QPS, ft2-hr-F/Btu [2] ft2-hr-F/Btu [1]

Tag No. SS Fluid TS Fluid Remarks


SS Fouling Factor TS Fouling Factor SS Fouling Factor TS Fouling Factor
E-923 Sour Off Gas Cooling Water 0.0073 0.0020 0.001 0.002
E-918 Naphtha Pdt Cooling Water 0.0073 0.0244 0.001 0.002
E-916 Diesel Pdt Cooling Water 0.0073 0.0024 0.002 0.002
E-915 Sour Water Cooling Water 0.0020 0.0020 0.002 0.002
E-910 - Naphtha - 0.0020 - 0.001 Air Cooler
E-909 - CC-902 Ovhd. Vapor - 0.0020 - 0.001 Air Cooler
E-903 - Fuel Oil - 0.01 - 0.002 Air Cooler
E-928 - R-904 Effluent - 0.002 - 0.002 Air Cooler
E-927 Column Feed Reactor Effluent 0.0073 0.0073 0.002 0.002
E-925 Diene Reactor Feed HCR Reactor Effluent 0.0073 0.0073 0.002 0.002
Electric Heater at
E-924 - R-904 Reactor Feed - 0.01 - 0.002
present
E-921 Reactor Effluent Cooling Water 0.0073 0.0020 0.002
E-920 HCR Feed Reactor Effluent 0.0073 0.0073 0.002 0.002
E-919 - R-901 Feed - 0.01 - 0.002 Air Cooler
E-913 - R-901 Effluent - 0.007 - 0.002 Air Cooler
E-912 - Diesel - 0.007 - 0.002 Air Cooler
E-904 Reactor Feed Reactor Effluent 0.0073 0.0073 0.002 0.002

RED FONT VALUES THAT ARE WAY BEYOND TYPICAL VALUES

[1] Based on Standard (refer section 4.6 in Process design criteria doc. No. US00-40-100-PQ-DCR-0001). CPE to review and advise whether to
use these or retain QPS values.
[2] Values from QPS exchanger datasheets.