M D B - Model

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

OUT GOING TO NEARST FEEDER OUT GOING TO NEARST FEEDER OUT GOING TO NEARST FEEDER OUT GOING TO NEARST

OUT GOING TO NEARST FEEDER OUT GOING TO NEARST FEEDER OUT GOING TO NEARST FEEDER

RING MAIN UNIT RING MAIN UNIT

SECENARIO OF OPERATION :
devices
cases Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9
normal operation ON ON ON ON OFF OFF OFF ON ON
Q1 out OFF ON ON ON ON OFF OFF ON ON
Q2 out ON OFF ON ON ON OFF OFF ON ON
Q3 out ON ON OFF ON OFF ON OFF ON ON
Q4 out ON ON ON OFF OFF ON OFF ON ON
Q1 & Q4 out OFF ON ON OFF ON ON OFF ON ON
Q2 & Q3 out ON OFF OFF ON ON ON OFF ON ON
Q1 & Q2 out
or OFF OFF OFF OFF ON OFF ON OFF OFF
Q3 & Q4 out

(ELECTRICAL INTERLOCK) B.C


(2 OUT OF 3)

Q4 Q3
Q6

T.R02 T.R01
1500 KVA 1500 KVA
22KV/380-220V,50 HZ 22KV/380-220V,50 HZ
DY11,+- 2.5%, +- 5% DY11,+- 2.5%, +- 5%
DRY TYPE DRY TYPE

BACKUP
GENERATOR G2
1500KVA TAP OFF

380V/220V, 4 WIRES, 50Hz.

BUS BAR RATING=3000A


PHASES+N+E

LOCATION : PUMP ROOM

CONTROL PANEL
FOR FIRE PUMP
( REFER TO SANITARY WORKS)

C.B(F.P)
1000
MCCB
with over load devis adjusted at 1.05 of the rated current
BUS BAR RATING=3000A BUS BAR RATING=3000A
PHASES+N+E PHASES+N+E

VOLTAGE,CURRENT
Q7
VOLTAGE,CURRENT VOLTAGE,CURRENT Q1
,P.F,KWH,KW, DIGITAL
METERING ,P.F,KWH,KW, DIGITAL
METERING
Q2 ,P.F,KWH,KW, DIGITAL
METERING
,KVAR,KVA,...ETC ,KVAR,KVA,...ETC ,KVAR,KVA,...ETC

Q5

Q9 Q8 Project Code Area / Location Initiator Trade Document Type Serial Number Revision Sheet Color
Sheets :
Annexes :
B&W
Document type : Sheet Size Scale
A0

Contractor Reference Number: Initiator Reference Number:

Review Response by Employer

Code A No Comments Code B Comments, No Re-submital

Code C Resubmit according to Comments Code D Rejected Code E For Information

Name: .............................. Signature: .............................. Date: ..............................

REV. DATE DESCRIPTION PRE. CHK. APP.