Professional Documents
Culture Documents
Frequency Stability of Synchronous Machines and Grid-Forming Power Converters
Frequency Stability of Synchronous Machines and Grid-Forming Power Converters
2, JUNE 2020
Abstract— An inevitable consequence of the global power sys- renewable system is the gradual loss of synchronous machines
tem transition toward nearly 100% renewable-based generation (SMs), their inertia, and control mechanisms. This loss of the
is the loss of conventional bulk generation by synchronous rotational inertia changes the nature of the power system to
machines (SMs), their inertia, and accompanying frequency- and
voltage-control mechanisms. This gradual transformation of the a low-inertia network resulting in critical stability challenges
power system to a low-inertia system leads to critical challenges [1]–[3]. On the other hand, low-inertia power systems are char-
in maintaining system stability. Novel control techniques for con- acterized by large-scale integration of generation interfaced by
verters, so-called grid-forming strategies, are expected to address power converters, allowing frequency and voltage regulations
these challenges and replicate functionalities that, so far, have at much faster timescales compared with SMs [1], [4].
been provided by SMs. This article presents a low-inertia case
study that includes SMs and converters controlled under various Indeed, power converters are already starting to provide
grid-forming techniques. In this article, the positive impact of the new ancillary services, modifying their active and reactive
grid-forming converters (GFCs) on the frequency stability of SMs power outputs based on local measurements of frequency and
is highlighted, a qualitative analysis that provides insights into voltage. However, because of the dependence on frequency
the frequency stability of the system is presented, we explore measurements, these grid-following control techniques only
the behavior of the grid-forming controls when imposing the
converter dc and ac current limitations, the importance of the replicate the instantaneous inertial response of SMs after a
dc dynamics in grid-forming control design as well as the critical contingency with a delay and result in degraded performance
need for an effective ac current limitation scheme are reported, on the timescales of interest [5]. To resolve this issue, grid-
and finally, we analyze how and when the interaction between forming converters (GFCs) are envisioned to be the corner-
the fast GFC and the slow SM dynamics can contribute to the stone of future power systems. Based on the properties and
system instability.
functions of SMs, it is expected that GFCs must support load-
Index Terms— Frequency stability, grid-forming converters sharing/drooping, black start, inertial response, and hierarchi-
(GFCs), low-inertia power system, synchronous machines (SMs). cal frequency/voltage regulation. While these services might
not be necessary for a future converter-based grid, a long
I. I NTRODUCTION transition phase is expected, where SMs and GFCs must be
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1005
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1006 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
Fig. 3. IEEE nine-bus test system with an SM, two large-scale multiconverter
systems (i.e., aggregate GFCs), and constant impedance loads.
TABLE I
Fig. 2. Equivalent model of an individual converter module (left), large-
C ASE S TUDY M ODEL AND C ONTROL PARAMETERS [23]
scale multiconverter system consisting of n identical modules (middle), and
aggregate model (right).
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1007
Fig. 4. Grid-forming control architecture with reference models described in Sections III-C–III-F.
source (1a) and the modulation signal mαβ for the dc–ac
where ī s,dq denotes the limited reference current that preserves
conversion stage (1) (see Fig. 1). In the following, we briefly
the direction of i s,dq ac /i ). We emphasize
and γi := (i max s,dq
review the low-level cascaded control design (i.e., ac volt- that limiting the ac current can have a strong impact on
age control, and current limitation and control) for two- the stability margins and dynamics of grid-forming power
level voltage-source converters that track a voltage reference converters [34]. While numerous different strategies have been
provided by a reference model (i.e., grid-forming control). proposed to limit the ac current injection of voltage-source
Moreover, we propose a controller for the converter dc voltage converters with grid-forming controls [26], [33], [35]–[39],
that defines the reference dc current. Because their design is the problem of designing a robust ac current limitation strategy
independent of the choice of the reference model, we first that effectively reacts to the load-induced overcurrent and grid
discuss the cascaded voltage/current control and the dc-side faults is an open research problem. Moreover, complex current
control. Subsequently, we review four common grid-forming limitation strategies typically require careful tuning of the con-
control strategies. For each strategy, we describe the angle trollers. Therefore, to provide a clear and concise investigation
dynamics, frequency dynamics, and ac voltage magnitude of the behavior of the existing grid-forming control solutions,
regulation. Throughout this section, we will employ the three we use the simple ac current limiting strategy (7).
phase abc, αβ and dq-coordinates (see [25, Secs. 4.5 and 4.6] 3) AC Current Control: In order to implement this scheme,
for details on the transformations). We remind the reader that a PI controller for the current i s,dq = [i s,d i s,q ] is used to
the Simulink implementation of the controls presented in the
track ī s,dq
forthcoming subsections is available online [23].
ẋi,dq = ī s,dq − i s,dq, (8a)
A. Low-Level Cascaded Control Design
vs,dq := vdq + Z i s,dq + Ki, p i s,dq − i s,dq + Ki,i xi, dq (8b)
1) AC Voltage Control: We employ a standard converter
control architecture that consists of a reference model provid- feed-forward terms PI control
ing a reference voltage v̂dq with angle v̂dq = θ and magnitude ] is the
v̂dq (as it is illustrated in Fig. 5). The modulation signal where Z = LωJ2 + RI2 , vs,dq = [v s,d v s,q
mαβ is determined by cascaded proportional–integral (PI) reference for the switching node voltage (i.e., before output
controllers that are implemented in dq-coordinates (rotating filter in Fig. 1), xi,dq = [x i,d x i,q ] denotes the integrator
with the reference angle θ ) and track the voltage reference state, and Ki, p = k p,i I2 and Ki,i = ki,i I2 denote the diagonal
v̂dq (see [18]). The voltage tracking error v̂dq − vdq is used matrices of proportional and integral gains, respectively. Note
to compute the reference i s,dq i ] for the switching
= [i sd that the first two terms of the right-hand side of (6b) and (8b)
sq
node current i s,dq are feed-forward terms. Finally, the modulation signal mαβ is
given by
ẋv,dq = v̂dq − vdq (6a)
2vs,αβ
i s,dq := i dq + CωJ2 vdq + Kv, p (v̂dq −vdq )+Kv,i xv,dq (6b) mαβ =
v dc
(9)
feed-forward terms PI control
where xv,dq = [x v,d x v,q ] denotes the integrator state,
where vs,αβ
is the αβ-coordinates image of vs,dq defined in (8)
vdq = [v d v q ] denotes the output voltage measurement, denotes the nominal converter dc voltage.
and v dc
v̂dq = [v̂ d 0] denotes the reference voltage, i dq = [i d i q ]
denotes the output current, I2 is the 2-D identity matrix, and
Kv, p = kv, p I2 and Kv,i = kv,i I2 denote diagonal matrices of B. DC Voltage Control
proportional and integral gains, respectively. that is tracked by the control-
2) AC Current Limitation: We assume that the underlying The dc current reference i dc
current controller or low-level protections of the converter lable dc source (2) is given by a proportional control for the
limit the ac current. We model this in abstraction by scaling dc voltage and feed-forward terms based on the nominal ac
down the reference current i s,dq if it exceeds the predefined active power injection p and the filter losses
ac
converter current limit i max [33, Sec. III], that is
p v dc i x − p
i dc = kdc v dc − v dc + + G dc v dc + (10)
i , if i s,dq ≤ i max
ac
v
v dc
ī s,dq := s,dq (7) proportional control
dc
γi i s,dq, if i s,dq > i max
ac
power injection and loss feed-forward
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1008 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
Fig. 5. Block diagram of the low-level cascaded control design (6)–(8) in Fig. 7. Block diagram of a grid-forming VSM-based (13)–(15).
dq-coordinates rotating with the angle θ provided by the reference model.
Fig. 6. Droop control frequency and ac voltage control block diagrams based
on (11) and (12). Fig. 8. Matching control block diagram based on (16)–(18).
where v dc i x is the dc power flowing into the switches, p is the where D p (ω − ω) is commonly referred to as (virtual)
ac power injected into the grid, and the last term on the right- damping [8, Sec. II-B] and is inspired by the speed droop
hand side of (10) implements a feed-forward power control response of an SM. Note that the speed dependent term in
that compensates the filter losses. The loss compensation is (13b) has no exact analog in an SM. The response of SM
required to ensure exact tracking of the power reference by damper windings and its turbine governor are on different
matching control (see Section III-E) and also improves the dc timescales, and the SM damper windings do not act relative
voltage regulation for the other control strategies considered to the nominal frequency. In contrast, the speed dependent
in this study. Thus, to employ an identical dc voltage control, term in (13b) provides both instantaneous damping and at
we apply (10) for all control strategies discussed throughout steady state (i.e., equivalent to SM turbine governor droop)
this article. relative to the nominal frequency. Moreover, Jr is the virtual
rotor’s inertia constant. Note that the dynamics (13) reduce to
C. Droop Control droop control (11) when using Jr /D p ≈ 0 as recommended in
Droop control resembles the speed droop property (5a) of [8]. These angle dynamics capture the main salient features of
the SM governor [6] and trades off deviations of the power VSMs but do not suffer from drawbacks of more complicated
injection (from its nominal value p ) and frequency deviations implementations (see [4] for a discussion). The three-phase
(from ω ) voltage induced by the VSM is given by
θ̇ = ω (11a) 2π 4π
v̂abc = 2ωM f i f sin (θ ) sin θ − sin θ −
ω = ω + dω ( p − p) (11b) 3 3
(14)
where dω denotes the droop gain. To replicate the service
provided by the AVR of SMs, we use a PI controller acting where M f and i f are, respectively, the virtual mutual induc-
on the output voltage error tance magnitude and excitation current. Similar to (12), we uti-
t lize input i f to achieve exact ac voltage regulation via PI
v̂d = k p (v − vdq ) + ki (v − vdq (τ )) d τ. (12) control and thereby replicate the function of the AVR of an SM
0
kp ki t
to obtain the direct axis reference v̂ d for the underlying voltage if = (v − vdq ) + (v − vdq (τ )) d τ. (15)
loop (v and vdq are the reference and measured voltage Mf Mf 0
magnitudes). We remark that v̂ q = 0 and the reactive power Transforming v̂abc to dq-coordinates with θ and ω as in (13),
injection varies such that exact voltage regulation is achieved. the voltage and current loops and modulation signal generation
The droop control block diagram is shown in Fig. 6. remain the same as (6)–(9).
D. VSM
E. Matching Control
Many variations of VSMs have been proposed [7], [8].
Matching control is a grid-forming control strategy that
In this article, we consider the frequency dynamics induced
exploits structural similarities between power converters and
by the synchronverter [8] (see Fig. 7)
SMs [10]–[13], [40] and is based on the observation that
θ̇ = ω (13a) the dc-link voltage—similar to the SM frequency—indicates
1 power imbalances. Hence, the dc voltage, up to a constant
Jr ω̇ = ( p − p) + D p (ω − ω) (13b)
ω factor, is used to drive the converter frequency. This control
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1009
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1010 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1011
Fig. 11. Normalized distribution of the RoCoF |ω̇i |/|pi | of the SM frequency at node 1 for load disturbances pi ranging from 0.2 to 0.9 p.u. at node 7.
For each load disturbance, |ω̇i |/|pi | is normalized by the maximum value corresponding to the all-SMs configuration.
Fig. 12. Normalized distribution of the nadir ||ωi ||∞ /|pi | of the SM frequency at node 1 for load disturbances pi ranging from 0.2 to 0.9 p.u. at
node 7. For each load disturbance, ||ωi ||∞ /|pi | is normalized by the maximum value corresponding to the all-SMs configuration.
In this section, we analyze the response of the GFCs to large Figs. 14 and 15 highlight that the matching control succeeds
disturbances when the dc source is working close to its maxi- to stabilize the dc voltage despite the saturation of the dc
mum rated values. Specifically, we focus on the implications of source. The nature of matching control, which accounts for the
the dc current limit (3) to highlight the response of GFCs when dc-side dynamics while regulating the ac dynamics, i.e., (16),
interfacing curtailed renewable generation with low headroom results in increased robustness with respect to large distur-
(i.e., PV/wind) or a converter system with an undersized dc–dc bances. From a circuit-theoretic point of view, this is possible
converter stage. In such scenarios, the dc current limit can only if the sum of the ac power injection and filter losses
be activated independently of the ac current limit. For clarity equals the approximately constant dc power inflow v dc i maxdc .
of representation, we first focus exclusively on the matching The converter can inject constant ac power into the network
control as its angle dynamic (16) explicitly considers the dc only if its angle difference with respect to the remaining
voltage. Droop control, which does not consider the dc voltage, devices in the network is constant. In the presence of the
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1012 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
Fig. 14. DC current demand of the converter at node 2 (top) and its dc Fig. 17. DC voltage (top) and dc current demand (bottom) of the converter
voltage (bottom) after a 0.9-p.u. load disturbance. at node 2 after a 0.9-p.u. load disturbance when all the limitation schemes,
i.e., (3), (7), and (24) are active and τg = 5 s.
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1013
Fig. 18. DC voltage (top) and dc current demand (bottom) of the converter Fig. 19. DC current demand (top) and dc voltage (bottom) of the converter
at node 2 after a 0.9-p.u. load disturbance when both dc and ac limitation at node 2 after loss of the SM at node 1.
schemes (3) and (7) are active and τg = 1 s.
complementary benefits by using both dc and ac measurements
manipulates the grid-forming dynamics through their set points in grid-forming control.
such that the ac current magnitude stays within the admissible
limits for large increases in load. We emphasize that this F. Interaction of GFC and SM Dynamics
strategy aims at mitigating instabilities induced by large load The forthcoming discussion highlights that the interplay
increases and that the resulting GFC response to grid faults between the fast GFC and slow SM dynamics influences the
needs to be carefully studied. system stability. The following case studies are tightly related
For a 0.9-p.u. load increase, the current limitation strategy to the scenarios in Sections IV-D and IV-E.
(24) is able to stabilize the system with i thac = 0.9 p.u. and
1) Loss of SM: We study the response of GFCs when
γ p = 2.3( pb /i b ), where pb and i b denote the converter base
ac ac
disconnecting the SM at node 1, that is, the system turns into
power and current, respectively. Fig. 17 depicts the response an all-GFCs network. The implications of such a contingency
of the same GFC as in Fig. 16. Note that (24) effectively are threefold. First, the power injected by the machine, which
stabilizes the dc voltage for droop control, VSM, and dVOC. partially supplies the base load, is no longer available. Sec-
Moreover, in contrast to Fig. 14, after the postdisturbance ond, the stabilizing dynamics associated with the machine’s
transient, the dc source is no longer in saturation. Broadly governor, AVR, and PSS are removed from the system. Third,
speaking, this strategy succeeds to stabilize the system by the slow dynamics of the SM no longer interact with the fast
steering the GFC power injection away from the critical limits. dynamics of the GFCs.
However, this also influences the postdisturbance operating For this test, we set the base load to 2.1 p.u., and the SM and
point of the GFCs due to the threshold value being below GFCs set points are set to 0.6 and 0.75 p.u., respectively. Note
the rated value. that when the SM at node 1 is disconnected, the converters
Finally, we observe that the different timescales in a increase their power output according to the power sharing
low-inertia system contribute to the instabilities observed in behavior inherent to all four grid-forming controls (see the
Section IV-D. In particular, if the SM’s turbine responds Appendix). The resulting increase in the converter power
faster, GFCs with the standard limitation strategy (7) pre- injection to roughly 1.05 p.u. is similar to the load disturbance
serve stability—without the need to implement (24)—despite scenario used to illustrate the instability behavior of droop
the fact that transient dc and ac currents exceed the limits. control in Fig. 14. Fig. 19 shows i τ and v dc for the converter
Fig. 18 shows the GFCs responses when the SM turbine at node 2. Although the disturbance magnitude affecting the
delay τg is 1 s (see Fig. 16 where τg = 5 s). It can be converters is similar to the one in studied in Section IV-D, all
seen that the slow SM turbine dynamics again contribute GFCs remain stable after the loss of the SM without the need
to the system instability when dc and ac currents are satu- to incorporate (24). In particular, due to the absence of the slow
rated. We conclude that the presence of different timescales turbine dynamics and fast synchronization of the converters,
in a low-inertia system—often neglected in the literature dc for around 50 ms, while it remains
i τ exceeds the limit i max
[26], [33]–[39]—must be considered in designing a robust ac above the limit for a prolonged period of time in Fig. 14.
current limitation mechanism for the GFCs. This highlights the problematic interaction between the fast
Remark 2 (DC and AC Measurements): We observe that response of the GFCs and the slow response of the SM. While
using ac measurements to drive the angle dynamics, e.g., the SM perfectly meets classic power system control objectives
VSMs use active power measurements in (13), improves on slower timescales, the dominant feature of GFCs is their
the frequency performance of GFCs (see Figs. 11 and 12). fast response. However, the fast response of GFCs can also
On the other hand, using dc voltage measurements, e.g., result in unforeseen interactions with other parts of the system,
matching control (16), results in robustness with respect to dc such as the slow SM response (shown here), line dynamics (see
current limits. Further research is required to combine these [16], [29]), and line limits [43].
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1014 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1015
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1016 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
VI. S UMMARY AND F URTHER W ORK GFC control techniques and SM perform equal-load sharing.
In this article, we provide an extensive review of different Moreover, by selecting kdc based on this criteria, the dc voltage
grid-forming control techniques. Subsequently, we used the control gain in (10) is automatically set, which is identical for
IEEE nine-bus test system incorporating high-fidelity GFC all GFC implementation [23].
and SM models to investigate the performance of different Regarding the ac voltage regulation, the control gains in
control techniques and their interaction with SM. Our case (12), (15), (17), and (22b) are selected to regulate the ac
studies revealed that: 1) the presence of the GFCs improves voltage at approximately equal timescales. We refer to [46]
the frequency stability metrics compared to the baseline all- for details on tuning the cascaded inner loops presented in
SMs system; 2) under a sufficiently large load disturbance, it is Section III-A. It is noteworthy that the timescale of the
vital to implement an ac current limiting scheme to stabilize reference model (i.e., grid-forming dynamics) must be slower
the grid-forming techniques that only rely on the ac mea- than ac voltage control shown in Fig. 4 to ensure the optimal
surements; 3) matching control exhibits robustness to the dc performance. Similarly, the ac current control must be faster
source saturation since its angle dynamics takes into account than the outer voltage controller. Finally, the choice of virtual
the dc quantities; 4) we explored the stabilizing influence of inertia constant in (13b) can largely influence VSM’s dynamic
the ac current limitation; and 5) we investigated the behavior behavior. We adopted the recommendation J/D p = 0.02
of GFCs in response to the loss of SM and in all-GFCs system proposed in [8]. The parameters used in the implementation
highlighting a potentially destabilizing interaction between the [23] are reported in Table I.
GFCs and SMs dynamics. Moreover, we provided a qualitative
R EFERENCES
analysis of GFCs impact on frequency stability. Topics for the
[1] F. Milano, F. Dörfler, G. Hug, D. J. Hill, and G. Verbic, “Foundations
future works include: 1) further exploration of the impacts and challenges of low-inertia systems (invited paper),” in Proc. Power
of dc and ac current limitations on the GFCs behavior and Syst. Comput. Conf. (PSCC), Jun. 2018.
providing a formal stability analysis; 2) proposing a complete [2] P. W. Sauer and M. A. Pai, Power System Dynamics and Stability.
Upper Saddle River, NJ, USA: Prentice-Hall, 1998.
ac current limitation strategy that is robust to load-induced [3] P. Kundur, Power System Stability and Control. New York, NY, USA:
overcurrent as well as grid faults; 3) the seamless transition McGraw-Hill, 1994.
between grid-forming and grid-following operations; and 4) [4] A. Tayyebi, F. Dörfler, F. Kupzog, Z. Miletic, and W. Hribernik, “Grid-
forming converters-inevitability, control strategies and challenges in
blending of the different control strategies into a controller future grids application,” in Proc. CIRED Workshop, 2018.
that achieves their complementary benefits. [5] High Penetration of Power Electronic Interfaced Power Sources
(HPOPEIPS) ENTSO-E Guidance Document for National Implemen-
A PPENDIX tation for Network Codes on Grid Connection, ENTSO-E, Brussels,
T UNING C RITERIA Belgium, 2017.
[6] M. Chandorkar, D. Divan, and R. Adapa, “Control of parallel connected
The load-sharing capability of the control techniques pre- inverters in standalone AC supply systems,” IEEE Trans. Ind. Appl.,
sented in Section III is investigated in [4], [7], and [15]. vol. 29, no. 1, pp. 136–143, Jan. 1993.
[7] S. D’Arco, J. A. Suul, and O. B. Fosso, “A virtual synchronous
Considering a heterogeneous network consisting of several machine implementation for distributed control of power converters in
GFCs (with different control) and SMs, we tune the control smartgrids,” Electr. Power Syst. Res., vol. 122, pp. 180–197, May 2015.
parameters such that all the units exhibit identical proportional [8] Q.-C. Zhong and G. Weiss, “Synchronverters: Inverters that mimic
synchronous generators,” IEEE Trans. Ind. Electron., vol. 58, no. 4,
load-sharing in steady state. For the SM- and droop-controlled pp. 1259–1267, Apr. 2011.
GFCs, (5a) and (11b) can be rearranged to [9] Q.-C. Zhong, P.-L. Nguyen, Z. Ma, and W. Sheng, “Self-synchronized
synchronverters: Inverters without a dedicated synchronization unit,”
1
ω − ω = ( p − p ) (29a) IEEE Trans. Power Electron., vol. 29, no. 2, pp. 617–630, Feb. 2014.
dp [10] I. Cvetkovic, D. Boroyevich, R. Burgos, C. Li, and P. Mattavelli, “Mod-
eling and control of grid-connected voltage-source converters emulating
ω − ω = dω ( p − p ). (29b) isotropic and anisotropic synchronous machines,” in Proc. IEEE 16th
Workshop Control Modeling Power Electron. (COMPEL), Jul. 2015.
For VSM, assuming steady-state frequency and setting [11] C. Arghir, T. Jouini, and F. Dörfler, “Grid-forming control for power
θ̈ = ω̇ = 0 in (13b) results in converters based on matching of synchronous machines,” Automatica,
vol. 95, pp. 273–282, Sep. 2018.
1
ω − ω = ( p − p ). (30) [12] S. Curi, D. Gross, and F. Dörfler, “Control of low-inertia power grids:
D p ω A model reduction approach,” in Proc. IEEE 56th Annu. Conf. Decis.
Control (CDC), Dec. 2017, pp. 5708–5713.
For matching control, we assume that in steady state, i dc ≈ i dc [13] C. Arghir and F. Dorfler, “The electronic realization of synchronous
and v dc /v dc ≈ 1. Setting ω̇ = 0 in (19b) and replacing i dc by machines: Model matching, angle tracking, and energy shaping tech-
niques,” IEEE Trans. Power Electron., vol. 35, no. 4, pp. 4398–4410,
the expression from (10) yield Apr. 2020.
kθ [14] M. Sinha, F. Dorfler, B. B. Johnson, and S. V. Dhople, “Uncovering
ω − ω = ( p − p ). (31) droop control laws embedded within the nonlinear dynamics of Van
kdc v dc der Pol oscillators,” IEEE Trans. Control Netw. Syst., vol. 4, no. 2,
pp. 347–358, Jun. 2017.
Finally, for dVOC, assuming v̂ dq ≈ v in steady state, [15] M. Colombino, D. Groz, J.-S. Brouillon, and F. Dorfler, “Global phase
the angle dynamics (22a) becomes and magnitude synchronization of coupled oscillators with application
η to the control of grid-forming power inverters,” IEEE Trans. Autom.
ω − ω = 2 ( p − p ). (32) Control., vol. 64, no. 11, pp. 4496–4511, Nov. 2019.
v [16] D. Gros, M. Colombino, J.-S. Brouillon, and F. Dorfler, “The effect
Hence, for any given droop gain d p , if dω , D p , kdc and η are of transmission-line dynamics on grid-forming dispatchable virtual
oscillator control,” IEEE Trans. Control Netw. Syst., vol. 6, no. 3,
selected such that the slopes of (29)–(32) are equal, all the pp. 1148–1160, Sep. 2019.
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
TAYYEBI et al.: FREQUENCY STABILITY OF SMs AND GRID-FORMING POWER CONVERTERS 1017
[17] G.-S. Seo, M. Colombino, I. Subotic, B. Johnson, D. Gros, and [38] I. Sadeghkhani, M. E. Hamedani Golshan, J. M. Guerrero, and
F. Dorfler, “Dispatchable virtual oscillator control for decentralized A. Mehrizi-Sani, “A current limiting strategy to improve fault ride-
inverter-dominated power systems: Analysis and experiments,” in Proc. through of inverter interfaced autonomous microgrids,” IEEE Trans.
IEEE Appl. Power Electron. Conf. Expo. (APEC), Mar. 2019. Smart Grid, vol. 8, no. 5, pp. 2138–2148, Sep. 2017.
[18] N. Pogaku, M. Prodanovic, and T. C. Green, “Modeling, analysis and [39] A. D. Paquette and D. M. Divan, “Virtual impedance current limiting
testing of autonomous operation of an inverter-based microgrid,” IEEE for inverters in microgrids with synchronous generators,” IEEE Trans.
Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007. Ind. Appl., vol. 51, no. 2, pp. 1630–1638, Aug. 2015.
[19] F. Paganini and E. Mallada, “Global analysis of synchronization per- [40] L. Huang et al., “A virtual synchronous control for voltage-source
formance for power systems: Bridging the theory-practice gap,” IEEE converters utilizing dynamics of DC-link capacitor to realize self-
Trans. Autom. Control., to be published. synchronization,” IEEE J. Emerg. Sel. Topics Power Electron., vol. 5,
[20] M. Pirani, J. W. Simpson-Porco, and B. Fidan, “System-theoretic no. 4, pp. 1565–1577, Dec. 2017.
performance metrics for low-inertia stability of power networks,” in [41] F. Milano and A. Ortega, “Frequency divider,” IEEE Trans. Power Syst.,
Proc. IEEE 56th Annu. Conf. Decis. Control (CDC), Dec. 2017, vol. 32, no. 2, pp. 1493–1501, May 2017.
pp. 5106–5111. [42] A. Crivellaro et al., “Beyond low-inertia systems: Massive integra-
[21] Frequency Measurement Requirements and Usage, RG-CE Syst. Protec- tion of grid-forming power converters in transmission grids,” 2019,
tion Dyn. Sub Group, Brussels, Belgium, 2018. arXiv:1911.02870. [Online]. Available: https://arxiv.org/abs/1911.02870
[43] “Queensland and South Australia system separation on 25 August 2018,”
[22] B. K. Poolla, D. Gros, and F. Dorfler, “Placement and implementation
Austral. Energy Market Operator, Melbourne, VIC, Australia, Tech.
of grid-forming and grid-following virtual inertia and fast frequency
Rep., 2019. [Online]. Available: https: //www.aemo.com.au/-/media/
response,” IEEE Trans. Power Syst., vol. 34, no. 4, pp. 3035–3046,
Files/Electricity/NEM/Market_Notices_and_Events/Power_System_
Jul. 2019.
Incident_Reports/2018/Qld—SA-Separation-25-August-2018-Incident-
[23] A. Tayyebi, D. Groß, and A. Anta. (2019). GridFormingConvert- Report.pdf
ers: Implementation of Grid-Forming Control Techniques in IEEE 9- [44] G. Peponides, P. Kokotovic, and J. Chow, “Singular perturbations and
Bus System. Git Repository. [Online]. Available: https://github.com/ time scales in nonlinear models of power systems,” IEEE Trans. Circuits
ATayebi/GridFormingConverters Syst., vol. CS-29, no. 11, pp. 758–767, Nov. 1982.
[24] U. Markovic, O. Stanojev, E. Vrettos, P. Aristidou, and G. Hug, [45] L. Sigrist, I. Egido, and L. Rouco, “Principles of a centralized UFLS
“Understanding stability of low-inertia systems,” 2019, engrXiv preprint. scheme for small isolated power systems,” IEEE Trans. Power Syst.,
[Online]. Available: http://engrxiv.org/jwzrq vol. 28, no. 2, pp. 1779–1786, May 2013.
[25] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Sys- [46] T. Qoria, F. Gruson, F. Colas, X. Guillaud, M.-S. Debry, and T. Prevost,
tems: Modeling, Control, and Applications. Hoboken, NJ, USA: Wiley, “Tuning of cascaded controllers for robust grid-forming voltage source
2010. converter,” in Proc. Power Syst. Comput. Conf. (PSCC), Jun. 2018.
[26] G. Denis, T. Prevost, M.-S. Debry, F. Xavier, X. Guillaud, and A. Menze,
“The Migrate project: The challenges of operating a transmission grid
with only inverter-based generation. A grid-forming control improve-
ment with transient current-limiting control,” IET Renew. Power Gener.,
vol. 12, no. 5, pp. 523–529, Apr. 2018.
[27] IEEE Recommended Practice for Excitation System Models for Power Ali Tayyebi received the B.Sc. degree in elec-
System Stability Studies, IEEE Standard 421.5, 2016. trical engineering from the University of Tehran,
[28] R. D. Zimmerman, C. E. Murillo-Sanchez, and R. J. Thomas, “MAT- Tehran, Iran, in 2012, the M.Sc. degree in engi-
POWER: Steady-state operations, planning, and analysis tools for power neering mathematics (Joint MATHMODS Program)
systems research and education,” IEEE Trans. Power Syst., vol. 26, no. 1, from the University of L’Aquila, L’Aquila, Italy,
pp. 12–19, Feb. 2011. and the University of Hamburg, Hamburg, Germany,
[29] P. Vorobev, P.-H. Huang, M. Al Hosani, J. L. Kirtley, and K. Turitsyn, in 2014, and the M.Sc. degree in sustainable trans-
“High-fidelity model order reduction for microgrids stability assess- portation and electric power systems (Joint STEPS
ment,” IEEE Trans. Power Syst., vol. 33, no. 1, pp. 874–887, Program) from the Sapienza University of Rome
Jan. 2018. (La Sapienza), Rome, Italy, the University of Not-
[30] V. Purba, S. V. Dhople, S. Jafarpour, F. Bullo, and B. B. Johnson, tingham, Nottingham, U.K., and the University of
“Reduced-order structure-preserving model for parallel-connected three- Oviedo, Oviedo, Spain, in 2016. He is currently pursuing the Ph.D. degree
phase grid-tied inverters,” in Proc. IEEE 18th Workshop Control Mod- with the Austrian Institute of Technology (AIT), Vienna, Austria, and the
eling Power Electron. (COMPEL), Jul. 2017. Automatic Control Laboratory, Swiss Federal Institute of Technology (ETH),
[31] M. M. S. Khan, Y. Lin, B. Johnson, V. Purba, M. Sinha, and S. Dhople, Zürich, Switzerland, with a focus on the design of grid-forming converter
“A reduced-order aggregated model for parallel inverter systems with control for low-inertia power systems.
virtual oscillator control,” in Proc. IEEE 19th Workshop Control Mod- In 2016, he joined AIT as an M.Sc. thesis candidate and then as a Research
eling Power Electron. (COMPEL), Jun. 2018. Assistant. His main research interests are the nonlinear systems and control
[32] V. Purba, B. B. Johnson, M. Rodriguez, S. Jafarpour, F. Bullo, and theory with applications to power systems.
S. V. Dhople, “Reduced-order aggregate model for parallel-connected Mr. Tayyebi was a recipient of the EU Scholarship for master studies from
single-phase inverters,” IEEE Trans. Energy Convers., vol. 34, no. 2, 2014 to 2016.
pp. 824–837, Jun. 2019.
[33] M. G. Taul, X. Wang, P. Davari, and F. Blaabjerg, “Current limiting
control with enhanced dynamics of grid-forming converters during fault
conditions,” IEEE J. Emerg. Sel. Topics Power Electron., to be published.
[34] H. Xin, L. Huang, L. Zhang, Z. Wang, and J. Hu, “Synchronous Dominic Groß (Member, IEEE) received the
instability mechanism of P-f droop-controlled voltage source converter Diploma degree in mechatronics and the Ph.D.
caused by current saturation,” IEEE Trans. Power Syst., vol. 31, no. 6, degree in electrical engineering from the University
pp. 5206–5207, Nov. 2016. of Kassel, Kassel, Germany, in 2010 and 2014,
[35] X. Wang, Y. W. Li, F. Blaabjerg, and P. C. Loh, “Virtual- respectively.
impedance-based control for voltage-source and current-source convert- He was with the Research Division, Volkswa-
ers,” IEEE Trans. Power Electron., vol. 30, no. 12, pp. 7019–7037, gen Group, Wolfsburg, Germany, from 2014 to
Dec. 2015. 2015. From 2016 to 2019, he was a Post-Doctoral
[36] Q.-C. Zhong and G. C. Konstantopoulos, “Current-limiting droop control Researcher with the Automatic Control Laboratory,
of grid-connected inverters,” IEEE Trans. Ind. Electron., vol. 64, no. 7, ETH Zürich, Zürich, Switzerland. He is currently
pp. 5963–5973, Jul. 2017. an Assistant Professor with the Department of Elec-
[37] A. Gkountaras, S. Dieckerhoff, and T. Sezi, “Evaluation of current trical and Computer Engineering Department, University of Wisconsin–
limiting methods for grid forming inverters in medium voltage micro- Madison, Madison, WI, USA. His research interests include distributed control
grids,” in Proc. IEEE Energy Convers. Congr. Expo. (ECCE), Sep. 2015, and optimization of complex networked systems with applications in power
pp. 1223–1230. systems dominated by power electronic devices.
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.
1018 IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, VOL. 8, NO. 2, JUNE 2020
Adolfo Anta received the Licenciatura degree Florian Dörfler (Member, IEEE) received the
from the ICAI Engineering School, Madrid, Spain, Diploma degree in engineering cybernetics from the
in 2002, and the M.Sc. and Ph.D. degrees from University of Stuttgart, Stuttgart, Germany, in 2008,
the University of California at Los Angeles, Los and the Ph.D. degree in mechanical engineering from
Angeles, CA, USA, in 2007 and 2010, respectively. the University of California at Santa Barbara, Santa
From 2002 to 2005, he was a Design Engineer with Barbara, CA, USA, in 2013.
Airbus, Madrid. From 2010 to 2012, he was a Post- From 2013 to 2014, he was an Assistant Professor
Doctoral Researcher with the Technical University with the University of California at Los Angeles,
of Berlin, Berlin, Germany, and the Max Planck Los Angeles, CA, USA. He is currently an Associate
Institute, Berlin. From 2012 to 2018, he was a Professor with the Automatic Control Laboratory,
Lead Researcher with GE Global Research Europe, ETH Zürich, Zürich, Switzerland.
Münich, Germany. He is currently a Research Engineer with the Austrian Dr. Dörfler’s students were the winners or finalists for the Best Student Paper
Institute of Technology (AIT), Vienna, Austria. His research interests cover Awards at the 2013/2019 European Control Conference, the 2016 American
a wide range of control applications, in particular stability issues in power Control Conference, and the 2017 PES PowerTech Conference. His articles
systems. received the 2010 ACC Student Best Paper Award, the 2011 O. Hugo Schuck
Dr. Anta received the Fulbright Scholarship in 2005, the Alexander von Best Paper Award, the 2012–2014 Automatica Best Paper Award, and the
Humboldt Fellowship in 2011, was a Finalist for the Student Best Paper Award 2016 IEEE Circuits and Systems Guillemin-Cauer Best Paper Award. He was a
at the IEEE Conference on Decision and Control in 2008, and received the recipient of the 2009 Regents Special International Fellowship, the 2011 Peter
2010 EMSOFT Best Paper Award and the IEEE CSS George S. Axelby Award J. Frenkel Foundation Fellowship, and the 2015 UCSB ME Best PhD Award.
in 2011.
Authorized licensed use limited to: SHIBAURA INSTITUTE OF TECHNOLOGY. Downloaded on April 04,2024 at 13:51:05 UTC from IEEE Xplore. Restrictions apply.