1B 1Y 3 1B 2B < 1B 2Y ok
8 Winding Resistance Test : ( Injected Current Amps ) , Temp: 42 C ( at LV Side Inj. Current A)
Tap HV Side wdg. Res. In ohm LV wdg. Res. In mili - ohms (Resi.Value in mW)
No. R-Y Y-B B-R r-y y-b b-r r-n y-n b-n
1 4.774 4.778 4.780
2 4.646 4.650 4.651
3 4.518 4.519 4.520
4 4.389 4.392 4.393
5.410 5.400 5.500 2.750 2.720 2.810
5 4.258 4.260 4.261
6 4.130 4.132 4.134
7 3.999 4.000 4.002
3 4.527 4.525 4.523
TRFR BDV : WTI CT INJ.Current WTI CT Ratio WTI CT Actual Measured Current
60 KV
Remarks : Transformer Found Healthy
Sujit Nath
Tested By :
TATA STEEL UISL - PSD