Cummins engine model. The proportion of ECM-
monitored alarm sensors to separately-monitored alarm sensors also varies
depending on engine model. The independent safety system includes 5
sensors in all cases.
The demonstration of the Alarm and Safety system sensors depends upon the
monitoring device. There are 3 categories of sensors to be tested in this
procedure:
A. Sensors used by the ECM and shared with the Alarm system
B. Sensors used only by the Alarm system
C. Sensors used only by the Safety system
Important Information:
QSK19
QSK38
QSK50
QSK60
Alarm Sensor Alarm Type Action
NOTE: Safety System sensors are only connected at the Shutdown Unit
(SDU). No Engine ECM connections are present.
This method allows you to override a sensor’s value to the ECM with a
demonstration value. It must be entered manually using the selected
Calterm parameter and the ECM will alarm for that value accordingly.
Once the selected parameter override is disabled, the ECM will report the
value received from the sensor. Refer to Figure 1 for an overview of how
this demonstration method functions.
‘0’ default
Sensor
Value
ECM
Logic
Override
Value Display Value
‘1’ Override (Electronic
Display / Calterm)
Override
Enable
(Using Calterm)
Override Value:
This is the digital switch (flag) in the calibration which is defaulted to “0”
(disable); it needs to be “1” (enabled) for the processor to read the
“Override value” as the surrogate “sensor value.”
Display Value:
1. For selected Calterm III screen, add display value, override value
and override enable parameters from Table 4
a. Coolant_Temperature
b. AIP_Cool_Tmptr_Override_Value
c. T_AIP_CT_User_Override
4. Add 5 deg. above the threshold to that value and enter it into the
AIP_Cool_Tmptr_Override_Value parameter
Similarly any other sensor channel can be demonstrated with the method
described above. The only exception to this method is the demonstration
of Engine Overspeed. The procedure for this demonstration is covered in
the next section.
The engine overspeed feature works differently than all other engine
protection channels because of the software layout and the fact that this
protection is always enabled and cannot be disabled.
The “engine protection value” is the limit that, when exceeded, will cutoff
the fueling to the engine, thus causing a shutdown. This condition will
also generate a fault code indication to inform the operator of the
shutdown. The “secondary processor value” is the limit, when exceeded,
will cutoff the fueling to the engine but it will not generate a fault code.
NOTE: A Calterm III screen file of the values in this table is available in the Attachments section of this document.
(EP_Witness_Test.scr.xml)
II. Alarms Demonstration Procedure Using INSITE™
This feature is already available with INSITE™ v 7.0 for Auxiliary engine
models. A similar function for use on propulsion engine models will be
available the next INSITE software release.
It allows the customer to prove the operation of the engine protection feature by
using the tool to temporarily override sensor values. By overriding a sensor to
a value that exceeds an engine protection threshold, the desired engine
protection response can be observed.
This feature is available on electronic service tool v7.0 onwards and resides in
the ECM diagnostic test section. The following figure shows the window users
will be able to access with INSITE™. The engine protection channel and the
severity of fault can be selected through a drop down box. Pushing the “start”
executes the algorithm which demonstrates the function. All parameters
discussed in Table 1 are available for this witness testing.
Cummins Confidential
12 of 37
Summary of Engine Protection Settings
The selection for “Engine Protection Settings” is an INSITE™ view that displays
the dialog screen for the Engine Protection feature. Within this view the user
can determine how the engine will react when an engine protection fault is
logged.
The user can know if the engine protection derate has been suppressed or not.
In addition, the user can see all or some of the following information for each of
the critical parameters being monitored for engine protection through torque or
time derate or both:
• If the derate is applicable (and enabled) or not
• Fault Code
• Type of Derate (time or severity based)
• Parameter thresholds that triggers the derate
• Delays before the onset of derate.
Conditions and enable parameters for time based Torque and RPM shutdowns
such as the thresholds and warning periods for lamp flashes are also visible to
the user. Similar information for severity-based shutdowns is also given.
1. Select ECM Diagnostics Tests from the left side of the screen in the
INSITE tool.
2. Select the Engine Protection Witness Test feature from the list of tests.
5. With the engine running at desired speed, click “start” on the INSITE
screen to begin the test.
Page 13 of 37
6. Observe the test value of Oil Pressure displayed on the INSITE screen;
this value is now being supplied to the ECM for engine protection
functions in place of the value measured by the oil pressure sensor.
7. Observe the alarm threshold value for Oil Pressure as displayed on the
INSITE screen, below which the alarm will occur after the programmed
persistence time. This value is a function of engine speed (rpm).
10. Observe that approximately 3 minutes after clicking “start”, the low Oil
Pressure alarm goes inactive (and can be cleared from the display by
Acknowledge command) on the Cummins-provided display panel(s).
11. At this point, the test is complete and normal use of the Oil Pressure
sensor output by the ECM has resumed.
Page 14 of 37
III. Alarms Demonstration Procedure Using External Sources
For Alarm System sensors not shared by the engine ECM, an external source
is required to simulate the alarm condition. The external sources are used to
generate pressures, temperatures, and high level conditions that would trigger
a system alarm during normal operation. These sensors report to the Alarm
System monitoring panel. For C Command Elite Plus, this module is called the
Remote Input/Output Module (RIO).
The RIO is also responsible for triggering alarms when an Alarm System
sensor has exceed a pre-defined threshold. This alarm state is also broadcast
by the RIO to the C Command Elite RP display panel(s) or by a vessel supplied
monitoring system. As shown in Table 1, the component responsible for
monitoring the Alarm System sensors varies depending upon engine model.
The following section will outline the alarm demonstration procedures for the
each of the possible monitoring channels.
For this document, the QSK60 was chosen to be the example engine model.
Please refer to the QSK Series Engines with MCRS Sensor Locations
document in the appendix for a complete list of sensor locations.
Page 15 of 37
A. Fuel Leakage from High Pressure Fuel Lines Alarm Demonstration
1. Disconnect the input tube at the lower fitting on the leak tank. (See
Figure 3 for location)
3. Observe the alarm indication for fuel leakage from high pressure lines
on the Cummins-provided display panel, both visual and audible
4. Using a pressurized air source, blow out the fuel from the leak tank
(the drain fitting is on opposite side of tank from inlet fitting).
5. Observe that the alarm for fuel leakage from high pressure lines
becomes inactive on the Cummins-provided display panel.
Page 16 of 37
B. Sea water Cooling System Pressure Alarm Demonstration
1. Loosen the hold-down screw and remove the electrical connector from the
pressure sensor
Note: The alarm system will indicate an open circuit fault for
seawater pressure
Electrical Connector
Check Valve
2. Loosen the two hex head screws holding the pressure sensor in place.
3. Hold the check valve with a wrench to prevent it from rotating, and use
another wrench to rotate the pressure sensor counter-clockwise to
remove it from the check valve.
Note: the check valve prevents seawater from spraying out as the
sensor is removed.
Page 17 of 37
5. Apply an appropriate pressure to simulate normal operating conditions
(use a value above the line in Table 2 corresponding to the actual engine
rpm).
7
Seawater Pressure (psig)
0
0 500 1000 1500 2000 2500 3000
Engine RPM
7. Reduce the regulated pressure source to a desired value (below the line
in Table 2) in order to test the alarm system; observe that a low
seawater pressure alarm is indicated on the Cummins-supplied display
panel (and on the vessel alarm system if connected).
8. Once the alarm has been suitably demonstrated, re-install the sensor by
Page 18 of 37
C. Intake Manifold Temperature Alarm Demonstration (QSK38 IMT 2/3/4)
1. Remove the intake manifold sensing element from the thermo-well (do
not remove the thermo-well), located on the left underside of intake
manifold to be tested.
Thermo-well
Sensor Element
Temperature Sensor
Harness Connector
Page 19 of 37
2. Remove the P-clip bolt(s) as needed to gain sufficient free length of the
armored capillary to enable the sensing element to reach the heat bath.
3. Set the temperature of the heat bath to a value less than 93 C (200 F) and
allow to stabilize.
7. The DCU will alarm for high intake manifold temperature after 10 seconds.
8. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the buzzer.
9. Confirm that the DCU displays a yellow alarm for high intake manifold
temperature.
10. Remove the temperature sensing bulb from the heat bath.
12. Viewing the DCU alarm list, confirm that no faults remain active (Active
faults have red or yellow backgrounds, inactive faults have grey
backgrounds).
13. Press the Alarm button on the DCU again to return to the engine
parameter display.
14. Replace the sensing element in the pocket (removed in Step 1 above)
Page 20 of 37
D. Lube Oil Temperature Alarm Demonstration (QSK19 Only)
1. Remove the intake manifold sensing element from the thermo-well (do
not remove the thermo-well), located on the left underside of intake
manifold to be tested. (Refer to Figures 5 and 6 for images of an
example sensor)
2. Remove the P-clip bolt(s) as needed to gain sufficient free length of the
armored capillary to enable the sensing element to reach the heat bath.
3. Set the temperature of the heat bath to a value less than 120 C (250 F)
and allow temperature to stabilize.
7. The DCU will alarm for high lube oil temperature after 5 seconds.
8. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the buzzer.
9. Confirm that the DCU displays a yellow alarm for high intake lube oil
temperature.
10. Remove the temperature sensing bulb from the heat bath.
12. Viewing the DCU alarm list, confirm that no faults remain active (Active
faults have red or yellow backgrounds, inactive faults have grey
backgrounds).
13. Press the Alarm button on the DCU again to return to the engine
parameter display.
14. Replace the sensing element in the pocket (removed in Step 1 above)
Page 21 of 37
E. Low Coolant Pressure Alarm Demonstration (QSK19 Only)
Isolation Valve
Pressure Fitting
2. Remove pressure fitting cap nearest the engine from the manifold block
4. Adjust the regulated pressure source to provide at least 70 kPa (10 psig)
into the manifold.
8. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the buzzer (the SDU buzzer will continue)
Page 22 of 37
9. Confirm that the DCU displays yellow alarm for low coolant pressure.
12. Viewing the DCU alarm list, confirm that no related faults remain active
(Active faults have red or yellow backgrounds, inactive faults have grey
backgrounds).
13. Press the Alarm button on the DCU again to return to the engine
parameter display.
14. Remove the regulated pressure source, and replace the cap on the
manifold.
Page 23 of 37
IV. Alarm and Shutdown Demonstration Procedure for Sensors Monitored
by the Safety System
The SDU is also responsible for triggering alarms and providing an engine
shutdown when a Safety System sensor has exceeded a pre-defined threshold.
This alarm state is also broadcast by the RIO to the C Command Elite RP display
panel(s) or by a vessel supplied monitoring system.
All engines delivered with C Command Elite Plus monitoring systems are
delivered with the sensors and connectors according to Table 2 above. The
following section will outline the alarm and shutdown demonstration procedures
for the each of the Cummins Supplied SDU monitoring channels.
Be advised that the switch locations, orientations, and size will vary from engine
to engine. For this document, the QSK60 was chosen to be the example engine
model. Please refer to the QSK Series Engines with MCRS Sensor Locations
document in the appendix for a complete list of sensor locations.
Page 24 of 37
A. Low Lube Pressure LSR (Low Speed Range) Shutdown Demonstration
[SDU Switch 3 input]
2. Remove the upper-most pressure fitting cap from the manifold block
4. Adjust the regulated pressure source to provide at least 138 kPa (20
psig) into the manifold port.
5. Run the engine at idle (Must be less than 1400 rpm to operate in low
speed range).
Page 25 of 37
7. The SDU will shut down the engine after 5 seconds below approximately
104 kPa (15 psig).
8. After the engine has shut down, confirm that the red “Shutdown” LED on
the SDU is illuminated as well as the red LED for “Switch 3” indicating
low lube pressure.
9. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the DCU buzzer (The SDU buzzer has an auto-off
feature that will silence the alarm after 5 seconds.)
10. Confirm that the DCU displays a red SDU alarm for low lube oil pressure
(low speed range).
12. Press the Alarm button on the DCU to return to the screen displaying
gauges.
13. Attempt to start the engine using the Start button on the DCU, to
demonstrate it will not start (Prior to Acknowledging the SDU).
14. Press the “Acknowledge” (upper) pushbutton on the face of the SDU
inside the CIB.
15. Confirm that the SDU buzzer ceases, and that there are no faults
indicated on the SDU via illuminated yellow LEDs.
16. Confirm the red LED for switch 3 is no longer illuminated on the SDU.
Page 26 of 37
17. Acknowledge any SDU related faults appearing on the DCU by pressing
the Alarm button on the DCU, then pressing the Acknowledge button at
bottom left of screen.
18. Viewing the DCU alarm list, confirm that no SDU related faults remain
active (Active faults have red or yellow backgrounds, inactive faults have
grey backgrounds).
19. Press the Alarm button on the DCU again to return to the engine
parameter display.
20. Remove the regulated pressure source, and replace the cap on the
manifold.
22. Confirm that the engine can be started using the Start button on the
DCU.
Page 27 of 37
B. Low Lube Pressure HSR (High Speed Range) Shutdown Demonstration
[SDU Switch 4]
4. Adjust the regulated pressure source to provide at least 240 kPa (35
psig) into the manifold.
5. Start the engine and run it at rated (Must be at least above 1400 rpm to
operate in high speed range).
7. The SDU will shut down the engine after 5 seconds below approximately
200 kPa (29 psig).
8. After the engine has shut down, confirm that the Red “Shutdown” LED
on the SDU is illuminated as well as the red LED for “Switch 4” indicating
low lube oil pressure HSR.
9. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the DCU buzzer (The SDU buzzer has an auto-off
feature that will silence the alarm after 5 seconds)
10. Confirm that the DCU displays a red SDU alarm for low oil pressure
(high speed range).
12. Press the Alarm button on the DCU to return to the screen displaying
gauges.
13. Attempt to start the engine using the Start button on the DCU, to
demonstrate it will not start (Prior to Acknowledging the SDU).
14. Press the “Acknowledge” (upper) pushbutton on the face of the SDU
inside the CIB.
Page 28 of 37
15. Confirm that the SDU buzzer ceases, and that there are no faults
indicated on the SDU via illuminated yellow LEDs.
16. Confirm the red LED for Switch 4 is no longer illuminated on the SDU.
17. Acknowledge any SDU related faults appearing on the DCU by pressing
the Alarm button on the DCU, then pressing the Acknowledge button at
bottom left of screen.
18. Viewing the DCU alarm list, confirm that no SDU related faults remain
active (Active faults have red or yellow backgrounds, inactive faults have
grey backgrounds).
19. Press the Alarm button on the DCU again to return to the engine
parameter display.
20. Remove the regulated pressure source, and replace the cap on the
manifold.
22. Confirm that the engine can be started using the Start button on the
DCU.
Page 29 of 37
C. Low Coolant Pressure Switch Shutdown Demonstration
[SDU Switch 2]
Isolation Valve
Pressure Fitting
2. Remove pressure fitting cap nearest the engine from the manifold block
4. Adjust the regulated pressure source to provide at least 70 kPa (10 psig)
into the manifold.
7. The SDU will shut down the engine after 5 seconds below approximately
14 kPa (2 psig).
Page 30 of 37
8. After the engine has shut down, confirm that the red “Shutdown” LED on
the SDU is illuminated as well as the red LED for “Switch 2” indicating low
coolant pressure.
9. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the buzzer (The SDU buzzer has an auto-off feature that
will silence the alarm after 5 seconds)
10. Confirm that the DCU displays a red SDU alarm for low coolant pressure.
12. Press the Alarm button on the DCU to return to the screen displaying
gauges.
13. Attempt to start the engine using the Start button on the DCU, to
demonstrate it will not start (Prior to Acknowledging the SDU).
14. Press the “Acknowledge” (upper) pushbutton on the face of the SDU
inside the CIB.
15. Confirm that the SDU buzzer ceases, and that there are no faults
indicated on the SDU via illuminated yellow LEDs.
16. Confirm the red LED for Switch 2 is no longer illuminated on the SDU.
17. Acknowledge any SDU related faults appearing on the DCU by pressing
the Alarm button on the DCU, then pressing the Acknowledge button at
bottom left of screen.
18. Viewing the DCU alarm list, confirm that no SDU related faults remain
active (Active faults have red or yellow backgrounds, inactive faults have
grey backgrounds).
19. Press the Alarm button on the DCU again to return to the engine
parameter display.
20. Remove the regulated pressure source, and replace the cap on the
manifold.
21. Open the isolation valve (Closed in Step 1 above) by rotating it 90 degrees
counterclockwise, so that the arrow heads are pointing up and down.
22. Confirm that the engine can be started using the Start button on the DCU.
Page 31 of 37
D. High Coolant Temperature Switch Shutdown Demonstration
[SDU Switch 1]
1. Remove the coolant sensing element from the thermo-well (do not
remove the thermo-well), located on the left underside of thermostat
housing.
Thermo-well
Sensor Element
P-Clip Bolt
2. Remove the P-clip bolt(s) as needed to gain sufficient free length of the
armored capillary to enable the sensing element to reach the heat bath.
3. Set the temperature of the heat bath to a value less than 100 C (212 F)
and allow temperature to stabilize.
7. The SDU will shut down the engine after 5 seconds above approximately
105 C (221 F).
Page 32 of 37
8. After the engine has shut down, confirm that the red “Shutdown” LED on
the SDU is illuminated as well as the red LED for “Switch 1” indicating
high coolant temperature.
9. Press the Alarm button on the DCU (Engine room panel on front of CIB
door) to cancel the buzzer (The SDU buzzer has an auto-off feature that
will silence the alarm after 5 seconds)
10. Confirm that the DCU displays a red SDU alarm for high coolant
temperature.
11. Remove the temperature sensing bulb from the heat bath.
12. Press the Alarm button on the DCU to return to the screen displaying
gauges.
13. Attempt to start the engine using the Start button on the DCU, to
demonstrate it will not start (Prior to Acknowledging the SDU).
14. Press the “Acknowledge” (upper) pushbutton on the face of the SDU
inside the CIB.
15. Confirm that the SDU buzzer ceases, and that there are no faults
indicated on the SDU via illuminated yellow LEDs.
16. Confirm the red LED for Switch 1 is no longer illuminated on the SDU.
17. Acknowledge any SDU related faults appearing on the DCU by pressing
the Alarm button on the DCU, then pressing the Acknowledge button at
bottom left of screen.
18. Viewing the DCU alarm list, confirm that no SDU related faults remain
active (Active faults have red or yellow backgrounds, inactive faults have
grey backgrounds).
19. Press the Alarm button on the DCU again to return to the engine
parameter display.
20. Replace the sensing element in the pocket (removed in Step 1 above).
22. Confirm that the engine can be started using the Start button on the
DCU.
Page 33 of 37
E. Overspeed Shutdown
1. With the engine running at Idle, disconnect the electrical connector from
the speed sensor for the Safety System, located on the flywheel housing
as shown in Figure 13.
Note: This unit contains two sensors with two connectors in one
assembly.
Page 34 of 37
2. Confirm that the SDU indicates a fault for both Tacho 1 and Tacho 2 via
two illuminated yellow LEDs.
3. Press the alarm button on the DCU to observe that an active yellow SDU
alarm is present for both Tacho 1 and Tacho 2.
5. Press the Acknowledge button on the SDU and observe that the yellow
LEDs for Tacho 1 and Tacho 2 are extinguished.
6. On the DCU alarm screen, observe that the SDU Tacho alarms are
inactive (grey background)
7. Press the Acknowledge button on the DCU and observe that the two
SDU Tacho faults disappear.
8. Press and hold for more than 2 seconds the “Overspeed Test” button on
the SDU. This button is found beneath the “Acknowledge” button.
Observe the red “Overspeed” LED blinks rapidly to confirm that
overspeed test mode is active.
Page 35 of 37
9. While the “Overspeed” LED is blinking (Within 4 minutes of completing
Step 8), increase the engine speed toward 1500 rpm, which is 75 rpm
above the Overspeed Test threshold while the SDU is in Overspeed Test
mode.
10. Observe that the engine shuts down immediately after exceeding 1425
rpm, and that the red “Overspeed” LED is illuminated solidly.
11. Press the Alarm button on the DCU (engine room panel on front of CIB
door) to cancel the buzzer (The SDU buzzer has an auto-off feature that
will silence the alarm after 5 seconds)
12. Confirm that the DCU displays a red SDU shutdown alarm for
overspeed.
13. Press the Stop button on the DCU, return the throttle to zero and/or
remove any automatic engine start command from the DCU.
14. Press the Alarm button on the DCU to return to the screen displaying
gauges.
15. Attempt to start the engine using the Start button on the DCU, to
demonstrate it will not start (Prior to Acknowledging the SDU).
16. Press the “Acknowledge” button on the SDU inside the CIB.
17. Confirm that the SDU buzzer ceases, and that there are no faults
indicated on the SDU via illuminated yellow LEDs.
18. Confirm the red LED for “Overspeed” is no longer illuminated on the
SDU.
19. Acknowledge any SDU related faults appearing on the DCU by pressing
the Alarm button on the DCU, then pressing the Acknowledge button at
bottom left of screen.
20. Viewing the DCU alarm list, confirm that no SDU related faults remain
active (Active faults have red or yellow backgrounds, inactive faults have
grey backgrounds).
21. Press the Alarm button on the DCU again to return to the engine
parameter display.
22. Confirm that the engine can be started using the Start button on the
DCU.
Page 36 of 37
Attachments
Change Log
Revising Author’s
Date Change Page
Name
5/21/2008 Published to the Web ddc
Distribution of this document is intended for Cummins personnel and distributors. The information contained in this
document is only considered valid while published on the Marine Website. Copies and archived documents are not
considered current.
Page 37 of 37