2UCD190000E013_e PCS100 ESS Overload Curves.

xlsx

PCS100 ESS System Overload Curves


Cu + IGBT
Preload
10000 50% Cu

75% Cu

100% Cu

1000 50% Silicon


600
75% Silicon

100% Silicon
Time (s)

100 @75% preload

@100%
30 preload
Software
overload
10 50% Cu*

*extrapolated
2
values not verified

1
100% 120% 140% 160% 180% 200%
40°C ambient Current (%) 2UCD190000E013-E

PCS100 ESS Overload Curves (Provisional)


The PCS100 ESS Overload Curves show the absolute operational limits (trip levels) permitted
by the ESS software for various preload levels.

Three thermal protections are employed:


1) System copper thermal model to protect the system wiring
2) Module copper thermal model to protect the module PWM reactors and cables
3) Module IGBT junction thermal model to protect the PCS100 module IGBTs.

The maximum safe overload duration is the lower of the Copper and Silicon protection curves
for a given preload level.

Specified claims are plotted for reference:


- 120% for 600 seconds from a 75% preload.
- 150% for 30 seconds from a 100% preload.
- 200% for 2 seconds from a 75% preload.

ABB Confidential 11/08/2016 1


2UCD190000E013_e PCS100 ESS Overload Curves.xlsx

PCS100 ESS System Overload Curves


Preload
10000 @75% preload

@100% preload

100% Combined

1000 75% Combined


600
Software
overload
75% Cu*
Time (s)

100 *extrapolated
values not verified
30

10

2
1
100% 120% 140% 160% 180% 200%
40°C Ambient Current (%) 2UCD190000E013-E

PCS100 ESS Overload Curves (Provisional)


The PCS100 ESS Overload Curves show the absolute operational limits (trip levels) permitted
by the ESS software for various preload levels.

Three thermal protections are employed:


1) System copper thermal model to protect the system wiring
2) Module copper thermal model to protect the module PWM reactors and cables
3) Module IGBT junction thermal model to protect the PCS100 module IGBTs.

Specified claims are plotted for reference:


- 120% for 600 seconds from a 75% preload.
- 150% for 30 seconds from a 100% preload.
- 200% for 2 seconds from a 75% preload.

ABB Confidential 11/08/2016 2