to low energy building. After all, what’s the point of our industry spending time, effort
and money on making supposedly low energy buildings if we don’t check how they’re EDITORIAL
actually performing. Is it because we won’t like what we discover?
EDITOR:
Looking at Ireland and the UK’s energy standards for new buildings, Ireland appears to take the Jeff Colley
E: jeff@passivehouseplus.ie
view that it’s best to aim high (in the case of dwellings at least) but not monitor how the resultant
buildings are actually performing, while the UK is instead aiming much lower but is actually
monitoring performance. Really, given how high the stakes are in terms of climate change, energy
supply and the needless running costs and discomfort of sub-standard buildings, we need to be DEPUTY EDITOR:
Lenny Antonelli
aiming to design and build ultra low energy buildings, and we need to monitor those buildings – E: lenny@passivehouseplus.ie
or representative samples of those buildings – to see whether the approaches we try out actually
work or not, and to feed that information back into how we legislate, design and build.
Calculated and actual performance can differ wildly, for a variety of reasons, and we shouldn’t REPORTER:
John Hearne
assume that buildings with energy performance calculated to comply with building regulations E: john@passivehouseplus.ie
will actually perform to those levels. Sadly we have no reason to expect this to be the case. For
its part the Westminster government recognises that a significant performance gap exists between
designed and actual energy use of notionally low energy buildings in the UK, and although its
REPORTER:
regulations are much worse than Ireland’s on paper, the government has pledged to eliminate the
Kate de Selincourt
performance gap in England, stating that by 2020 90% of all new homes will perform as well as
or better than designed, with substantial and detailed analysis ongoing at present by the Zero
Carbon Hub to establish the causes of this gap. The Irish government appears not to share these
concerns. There hasn’t been an attempt since 2005’s still unpublished Energy Performance Survey
of Irish Housing to check whether the actual energy performance of new build homes corresponded to
the calculations. A cynic might argue that the widespread non-compliance with building regulations – CONTRIBUTORS
and, perhaps unsurprisingly, correspondingly higher than expected energy usage – noted in that Dr Benjamin Krick, Passive House Institute
Tom Dollard, Pollard Thomas Edwards
study, serves a powerful disincentive for the authorities to commission further research. Chris Parsons, Parsons + Whittley Architects
Paul McNally, PassivHaus Architecture Company
Philip Lee, Philip Lee Solicitors
And while to an extent poor performance may be down to non-compliance with regulations, there are
Anna Crowley, Philip Lee Solicitors
broader questions about some of the assumptions made in the regulations and more particularly
in the associated documents. I contend that it’s possible to satisfy Ireland’s technical guidance
documents or the UK’s approved documents – and therefore show prima facie compliance with UK SALES
the regulations – and still produce a building that fails. Some of the “natural” ventilation strategies Stephen Molyneux
that abound, coupled with ropey thermal bridging and airtightness performance are causes for E: stephen@passivehouseplus.co.uk
particular concern.
So it’s critical that we don’t just take a tick box approach to compliance, but actually design and READER RESPONSE
construct buildings that work – buildings underpinned with a sound theoretical basis and strong / IT
empirical evidence of actual performance. Part of the reason my company rebranded our magazine
Dudley Colley
from Construct Ireland to Passive House Plus was because of our conviction that the passive house E: dudley@passivehouseplus.ie
standard offers a tried and tested route to delivering ultra low energy, healthy, robust buildings. We’re
not saying that everyone should build a passive house, but we think we all have a lot to learn from ACCOUNTS
the principles and rigorous attention to both a priori and empirical data which underpin its approach.
Oisin Hart
E: oisin@passivehouseplus.ie
Regards,
the editor
ART DIRECTOR
Lauren Colley
E: lauren@passivehouseplus.ie
ph+ 3
6
contents
NEWS
18 BUILDING OR UPGRADING?
Passive House Plus is here to make your building more sustainable
20 COMMENT
26 26 INTERNATIONAL
This issue’s selection features ultra low energy buildings from Mexico,
Germany, New Zealand and Italy, and illustrates how widely the energy
efficiency specification can vary in different climate zones.
36 NEW BUILD
62 UPGRADE
76 INSIGHT
ph+ 5
passivehouse+ | Issue 9
News
First annual Heat Merchants conference
hears from industry experts
News
Saint-Gobain building academy to train 25,000 workers
Saint-Gobain, the building materials multinational,
has announced the launch of a new construction
skills academy for Dublin that will train 25,000
new construction workers over the next five
years.
presented with special recognition awards for The five-day long period of passive house ac-
“This is not a call to replace either SEAI’s Dwelling their pioneering work on passive house in Ireland. tivities concluded with the Passive House/NZEB
Energy Assessment Procedure (DEAP) or the Open Days tours of buildings built to the passive
European Energy Performance of Buildings Held in conjunction with UCD’s Earth Institute, house and low-energy standards throughout
Directive (EPBD). It is rather a proposition to the conference was part of five days of passive the country.
formally recognise the passive house standard house activities. A design charrette competition
as compliant with Part L of the Irish building was held on Wednesday and Thursday, 5 and
regulations. I do not believe that there is any 6 November, with nine teams from colleges around At this year’s See The Light conference, (l-r): PHAI
serious legal impediment to doing so.” Delegates Ireland competing to design a development to chairman Dr Shane Colclough, Pat Cox, PHAI board
at the conference also signed a petition calling the passive house standard, with Waterford member and architect Martin Murray, and Tomás
for the passive house standard to “be accepted in Institute of Technology emerging victorious. O’Leary of the Passive House Academy
ph+ 7
passivehouse+ | Issue 9
News
Electric Ireland to end feed-in tariff
Electric Ireland has announced that it will no
longer buy electricity from residential properties
generating electricity from renewable sources
such as solar and wind. The move has come
as a complete shock to companies trying to
build a market for solar panels producing
electricity on domestic roofs.
Corrections
Ecodan suitable for almost any situation. with an existing traditional boiler. To ease in-
stallation, fast on-site commissioning and log-
David McConnell, heating products manager ging is available via the pre-programmed SD
at Mitsubishi Electric Ireland, said: “We are card, and for the building owners, Ecodan
In the article ‘How to save social housing
constantly reviewing our line-up to ensure that can be controlled by the MELCloud Wi-Fi re-
blocks’ in issue eight, we wrongly quoted David
we deliver what the market wants. This new mote controller.
Williams of Eastlands Homes as saying: “The
model slots nicely into the range to ensure
residents in the maisonettes are the poorest
we can deliver renewable Ecodan heating to McConnell added: “As the heat pump market
people in our housing stock”. This was a mis-
almost any home in the country.” grows, installers are becoming aware of the
quote. His actual words were, “the maisonettes
different levels of technology and support
are the poorest in our housing stock”, and the
The new PUHZ-W112VHA model is a single available from manufacturers and here at Mit-
quote was from an article in Inside Housing
phase Harp database and MCS-certified 11.2kW subishi Electric, we are determined to con-
magazine, who we should have credited.
unit that shares the ability to cascade up to tinue to lead the way towards reliable renewable
six units of the same output, allowing Ecodan heating.” In the same issue, we wrongly attributed
systems to offer a capacity range from 5kW photography for the Riedberg school, youth
through to 84kW. The second Ecodan unit centre & gym in our ‘International Selection’
launched is a 4.5kW split unit which boasts an feature to Achim Große. The photographs were
impressive Harp database SPF of 440% - a in fact by Thomas Herrmann. We apologise
significant advantage in terms of attaining high (above right) the collector for a Mitsubishi Ecodan air- for these errors.
BER scores and achieving Part L compliance. source heat pump
passivehouse+ | Issue 9
News
Window design & fitting as important as
U-value — True Windows
Sligo-based low energy window supplier and
Photo: www.kelvingillmor.com
installer True Windows has advised anyone
installing new windows to think carefully about
the details of design and installation.
ph+ 9
passivehouse+ | Issue 9
News
Firebird boilers top Poor design &
install threaten
Harp database for HRV market —
ProAir
efficiency Galway-based heat recovery ventilation man-
ufacturer ProAir has warned that poor quality
both from the plans and also upon completion of design and installation poses a threat to the
the dwelling. Nicola Barry, technical manager HRV market in Ireland and the UK. The com-
at Firebird Heating Solutions, told Passive pany’s David McHugh told Passive House
House Plus that a typical package Firebird Plus that a lack of quality standards mean
supplies to achieve a highly efficiency heating systems are being improperly specified, de-
setup would include a high efficiency con- signed and installed. He said ProAir had
densing oil boiler, solar thermal and a wood been asked to advise on a number of build-
inset stove. Other options include range cookers, ings where these issues had led to inade-
wood gasification boilers or wood pellet boilers. quate ventilation, causing condensation and
mould.
Barry said Firebird’s engineering team, working
with BER assessors, has completed a vast “Quite a lot of print space has been allocated
number of assessments from new house plans to the common concepts attached to low energy
built to TGD L 2011, and these are achieving construction such as insulation, draught-proofing
at least an A3 rating with Firebird products as and the elimination of cold bridges, but relatively
the heating source. The company, based in little has been written on the other essential
County Cork has been manufacturing oil boil- component, heat recovery ventilation,” he
ers in Ireland for over 30 years, and has since said.
branched out into solar thermal and biomass
Irish boiler manufacturer Firebird Heating So- boilers. “In particular, HRV design and installation.
lutions has advised potential customers that The British building regulations Part F stipulates
it is possible to achieve excellent BERs and Barry said: “It is key that the design and build that all systems must be commissioned and
heating system efficiency while still going down team speak with the client on the various heat- the results furnished to building control. Because
the traditional route of installing an oil boiler. ing options available. It is the responsibility of of this, the Building Research Establishment
Firebird’s range of Enviromax condensing oil the team to ensure the client obtains the dwelling have published recommendations on com-
boilers offer the highest efficiencies of any they want and a key factor to this is that they missioning these systems, which indeed make
gas, oil or LPG boiler on SEAI’s Harp data- are given heat and comfort, especially when sense, but it is impossible to commission sys-
base, with various models occupying the top they require it. We are all aware that the regulations tems that have been improperly designed,
nine places on the list. require us to build more energy conscious houses specified and installed," he said.
with respect to insulation, heating and orientation.
The new Building Control (Amendment) Regula- At Firebird, we are confident that we are the McHugh said that while EN standards do exist
tions 2014 came into effect on 1 March, and best in our oil heating industry in Ireland and on the methodology for testing HRV systems,
one of the many additional sections to be en- that we have the best products to give you there are no standards on the proper speci-
forced is the completion of a BER assessment, the heat you need when you need it.” fication of these systems, or on suitable ducting
systems.
News
Aereco celebrates 30th birthday
Photos: © G. Satre/Aereco
On 17 October, Aereco SA, a global leader in The event was opened by Aereco CEO Marc for the UK & Ireland, said of the company’s
demand controlled ventilation, celebrated 30 Jardinier, who thanked all of those present in- new headquarters: “It secures Aereco’s growth
years in business and inaugurated its new cluding guests, customers, suppliers, subsidiaries, and development for the future here in the UK
18,000 square metre headquarters, research financial partners, regional development actors, and Ireland, and re-emphasises its commit-
facilities and manufacturing plant in Collégien, officials, and employees. Jardinier gave a his- ment to innovation and development with the
France. The event was attended by over 500 torical overview of the company since its birth in state-of-the-art research facilities it now houses
people from 20 different countries. Aereco’s 1984, expressing his pride at watching Aereco’s under one roof.”
UK and Ireland team were there, along with development over the last thirty years.
the other guests, for guided tours of the new (above) Aereco’s new headquarters in France, which
facilities and to join in the celebrations. Simon Jones, Aereco’s commercial director was designed by the architect Frank Tomassi
ph+ 11
passivehouse+ | Issue 9
News
Solas Bhríde centre picks up two sustainability awards
The Solas Bhríde centre in Co Kildare picked The M&E design was by Glenn Nunan of GNCE. by a Swedish OptiHeat underfloor heating system
up its second environmental award recently when Hotfoot supplied three Ice Stick hybrid heat which redistributes the solar gain within the
it won the prize for Sustainability Achievement pumps, which combine both air-source and building.
at the 2014 Fit Out Awards at the beginning of ground-source technology.
November. The award follows on from the project The underfloor heating pipes on the south side
picking up the prize for Sustainability Initiative The Ice Stick is primarily an air-source heat pump, of the development re-circulate heat absorbed
of the Year at the Construction Industry Awards “but when it’s very cold outside it can take ad- via passive solar gain throughout the whole
during the summer. ditional heat from the ground,” Jonathan Leonard underfloor heating network, further boosting the
of Hotfoot told Passive House Plus. efficiency of the system.
The building was designed by renowned eco-
logical architects Solearth, who describe Solas Leonard said that the system not only cost Hotfoot also supplied solar thermal panels at
Bhríde as “an education and retreat centre less in terms of capital investment compared the development, plus three Ecotank heat pumps.
dedicated to the teachings and memory of St to potential alternatives, but it is also largely The Ecotank captures heat from steam gen-
Brigid”. The centre is run by the Brigidine Sisters. maintenance free. Solas Bhríde features two erated within bathrooms and uses it to deliver
20kW Ice Stick heat pumps for the main building domestic hot water when solar isn’t available.
Solas Bhríde features an innovative, high-efficiency which comprises common areas, kitchens and
heating system supplied by Wicklow-based com- meeting rooms, and a third smaller Ice Stick for (above) Solearth’s award-winning Solas Bhríde centre
pany Hotfoot and installed by EL Mechanical. the two apartments. Heat from both is delivered in Kildare
News
Cork company launches
Irish-made thermally broken
window sills
A new Irish company is manufacturing window ment programme at the Rubicon Centre in CIT,
sills in County Cork designed to eliminate ther- and the South Cork Local Enterprise Office.
mal bridging at this critical building junction.
Founded by Patrick Beausang, Passive Sills “We’ve been manufacturing for about 18 months.
produces window sills and over sills from a I started off making them in my garage, and we
News
Hammond Roof & Energy secure Soltherm
EWI agency
Photo: Donal Murphy Photography
Dublin-based company Hammond Roof & Hammond also told Passive House Plus that
Energy has become the exclusive Irish agent Solix has also now launched Soltherm HD Ul-
for Solix Soltherm external wall insulation timate, an advanced new impact-resistent external
systems. The company’s Nick Hammond told insulation system. “It’s virtually indestructible,”
Passive House Plus that unlike most EWI he said, “because of the build-up of the renders
systems, the Soltherm HD Weather system and the meshes.”
can dry quickly in wet weather, giving it a dis-
tinct advantage on the Irish market. Soltherm incorporates Xtratherm platinum
EPS in all its systems as standard and is NSAI
“It’s not an acrylic system, it’s a silicone HD certified. Hammond comes from a background
system. It doesn’t depend on the atmosphere in the roofing industry, which his family has
to dry, it’s a chemical drying reaction,” he said. been in for four generations, and said this has
instilled in him a philosophy of quality work-
Hammond said many applicators won’t apply manship which has carried through to his in-
EWI renders between October and March be- sistence on working closely with quality applicators
cause weather conditions aren’t suitable. “But for Soltherm.
this system is waterproof within an hour of dry-
ing. It can be used in damp conditions,” he said. Hammond said his company will not simply
sell a product over the counter, but will only
He added that Soltherm has been tested for algaes, supply an entire system with the associated
lichens and mosses that grow in Ireland and the technical support and backup. Hammond Roof
UK, and that the nature of the system means & Energy also provides free training in Soltherm
these organisms simply can’t adhere to the render. to suitable tradespeople to ensure applicators
are properly skilled in installing the system.
“It’s a self cleaning system and you have no
algaes, mosses or lichens that will grow on
it,” he said, explaining that the nature of the (right) The new Department of Justice building in
silicone topcoat means it is being continuously Tipperary town –as featured on pp44-51 of this
rinsed clean by the rain. issue – used the Soltherm external insulation system.
passivehouse+ | Issue 9
News
Go rainscreen clad to protect building fabric — Elemental
More and more architects and specifiers are
choosing rainscreen cladding systems for the
protection they offer the building fabric, in ad-
dition to their aesthetic benefits, according to
Mark Walsh of architectural cladding supplier
Elemental.
The recent green paper on energy A key question is how Part L can be document, such works will, prima
policy in Ireland, published in May 2014, satisfied in practice. Although already facie, indicate compliance with the
suggests that Ireland reaching the EU in place for six years (Ed. – former requirements of Part L. The technical
target of a 20% reduction in energy use environment minister John Gormley guidance document itself further
by 2020 will deliver collective societal introduced 40% energy & carbon re- states that what is contained therein
savings valued at €2.36 billion. ductions and mandatory renewable is not mandatory, and that the adoption
energy systems in 2008) Part L obli- of design and construction approaches
As part of this economic and envi- gations and how they may be achieved other than those outlined in the technical
ronmental drive, the Building (Part L remains somewhat abstruse, particularly guidance document is not precluded
Amendment) Regulations 2011 aim to when it comes to the role of renewable provided that the relevant requirements
achieve 60% aggregate improvements energy. Many ambiguities remain in of Part L are complied with. This un-
over the 2005 standards in both the respect of alternative methods of doubtedly generates concern for those
energy performance and associated compliance to what is set out in the tasked with enforcing compliance
carbon emissions of new dwellings Part L technical guidance document. with Part L.
from 1 December 2011. Given that This applies most saliently in the case
residential energy represents over a of houses which are designed to the Ultimately, the objectives giving rise
quarter of final energy use, the passive house standard, where the to Part L and moreover, the theory
framework underpinning these targets sorts of specifications that result may behind the technical guidance document
has massive potential for Ireland. differ from those of buildings where are derived from principles of EU law.
SEAI’s Dwelling Energy Assessment Thus, it can be argued that a purposive
Procedure (DEAP) has played a more interpretation is required when as-
prominent role. certaining what must be achieved in
with the law. However they do not have the force of law. In
a manner of speaking, the text of Part
L sets out the letter of the law and the
shall introduce ‘appropriate measures’
to increase the share of all kinds of
energy from renewable sources in the
only “how to”” that this does not present the only
“how to”.
national measures relating to sub-
stantial increases in energy efficiency
and relating to cogeneration and to
Primary consideration must be given passive, low or zero-energy buildings.
to the law – every person to whom a This is supported by Recital 48 of
Part L plays a fundamental role in legislative instrument applies is the RES Directive, which states that
addressing climate change by setting under a legal duty to comply with it. in facilitating minimum levels for re-
out a methodology for achieving these The technical guidance document, newables in buildings, it may be ap-
targets. It does this by providing a however, is not a legislative instrument. propriate for member states to
balance of reducing energy demands As set out in article 7 of the Building provide that levels are achieved by
by implementation of energy saving Regulations 1997 the status of the incorporating a factor for energy
measures on the one hand, while at technical guidance document is such from renewable sources in meeting
the same time increasing the use of that, where works are carried out in the requirements of the 2002 Energy
renewables. accordance with the technical guidance Performance of Buildings Directive.
comment
Recital 19 of the RES Directive reminds
member states that in evaluating the
realisation of national targets set, the
optimal combination of energy effi-
ciency technologies with energy from
renewable sources should be taken
into account.
“Comparing Part L to
passive house is akin
to comparing apples
SEAI’s Deap software: a house that meets the energy & carbon targets under TGD L, but fails to hit
with elephants, as the the renewables target. Is Deap incorrect in asserting it fails to comply with Part L’s renewables
target, when the target is only expressed in the TGD, meaning alternative methods may be used?
ph+ 21
a passive house, which is built to a substantial measures to reduce the Conclusion
high energy efficiency specification energy consumption. In the meantime The first conclusion to arrive at must be
and requires less fossil energy to (i.e. before December 2014), if one that the Department of the Environment
start off with, would such a passive takes the approach (which is quite must update the technical guidance
house be deemed compliant with correct) that the technical guidance document and Part L itself. What is
Part L where it could be argued that is (as it suggests) no more than also clear is that someone constructing
a reasonable proportion of the energy mere guidance, one is left with inter- a passive house after 2014 should
consumption is provided by renewable preting what is a “reasonable propor- derive at least some of its energy from
energy sources but where the proportion tion” of renewable energy as renewable sources. However, the current
differs from the values set out in the required by Part L. regulations and technical guidance
technical guidance document? If this document if unaltered will be unen-
would not be the case, this certainly Apart from the immediate and obvious forceable as setting a “reasonable”
undermines the concept of the passive problem that Part L will, from December proportion will no longer be the correct
house. Building control authorities of this year be in breach of the RES test. Prior to December 2014 passive
are in the dark in relation to situations Directive as it should specify a mini- house builders can, with likely success
of houses built to standards differing mum and not a proportion, there are compare, either their percentage of
from the restrictive formula set out in perhaps two ways of approaching this. renewables to the percentage in the
the technical guidance document, It could be argued that the proportion technical guidance document or compare
which focuses on the application of of renewable energy to fossil fuels their net fossil fuel consumption to
assumptions contained therein. inherent in the technical guidance the estimated net fossil fuel set out
in the technical guidance document.
For those seeking to enforce Part L,
measures to reduce energy consumption” their own legal and other advice as
may be required. Philip Lee does not
accept responsibility for information
on third-party websites.
In this context it is useful to refer back document could also be applied to a
to the purpose of the RES Directive, passive house. Therefore, if a passive
which is the promotion of the use of house consumes 50% less primary 1Directive 2009/28/EC on the promotion of the use
energy from renewable sources in energy, then the “proportion” of re- of energy from renewable resources, which sets
order to achieve energy savings and newables set out in the technical mandatory national targets for the overall share
to reduce fossil fuel dependence. guidance document, namely 10 kWh/m2 of energy from renewable sources in gross final
consumption of energy.
The RES Directive requires member (heating) and 4 kWh/m2 (electrical 2Directive 2010/31/EU on the Energy Performance
states to introduce “appropriate meas- energy), should be reduced by 50% of Buildings (EPBD) (Recast) replaced Directive
ures” to increase the share of energy to 5 kWh/m2 and 2 kWh/m2 2002/91/EC on the Energy Performance of Buildings.
3Article 13 (4) of Directive 2009/28/EC.
from renewable sources in buildings, respectively.4 An alternative approach 4Ed. – this could be simplified by switching from a
including passive buildings. That re- to the same interpretation of “rea- kWh target to an equivalent percentage – perhaps
quirement was to be introduced in sonable” would be to look at the net a requirement that 10 or 15% of a building’s primary
energy demand be met with renewable energy
member states on or before 5 December balance of brown energy that is pro- sources, or a smaller percentage in the case of
2010. The use of “appropriate” in that duced in a standard house and com- microgeneration. Though the RES Directive re-
paragraph could have allowed (in the pare that to the net brown energy quires “minimum levels” of renewable energy, the
directive doesn’t stipulate that this must be a kWh
case of passive house) there to be no produced in a passive house. Pro- target, meaning Ireland could satisfy this requirement
minimum amount of renewable energy. vided that the net amount of fossil by setting an equivalent minimum percentage to
fuel being consumed in the passive the targets currently outlined in TGD L. This would
arguably satisfy the RES Directive requirements
However, the directive provides in house is less than that being con- better than an absolute kWh target, in that it would
the third sub-paragraph of article 4.3 sumed in a standard house then it address the requirements of article 13 to take into
that four years later, namely by 31 could be argued that any actual en- account national measures relating to substantial
increases in energy efficiency and relating to co-
December 2014 member states must ergy coming from renewable sources generation and to passive, low or zero-energy
require the use of minimum levels of would meet the “reasonable test”. building. In other words, it would ensure that a
energy from renewable sources in new Both of course are unsatisfactory. As minimum renewable energy target didn’t prevent
people from making buildings too energy efficient,
buildings and existing buildings sub- far as we understand there is no as there would be no pressure to keep the building’s
ject to major renovation. There is no ready system to accurately compare energy demand sufficiently and needlessly large
exemption. Accordingly, from December the primary energy consumed in a to ensure renewables could meet a kWh target. It
would also ensure that the renewables obligation
2014, even new passive houses must passive house compared to the primary doesn’t cause buildings to breach the requirements
have a minimum renewable energy. energy consumed in a traditional of Part L 3(a) that buildings be designed “to limit
house. It is our understanding that the calculated primary energy consumption and
related carbon dioxide (CO2) emissions insofar
From this it is clear that the current DEAP, which is produced by SEAI, is as is reasonably practicable”. If a client finds it
technical guidance document and a very rough and ready reckoner and “reasonably practicable” to go beyond the minimum
Part L will have to be updated before does not go into sufficient detail to energy and carbon reduction targets, but feels
compelled to make their building less efficient in
December 2014 to at least reflect the distinguish between an estimate of the order to satisfy an inflexible renewable energy
application of varying standards for actual energy consumption from a target, leading to net increases in fossil energy
different types of building specifications, house built to passive standards use, carbon emissions and energy bills, does the
fact that they’ve made the building less efficient
in particular to reflect a situation compared to a typical house designed than they found reasonably practicable not mean
where a building has already taken to TGD L 2011. that they are in breach of Part L3(a)?
How to close the performance gap
The gap between designed and real-life energy performance in new dwellings is a significant
threat to the UK’s plans to deliver zero carbon homes. Architect Tom Dollard describes research
by the Zero Carbon Hub to better understand this performance gap — and how to fix it.
The Zero Carbon Hub’s recent work with design review and SAP audits. This developed qualification schemes.
industry has found extensive evidence process was then supplemented on
of a considerable ‘performance gap’ a number of sites with on-site testing While the project did not specifically
between the energy use of new homes using thermography and air-testing look at the benefits of the passive
as-designed and the actual use of the across a selection of the plots. house methodology, the principles
completed building. This gap occurs can play a part in reducing the per-
when a home requires more energy The site inspections analysed several formance gap. The site inspections
than was predicted during its design, hundred elements of the buildings at and interviews have witnessed good
before taking into account the behaviour all stages of construction. Any deviations practice stemming from the passive
of occupants. from the design were fully documented house standard, and some of this
with good and poor practice noted, and has fed into the recommendations for
This gap represents a significant risk to graded in terms of impact on as-built industry and government. However at
the UK’s carbon reduction commitments. performance. The energy performance a larger scale, passive house projects still
It has the potential to result in higher was then analysed using SAP and suffer the same issues and demonstrate
than expected household energy bills, site findings to ascertain the gap in a significant performance gap.
undermining buyer confidence in new terms of KgCO2/m2 (% improvement
(low carbon) homes. As we approach over dwelling emission rate). This could Common problems are found at ground
the zero carbon homes target of 2016, be compared to the original SAP and floor and foundation junctions, where
housebuilders are producing higher energy performance certificate (EPC). insulation is inconsistent or missing
performing homes and need to be and significant thermal bridging occurs.
confident that they perform as intended. The review has identified 15 priority Other areas causing deviation from the
issues that require action to begin to design are poor installation of insulation,
address the performance gap. These incorrect window performance, optimistic
Taller Passive House, house standard. Herrera led the project along Heat recovery ventilation was not required either,
with Maris Igea, his partner at Inhab Sustainable just simple mechanical extract ventilation.
Mexico City Architecture.
Photos: Moritz Bernoully The team insulated the entire building envelope
One of the biggest challenges for the architects with EPS, and airtightness is provided by the
was the lack of a passive house supply chain, OSB along with Siga tapes and membranes.
Mexico’s first certified passive house is the retrofit in terms of skills or products, in Mexico. Contractors Now, a single electric heater is enough to heat
of a roof-top apartment in the country’s capital. had to be trained in passive house principles, the whole apartment.
This small space was originally built cheaply while experts travelled from overseas to advise
in 2007, mostly with plywood. on the build. The architects say: “A lot of collaborative work
took place, it involved a big effort and a deep
But while living in Germany, Mexican architect But in some ways, meeting the passive house commitment, and it was all worth it.” The finished
Alejandro Herrera trained in the principles of standard was easier in the warm Mexican climate. building is not just the first certified passive
energy efficient building. When he returned to The apartment achieves a space heating demand house building in Mexico, it’s also the first cer-
his homeland in 2011, he decided to upgrade of 15 kWh/m2/yr with double-glazing, with wall, tified passive residential building in all of Latin
the apartment — his home — to the passive roof and floor U-values of between 0.3 and 0.4. America.
international
ph+ 27
Day care building, glazing. thermally broken concrete frames.
Georg-August-University, The walls and ceilings were constructed from These external concrete elements are functional
Germany large, prefabricated concrete elements to minimise too: they provide seating at their bases, guard
the number of joints. The walls were externally rails for the roof, and static shading. The concrete
Photos: Jochen Stüber, Hamburg & Olaf Baumann, Hanover
insulated and the building is topped with a green frames also contain dynamic shades which
roof, while the earth-bermed surfaces help to can be pulled down in summer to control
Completed in 2010, this day centre for Göttingen reduce energy loss, too. The building achieved overheating and glare.
University was designed by Despang Architekten, an airtightness result of 0.43 ACH, comfortably
who describe it as a “hybrid of landscape and within the target for passive buildings, and has Passive solar gain is the building’s main heat
architecture”. The building’s north and west a space heating demand of 15 kWh/m2/yr. source, backed up by the campus-wide dis-
facades are earth-bermed, but the south facade trict heating and standalone water heaters.
forms a passive solar curtain-wall with views to The material palette inside — concrete, glass, During summer nights, the building is flushed
the outdoor playground and landscaping. This spruce wood, linoleum — was in part chosen to with cool air. But when the shades are up in
glazed facade is comprised of a timber-aluminium avoid off-gassing materials, and the concrete winter, the low sun penetrates deep inside to warm
post-and-beam structure with extensive triple- finishes are extended outside the building via up the thermally massive concrete structure.
international
ph+ 29
Whanau, Auckland, the clients made a game-changing request: that crete formwork. Meanwhile the airtight wrap
the dwelling meet the passive house standard. of the house is provided by a Proclima Intello
New Zealand vapour membrane.
Photos: Simon Devitt The windows were minimised on the south
side of the home — where they would lose Ventilation is provided by a Zehnder heat re-
heat in the southern hemisphere — and over- covery ventilation system, while an air source
New Zealand’s first certified passive house hangs were extended over the north-facing heat pump delivers hot water. The house also
started out typically enough: architect Darren glass to prevent overheating. has rainwater collection and solar photovoltaics.
Jessop was approached by Phillip and Carolyn
Ivanier, a couple wishing to build their first The roof and double-stud walls of this split-level On completion of the project, Jessop estimated
family home. They wanted a modern open-plan timber frame house are insulated with glass- that meeting the passive house standard
family dwelling, and a degree of separation wool, but in the subtropical climate of Auckland, adds around 10 to 12% to build costs in New
between the ‘adult’ and ‘child’ spaces. respective U-values of 0.37 and 0.23 were Zealand. But he says the occupiers will re-
enough to meet the passive house standard, as coup much more than this amount if they live
But with the design already settled, and prompted were double-glazed windows. Below ground in the house over its lifetime — while enjoying
by New Zealand’s low building insulation standards, level, the basement walls are of insulated con- a warm, comfortable, healthy home.
Image: Ken Nguyen
international
ph+ 31
international
ph+ 33
international
Passive solar gain and heat recovery ventilation And as one of its architects, Arthur Pichler
are the main sources of space heating. There is had special motivation to get the house right:
also a small Windhager wood pellet boiler that he lives on the lower floors with his young
provides hot water, and can deliver heat through family, while his parents live upstairs.
the ventilation system in the coldest weather.
ph+ 35
Sleek-and-striking
passive house
graces eco-village
The eco-village at Cloughjordan, Co Tipperary is no stranger to low energy buildings, and with this passive
house, architect Paul McNally set out to prove that energy efficiency and good architecture go hand-in-hand.
For me there was a strong wish with this house of this passive house from our current per- what was being planned. I also took the opportunity
to produce a design that would demonstrate spective. It’s safe to say that we are in a very to set up a stall at the event describing my profes-
that achieving the passive house standard different place in mid 2014 economically, to where sional services. From that event, I was lucky
was not an impediment to good architecture. we were when this house was being built in enough to pick up three clients in the eco-vil-
Two years ago, at the Better Building conference 2009 and 2010. At that stage, the wheels had lage for whom I would go on to design homes.
in Dublin, one of Ireland’s leading educators just fallen off the wagon in the Irish construction Fiona’s is the only one constructed to date, as
of young architects argued that great architecture sector. It was a frightening time to procure a changing circumstances in those turbulent times
should be exempt from energy efficiency reg- building. For those of us young enough for it to prevented the others from going ahead. Fiona
ulations, because having to comply would ex- be our first recession, it brought new challenges was fortunate enough to be able to proceed.
cessively interfere with the expression of his that we had never experienced before.
architecture. It is tragic to think that a great ar- Since setting up my practice in 2004, I have always
chitect believes he cannot accommodate robust This project was completed in late 2010 and appreciated the passive house approach to
detailing within his artistic objective. early 2011, and as I reacquaint myself with the construction, and initially strived unsuccessfully
project file for the purpose of researching this through bad luck and inexperience to take early
We can only counteract this attitude by proving it article, I see that most of the companies and per- potentially passive projects to completion. There
wrong. I think it is incumbent on clients and sonalities involved are no longer in business. are many interpretations of what kind of build-
designers of passive houses to ensure that Some got into difficulty during this project, and ing is most appropriate for addressing the en-
only the highest standard of design is achieved others have wound up since its completion. vironmental issues facing us. Some people
in passive buildings. A passive house certificate choose to place emphasis on the sourcing of
is not a substitute for good architecture. Sustainable Fiona Nolan, the client and owner of this house, materials, on breathability, natural ventilation,
buildings which are aesthetically poor create is one of the members of the eco-village at recycled components, local materials and avoiding
an example to be used by those who are not Cloughjordan, Co Tipperary. I met Fiona at the certain substances, etc. The eco-village has a
inclined to produce low-energy buildings, and Cultivate sustainability centre in Dublin in 2007, charter which obliges all members to address
want an excuse. Therefore high performance where she attended a planning day for the these issues and more.
buildings must also be beautiful. eco-village members. At the time, I was con-
sidering becoming a member myself, and had I was fortunate enough to find in Fiona a client
It’s interesting to take a look back at the story started attending some events to get a feel for who had the intention and means to get this
new build
ph+ 37
new build
project over the line. Fiona and I agreed that than site-insulated open-panel systems. The
energy efficiency was a primary concern and insulation is protected from the risk of getting
so the brief from day one was to aim for passive wet also.
house certification if possible, in excess of the
standard required in the charter. While the house The wall cassettes were then clad on-site with
has not been certified, it can be when the client Gutex wood fibre insulation externally, which
chooses to, as it has met all the requirements. eliminates thermal bridges, and an internal
service cavity was further insulated. External
The architect Louis Sullivan famously asserted render was applied to a vented Aquapanel
that ‘form follows function’. The design for this rainscreen. The roof and balcony construction
project emerged from a direct response to the were similar, with a vented air layer under the
site. I think tight, difficult sites, are actually the waterproof layer again offering a very robust
easiest to design for, because the difficulties way of dealing with moisture in the construc-
force a pragmatic response. My worst nightmare tion, which was breathable.
is to have to design a building for a greenfield,
blank canvas site. The literally endless possi- The eco-village has a district heating system,
bilities would make it very tough to decide which fired by a communal wood chip boiler and backed
way to go. In this case, the requirement to up with a solar array. The district heating is
provide southern aspect glazing for heat gain not working at its optimum yet, as it is designed
potentially conflicted with the entrance ap- for the full build-out of the development, which
proach, meaning privacy would be an issue. I re- is perhaps just over half occupied at the mo-
solved this by introducing a diagonal screen ment. The system supplies a large thermal
wall and hiding the living spaces behind it. store buffer tank in the plant room once or twice
The curve in plan draws the visitor towards a day, from which a heat exchanger draws
the front door, away from the large window heat and tops up the heat recovery ventilation
behind the screen wall. system.
The rest of the plan is generated by the very On top of the standing charge, the client has
efficient planning device of creating a central reported around €100 per annum heating costs.
stairwell and circulation space about which all At the 2013 NZEB (nearly zero energy building)
the rooms revolve. The logic of the plan allows Open Doors event, Fiona noted the house does
the living, dining and kitchen space to enjoy the not overheat, despite omission of the solar
west aspect, which means evening light and shading as a cost-saving measure, and maintains
sunsets can be appreciated from here and comfortable temperatures without a backup
the master bedroom upstairs, which has an heating system. There are no radiators, although
indented balcony. we plumbed a heating circuit in just in case.
There was originally intended to be a stove in
Incredible attention was paid to giving what the living room which was also omitted. I have
appears to be a relatively simple elevation an learned from this and subsequent passive
intrinsic harmony. The principles of the golden projects to be confident about what you leave
section, and the harmonic system of proportion, out. If your heat load is telling you that you don’t
were used to underpin the setting out and di- need a back-up heating system or central heat-
mensions of the facade. The dotted lines (‘traces ing, don’t put one in.
régulataire’ as Le Corbúsier called them) in the
elevation show where the golden section or A word of warning is that while on this project
square proportion was used to establish order. the OSB airtightness layer worked, it hasn’t for
some other practitioners, so I would recommend
The airtightness layer is the OSB board which you use the new products on the market which
has been taped and sealed with mainly Pro Clima give guaranteed results. We have also found
tapes. A Solitex membrane was used to give that on completion, some clients have found
continuity between ground and first floors by it difficult to obtain competitive house insurance
wrapping around the first floor cassette. The for ‘non-standard construction’. Mainstream
construction system used was closed-panel insurers often deem ‘standard’ to mean pre-
timber frame manufactured by sub-contractor 2011 building regulations 100mm cavity con-
A-Frame in Co Meath. This means the walls struction. This may have changed since the
were insulated in the factory, with Thermo Hemp, completion of this building, but at the time the
a method which gives greater quality control client struggled to get quotes and eventually
(from top) installation of the Supergrund insulated foundation system; the 60mm of Gutex Ultratherm
external to the Thermo-Hemp insulated, closed-panel timber frame system; a Siga Majpell airtightness and
vapour membrane, which was used in places in addition to the principle Pro Clima Intello vapour check; the
Aquapanel cement board helps to protect the house from the elements; Thermo-Hemp insulation in the walls
ph+ 39
new build
PROJECT OVERVIEW:
Building type: 163 sqm detached two-storey
timber frame house
Airtightness: 0.5ACH at 50 Pa
ph+ 41
LOW ENERGY
TIPPERARY OFFICES
GO FOR GOLD
A new development in Tipperary says that the staff are delighted with their new model works well with a sustainable agenda.
quarters. “My last building was an old period build- “You don’t get as many design iterations or
aimed to combine excellent levels ing that was converted for offices,” he says, “but it changes,” he says. “It’s much easier to drive
of airtightness and insulation with was cold, draughty and hard to heat. It needed a lot efficiencies because people know where
generous glazing and natural ven- of maintenance. This building is state of the art.” waste can occur, and they all work together.
There’s no incentive to do that on traditional
tilation to deliver ultra-modern, com- District engineer, Aidan Finn, agrees. “They’re build projects.”
fortable, low energy offices. How did bright, airy offices,” he says, “it’s a really pleasant
place to work in.” Finn, who was town engineer He points out that since the recession, the
it work out? during the build, explains that a committee tendering process has frequently precipitated
within the local authority co-ordinated with the a race to the bottom, as contractors sell at or
Words: John Hearne Office of Public Works (OPW) to develop a full below cost simply to keep going. Because price
specification ahead of the tendering process. isn’t the sole criterion on design and build projects,
there is much greater scope to deliver an optimal
This site in Tipperary Town is home to decentralised The contract was won by a building firm, Stewart, solution. It also gives the lifetime costs of the
offices for the Department of Justice and Equality, a company which has a long-established track building a priority that can be lost on traditional
and new civic offices for Tipperary County Council. record in sustainable building. The Galway firm builds.
Arranged in two separate buildings east and west built the Bucholz/McEvoy designed SAP offices
of a central civic plaza, the project is underpinned in Ballybrit, Galway, along with the BREEAM Stewart retained Coady Partnership Architects
by a sustainable ethos that can be identified at Excellent rated decentralised offices in Roscommon for the project. The two companies had worked
almost every point in the design process. in 2010. together on a number of other buildings, including
the aforementioned decentralised offices in
Bernie O’Brien is caretaker at the civic offices. He MD Paul Stewart says that the design and build Roscommon.
new build
Tomas Sexton, project architect for Coady, explains that we could improve on the green credentials sound can sometimes be difficult. Extensive
that the design team employed a collaborative of the project, even at that specification level.” glazing is a frequent requirement, both to pro-
approach. Contractor, architect, structural, civil vide the right look and to deliver daylight into
and M&E engineers, landscape architects and The design team sought to preserve as many office spaces. “But that isn’t necessarily the
others all came together in a round table format of the site’s natural features as possible. Work most environmentally friendly to design or build,”
to tease out the various issues. exclusion zones were instigated around trees, he says.
while archaeology discovered during excava-
“We worked all our strategies out early on,” tions was preserved and documented. The civil In large office buildings, the cooling load is
says Sexton. “Buildability solutions, structural engineers used a natural dip in the terrain to typically heavier than the heating load, which
solutions, we talked with M&E about ventila- facilitate a drainage solution and avoid the need is why conventional developments invariably
tion strategies, we discussed building width, for attenuation tanks. Swales were created to require large air conditioning systems. In Tip-
grid depth, steel versus concrete, precast ver- collect run-off water from car parks, which perary, both buildings are naturally ventilated.
sus insitu, grid structure, the depth of the plan meant that petrol interceptors were largely The natural ventilation strategy not alone reduced
for light penetration and so on.” unnecessary. the M&E bills for the project, it also makes both
buildings much cheaper to cool.
The Stewart-Coady partnership had used a “These kinds of approaches,” says Sexton,
poured-on-site concrete slab with columns on “allowed the contractor to keep his price down, This system is facilitated by windows at high and
the Roscommon project. In Tipperary, they had and at the same time, it demonstrated to the low level. The top hung sashes are controlled
intended using the same approach, but then OPW that we were taking a better environ- by the building management system (BMS)
realised that by using precast concrete sourced mental approach to developing the site.” linked to temperature and CO2 sensors. These
locally, onsite wastage would be cut. “So even facilitate automated indoor environmental control,
at that stage we were looking at supply chain,” Paul Stewart says that making a building both night purging and summer cooling. There’s also
says Sexton. “We wanted to show the OPW aesthetically pleasing and environmentally sufficient flexibility for staff to override the
ph+ 43
new build
system and open or close windows as they get everything just so.”
require. It was deemed that only meeting and
conference rooms, because of their higher occu- But he says that the brise soleil fitted to the
pancy levels, required mechanical ventilation. southern elevation to deal with glare didn’t do
that job quite as well as had been hoped. In-
District engineer Aidan Finn says that over the door temperatures in the Department of Jus-
summer months, the Tipperary County Coun- tice building also rose a bit above comfortable
cil building maintained an even, comfortable temperatures during the summer heatwave in
temperature even on the hottest days. “You can 2013.
manipulate the temperature in each individual
room. Some people are colder than others, some Flexibility was also an integral element of the
people are warmer than others. It’s about design. The natural ventilation strategy had to
playing around with that, making sure that you address, not alone the current layout, but also
(clockwise from above) Glazed curtain walling with brise soleil on the Tipperary County Council building; the
ground floors were insulated with 80-90mm of high performance insulation boards; construction proceeds
at the site; an aerial view of the site, with the Department of Justice building in the foreground; the project
won awards for sustainability achievement and public sector project of the year at the 2013 Fit Out Awards;
(p47) (top) the Tipperary County Council building with brise soleil and (bottom) the main Department of
Justice building was insulated and rendered externally with the Solix Soltherm EPS system
ph+ 45
new build
the possibility of future layout changes. Tomas
Sexton again: “The brief required office spaces
to be fully adaptable from cellular to individ-
ual and vice versa, so we needed a ventila-
tion strategy that would work for both.” Again,
in order to provide for future design changes,
open spaces were designed with raised floors
to facilitate distribution of services.
ph+ 47
new build
PROJECT OVERVIEW:
Building type: Two new office buildings, one
for the Department of Justice (4,405 sq m),
one for Tipperary County Council (1,970 sq m)
Location: Tipperary Town, Co Tipperary
Completion date: Early 2013
Building Energy Rating / Display Energy
Certificate: Not yet available. Project constructed
to target A3 BER.
Environmental certification: The Department
of Justice building will be submitted for LEED
‘Gold’ certification.
Airtightness (Q50 at 50pa):
Department of Justice: 1.73(m3/hr)/m2
Tipperary County Council: 2.64 m3/hr/m2
Floors: Insulated with 90mm Xtratherm
Thin R or 80mm Kingspan K3 Floorboard.
U-values: 0.15 & 0.156
Main roofs: Single ply membrane externally,
followed below by 150mm insulation*, vapour
barrier, screed, precast slab: U-value: 0.15
Single-storey/pop-out roofs: Single ply mem-
brane externally, followed below by 150mm
insulation*, vapour barrier, profiled metal
deck. U-value: 0.15
Rendered (main) walls:Render, 200mm Soltherm
HD Weather platinum EPS system, 215mm
blockwork, 16mm wet plaster. U-value: 015
Timber-clad walls: Timber weatherboarding,
followed inside by 40mm ventilated cavity, breather
Civil & structural engineering: Roof insulation: Ballytherm membrane, 120mm insulation* (foil faced, tape
Tobin Consulting Engineers Floor insulation: Xtratherm and sealed acting as vapour barrier), 215mm
Mechanical contractor: T Bourke & Company Windows, doors & curtain walling: Season Master blockwork, 18mm wet plaster. U-value: 0.18
Electrical contractor: Tim Kelly Electrical Contractors Entrance doors: Boon Edam Stone-clad walls: 175mm coursed stone,
Airtightness consultant: Brise soleils: QEF followed inside by 100mm blockwork, 50mm
Building Envelope Technologies HPL cladding: CEP Claddings cavity, 100mm insulation*, 215mm blockwork,
Biomass boilers: Filtrex Stone cladding: StoneTech 18mm wet plaster. U-value: 0.17
Gas boilers: Euro Gas / Remeha Green cement: Ecocem Basalt-clad walls: 40mm stone cladding on
Radiators: Versatile ss fixings 50mm cavity, followed inside by
Underfloor heating: Henco / Unitherm 160mm insulation* (foil faced, tape and sealed
Heating controls: Ace Control Systems Want to know more? acting as vapour barrier), 215mm blockwork,
Solar PV: Solaregy 18mm wet plaster. U-value: 0.2
Heat recovery ventilation: Mitsubishi Electric
Click here to view additional information on
these projects, including an online gallery HPL-clad walls: HPL boards on S/W battens
High level opening vents: Ace Control Systems
featuring illustrations, photographs, and followed inside by 40mm ventilated cavity,
Air conditioning: Mitsubishi Electric
breather membrane, 40mm insulation, vapour
Solar thermal & rainwater harvesting: project overview panels.
barrier, 18mm WBP plywood, 250mm mineral
Kingspan Environmental
This content is exclusively available to our wool insulation between primary steel structure
External wall insulation: Solix
U-values: 0.15
Additional wall insulation: Kingspan Insulation digital subscribers. *Insulations used were high-performance rigid insulation
boards from Kingspan, Xtratherm and Ballytherm
Glazing: Season Master double-glazed
windows, doors & curtain walling, with Carey
Glass. Argon fill. U-values: c.1.1
Heating:
Tipperary County Council building: Herz Firematic
90kW wood chip and pellet boiler & Rehema
140kW condensing gas boiler.
Department of Justice: 300kW Herz Biomatic
300kW chip/pellet boiler & Eurogas 450kW
condensing gas boiler.
Gas boilers were sized to allow for future ex-
pansion of the buildings. Heat distributed
principally via Jaga Mini Canal trench heaters
and Jaga wall-mounted radiators. Kingspan
Thermomax HP Vacuum tube solar collectors
contribute to domestic hot water.
Ventilation: High level opening vents con-
trolled by BMS throughout the building. Mit-
subishi Electric Lossnay heat recovery ventilation
units to meetings/ conference rooms.
Electricity generation and use: 45kW solar
photovoltaic array to Tipperary County Council
building. All artificial lighting is controlled by
automatically dimmable PIR sensors, and
low energy lifts were installed.
Water: Low water usage appliances and
rainwater harvesting for flushing WCs.
Green materials: 50% GGBS used in rein-
forced concrete throughout, and “responsibly
sourced” low VOC materials were used.
ph+ 49
Passive fishermen’s cottages
on Norfolk coast
ph+ 51
new build
(top left) the raft foundation which was insulated with 400mm Styrofoam XPS insulation; (middle left)
the cavity walls were insulated with Isover Hi-Cav 32 glass mineral wool insulation and clad with brick,
while Cavalok BigBlok insulated cavity closers and Ancon Teplo Tie basalt wall ties eliminate thermal
bridging; (bottom left) airtightness measures included the installation of a Pro Clima Intello membrane
and a suspended ceiling system to house ductwork; (above) the three terraced homes all obtained passive
house certification in June 2014; (p55) (top) it was decided not to aim for the passive standard with the
other three units at the site, as they had a poor orientation and form factor; (middle) Munster Joinery EcoClad
timber aluclad windows provided the necessary performance while retaining a traditional appearance
of passive house were recognised and em- of the move had subsided, Hastoe and the ar-
braced, making the delivery of this exacting chitects returned and spent an hour or so with
standard much easier. Coordination between each family taking them through the controls
design and site team continued throughout and the heating and cooling strategy. One of
the build and ensured that milestones were the most important aspects here is to ensure
passed without difficulty. The required air- that occupants experience the controls them-
selves and get to play with them while experts
are around to guide and assist. This process
mainly because it is highly effective At the same time as the handover, monitors
were installed with the occupants’ consent, to
ph+ 53
new build
PROJECT OVERVIEW:
Building type: Terrace of three 76 sqm passive
two-bedroom homes (the wider development
included three further units).
ph+ 55
Ledbury passive house
embraces warmth, wood & light
For Ruth Busbridge and her builder Mike Whitfield, aiming for the passive house standard was just
one part of an environmentally conscious approach that put natural, healthy materials to the fore.
Not everyone expects a passive house to be Once planning permission was secured, Janet,
like this – and indeed, when Ruth first heard who is based in London, was able to hand over
of passive house, she didn’t think it was right to Mike Whitfield. “Mike took on the construction
for her. “When I first heard about passive house, drawings, and took the lead on site. It was a
my initial reaction was ‘eurgh – I wouldn’t want bit of an unusual contract in that respect, but
to live in a hermetically sealed house’,” she says. I had seen the work Mike had done, and I
thought ‘Ruth won’t have any problems’ – she
However, that was before she had learned much was so lucky to have him as her contractor,”
about it. “I’d been planning to build a house for Janet says.
four years, so I did a course at Cat [the Centre
for Alternative Technology in Wales], and I joined Ruth also found specialist heating and venti-
the local AECB [the Association for Environment lation designers and suppliers through the
Conscious Building], which is how I met Mike, AECB: “Because of the collaborative atmos-
and passive house was just filtering in. Then phere in the organisation we never felt we were
I went on a study tour to Germany and became on our own,” Ruth recalls. “The expert advice
more interested in passive house. The more from Alan Clarke and Nick Grant and from Green
I heard, the more I thought it made sense.” Building Store, on designing and sizing the
heating, hot water and MVHR, and ongoing
Mike Whitfield has been building beautiful, en- support with PHPP, were invaluable. I couldn’t
vironmentally conscious buildings from natural have done it without them.”
materials for decades – he was the contractor
on the conversion of a derelict barn on the This was the first chance Mike had to build to
Duchy of Cornwall’s Herefordshire estate into passive house certification, and he was pleased
the new HQ for Architype West, for example. to take on the job because Ruth shared his
As a main contractor, Mike Whitfield offered preference for low impact, natural materials.
Ruth the ideal approach, with his preference The timber frame, which Mike built on site, is
for natural and low-impact materials, combined insulated with cellulose and clad in a mixture
with excellent energy performance, in a style of Douglas fir and lime render, and roofed with
she was drawn to. “I had seen some of his work reclaimed slates. “I would ideally also have
before. It was beautifully finished, and I prefer liked an alternative to EPS under the floor, but
the natural look.” there wasn’t really any alternative that was af-
fordable – and the EPS works really well,”
By the time Ruth approached him, passive house Ruth adds.
was becoming a valued tool in Mike’s mission
to construct buildings that are comfortable, The timber-frame build-up has a breathable
healthy and low-impact: “We had been doing construction, becoming more vapour perme-
energy efficient buildings anyway, and the able from the inside outwards. This means
AECB were developing their silver and gold that if any water does get in to the structure,
ph+ 57
new build
it will dry out. The walls and roof are both in- the same way as others on the street, so it Sometimes the anxiety level of the client is
sulated with Warmcel cellulose insulation. Mike does not have a direct south-facing facade. just so high that no matter how good a job you
says: “I have used Warmcel for very many years, The off-due-south angle means all glazing do, there is grief.” Ruth agrees: “I couldn’t
we have had our own blowing machine for a long has east or west elements, which makes it a imagine working with any other builder. It was
time and have never had problems. After it has bit harder to control overheating. stressful of course, but I loved doing it and
been pumped in it packs really densely, almost would do it again.”
like cork. It is hard to imagine it settling, for instance.” Looking back Ruth wonders if perhaps smaller
windows would have made the design easier. Both counsel against trying to work with a
One of the early design decisions was the “I think I would still have had ample daylight, team who are not all committed to the same
size and shape of the house, which is a kind but it would have been cheaper, and with less outcome. Mike warns: “If you are intent on
of fat L shape, with a porch. Ruth recalls: “We heat loss in winter and less unwanted gain in doing passive house it’s important to find a
were also considering a smaller house, but summer.” Though vast windows seem to be builder who is up for it properly, plus all the
opted for this shape and size [around 130 square de rigeur in some higher-end self-builds, Ruth consultants, the architect, everyone. If you
metres] so we could have an extra bedroom does not feel they are necessary. “You don’t are trying to drag anyone along you shouldn’t
and bathroom, and so get an income from want to live in a goldfish bowl, do you?” bother. Sometimes I’ll get approached by an
having lodgers.” architect who is not really committed, but they
Like pretty much all passive buildings the think that if they get me to build it, it can be a
As Mike Whitfield points out, this shape is house is beautifully quiet – you completely passive house. “
much more involved to build than a simple forget about the busy road outside, which is
rectangle: there had to be extra drainage and something Ruth really values. “It’s so peace- Ruth has experienced this too, now that she
more junctions, and inevitably it added to the ful in here,” she says. Ruth named the house is putting her passive house training to work
cost. As architect, Janet Cotterell was also Wahroonga after a suburb in Sydney where she for others as a consultant: “People come to
keen to keep the form as simple as possible: once lived. “We liked the sound of the name, me with a design, and say ‘can you make this
“Before she settled on passive house, Ruth but we were certain it was perfect when we a passive house?’ But they don’t want to
was considering a more complicated shape – looked up the meaning of the aboriginal word change it of course, so it doesn’t work.”
for my part though I would have been happy — it means 'home’.”
to make this even simpler. I think a plain rec- Ruth says her favourite aspect of the house
tangle would have looked fine!” Ledbury is quiet at night, but the traffic does isn’t any one thing, but the whole atmosphere:
become noticeable in the morning in hot “It’s just lovely to be in, has such a lovely feel,
Despite the more complicated form, however, weather when windows are opened for night it’s light and spacious. It’s comfortable, above
Ruth observes that making the house bigger cooling. Ruth would like to fit some summer all else. Warm, dry, peaceful, draught free – even
did make it easier to meet the passive house shading (omitted at the time of building for with a door wide open in mid-winter. What’s
standard. She adds: “I was very clear I wanted lots cost reasons), or perhaps install a skylight at not to like?”
of daylight, and light from two sides in every the back for faster purge ventilation, partly so
room, which means not all the windows lead she can keep the windows closed more of the There is a particular pleasure for passive house
to net heat gain. We also have the upstairs ceil- time, and enjoy the tranquillity. owners when the weather is nasty outside. “I
ings going up into the roof, which does add to love being here in winter, I can sit anywhere,
the heated volume and heat loss area. So to She adds: “A low but acceptable risk of over- and it’s always cosy. When I visit friends and
ensure the passive house standard was met, heating was predicted by PHPP [at 2.5% of family their homes always seem dark, cold
we have 400mm of insulation in the walls – and the time, well within the limits set in the stan- and damp, and I have to bring slippers and
the building also had to be extremely airtight.” dard], so I took a calculated risk in not dealing thick sweaters!” Even though Ruth opted for
with this at build time. But actually, if, like me, the simplicity (and exposed thermal mass) of
The original plan was for the OSB to form the you find 25C uncomfortably warm, I recommend a concrete floor, it’s never cold, she says.
airtight layer in the walls, but a preliminary you take any overheating risk seriously from
blower door test revealed the board was not the outset, and mitigate against it.” Everyone who visits likes the style, with the
quite as airtight as hoped. “So I decided we hand-crafted details. Ruth feels that the bespoke
should go for belt and braces with an additional The house is hitting its energy targets, according work that went in to creating her door latches,
membrane over the walls,” Ruth says. By that to Ruth’s careful records, with measured primary banister rails and the like has given her some-
stage the internal walls were already up, and energy consumption at 74 KWh/m2/yr (the thing she wouldn’t have had with a more hard-
adding a membrane to the roof would have passive house design target is 120). This is as edged, ‘interiors magazine’ style.
been been tricky, so the OSB still forms the you would expect in a house with relatively low
air barrier here. occupancy – and with mains gas and solar Yet, as Mike points out, the sharp and high-
hot water. Energy bills are correspondingly low. tech look isn’t easy to pull off. “Architects tend
Ruth says: “I don't know if we really needed to like the crisp modern contemporary look,
this additional membrane [in the walls] but I When you ask Mike Whitfield what aspect of and we can do it, but the contemporary thing
didn't want to risk not getting it certified. In the this job that he felt was most successful, his requires a lot of planning, with tiles cut just so,
end our result was 0.24 so perhaps it paid off. immediate response is “the lovely client”. Though glass stairs and so on.
Mike reckons we could easily have got 0.2 if this might sound flip, it goes to the heart of what
we'd remembered to seal the shower trap when Mike has learned over 30 years in construction. “I’d argue that with a more organic approach
doing the final test!” “In the end, it’s only about the people,” he says. like ours, you actually get a lot of nice effect
for more modest cost. And we find actually people
Planning rules meant the house had to face “You just want to be able to enjoy the job. tend to respond well to a bit of natural stuff,
ph+ 59
new build
PROJECT OVERVIEW:
Building type: 129 square metre (TFA) de-
tached two-storey timber frame house
Budget: £240K
so we prefer the handcrafted finish – people Gas boiler: Remeha Ground floor: 200mm reinforced concrete
comment most of all on things like the wobbly MVHR: Paul, via Green Building Store slab (raft foundation) insulated with 300mm
balustrading, and wooden door handles.” Solar thermal: Llani Solar EPS insulation. U-value: 0.113
Hot water cylinders: McDonald Engineers
Lamps: Locklamp Timber clad walls: douglas fir horizontal
Being able to finish a building like this is par- Light fittings: Colin Chetwood cladding externally, followed inside by 25 x
ticularly satisfying for Mike: “On one hand you Low water fixtures: Green Building Store 50mm treated battens, Permaforte membrane,
could say that is superficial, but the finish is Green roofing: Green Roof Options 22mm wood fibre board, 45x45 outer timber
an important part of the house. I think it gives Silica paint: Keim Mineral Paints frame with Warmcel, 280mm Warmcel cavity
the house soul.” I-beams: JJI Joists with Larsen truss ply gusset, 45 x 95 structural
Insurance: Insure Green timber frame with Warmcel, 18mm OSB,
Finance: Ecology Building Society Pro Clima DB+ vapour check and airtight
SELECTED PROJECT DETAILS membrane, 45mm service cavity insulated
Client: Ruth Busbridge with Black Mountain Natuwool (sheep wool)
Architect: CTT Sustainable Architect Want to know more? insulation, 28mm double plasterboard and
Contractor: Mike Whitfield Construction skim. U-value: 0.096
M&E Engineer: Alan Clarke Click here to view additional information on
Energy consultant: Elemental Solutions these projects, including an online gallery Render clad walls: lime-based render, 40mm
Airtightness tester: Paul Jennings featuring illustrations, photographs, and Steico board, 45x45 non-structural timber
Cellulose insulation: Warmcel, via PYC Insulation project overview panels. frame with Warmcel, 300mm Warmcel cavity
Sheep wool insulation: Black Mountain Natural with Larsen truss ply gusset, 45 x 95 structural
Insulation This content is exclusively available to our timber frame with Warmcel, 18mm OSB,
Windows & doors: Optiwin, via Green Building Store digital subscribers. Pro Clima DB+ vapour check and airtight
membrane, 45mm service cavity insulated
with Black Mountain Natuwool (sheep wool)
insulation, 28mm double plasterboard and
(below) metal web floor joists enable the HRV ducting to be run discretely through the house, along with skim. U-value: 0.089
pipes and wires; (bottom) the timber frame walls are insulated with Warmcel cellulose insulation but with
Natuwool sheep wool insulation at service voids and window reveals and finished with plywood boxes; Roof: reclaimed Welsh roof slates externally
(above) building contractor Mike Whitfield outside the house as it nears completion followed underneath by battening, 22mm
Steico board, 45/316/45 timber I-beams with
Warmcel, 75mm timber batten with Warmcel,
18mm OSB U-value: 0.085
ph+ 61
A passive retrofit in Co Meath offers a template that could be applied
across much of the Irish housing stock: a long, dark, 1970s bungalow
was transformed into a bright modern home that’s now warm and
comfortable.
Words: John Hearne
How to rescue a
had been poorly installed and sections of it
had to be removed, which further slowed the
work. The house also featured a combination
of floor slab and suspended floors, all of which
had to be taken out.
ph+ 63
upgrade
(top left) the existing bungalow’s roof was demolished along with all of the internal walls; (top right) the ground floor was insulated with Xtratherm Thin-R PIR insulation;
(bottom left) the dwelling was extended upwards by half a storey as part of the refurbishment; (bottom right) the walls were externally insulated with platinum EPS
team installed external fabric blinds, which chased, the cavities had to be sealed ahead the technology. In fact, one of the big advantages
were incorporated into the external insulation. of the first electrical fix. Similarly, all airtightness of the passive standard building envelope is
Made of a semi-transparent material, the visual details had to be completed before moving on noise reduction.
connection with the outside is retained even to creating the first floor. Galway-based com-
when the blinds are lowered. They filter out pany Partel supplied Ampack airtightness tapes “We live on the N2,” he says, “which is a very,
the sun’s UV rays and limit the solar gain that and membranes for the roof construction and very busy road. You get lorries going up and
might otherwise overheat the house during windows. down the road from five in the morning. Now,
the summer months.
ph+ 65
upgrade
ph+ 67
From drab
farm shed
to passive,
light-filled studio
new build
When Sjölander da Cruz Architects team embraced passive house principles from asbestos cladding from the old steel frame
the outset, and aimed for Enerphit certification, structure. Some of the steel beams were in a
sought to turn an old abestos-clad the Passive House Institute’s retrofit standard. bad state too, and needed refurbishment.
shed into the firm’s new studio, it
offered the perfect opportunity to put “This was the first passive house building we Sjölander da Cruz chose to keep the existing
worked on,” Shely says. “We’ve always been concrete slab, but wanted to construct two in-
an enthusiasm for passive house interested in sustainability. Prior to doing this we ternal mezzanines. This meant there was lit-
design into practice. had been to quite a few passive house lectures. We tle room to beef up the floor insulation without
felt [passive house] was the future of sustainability, limiting headroom under the mezzanines, so
and it was something we wanted to be involved in.” only 120mm of phenolic insulation was installed
Words: Lenny Antonelli on the slab. To reach the Enerphit standard for
Arden Construction was appointed as contractor heating demand, the team now had to push the
— it was their first passive project too — while thermal performance of the walls, roofs and
What better way for an architecture firm to break energy consultant Nick Grant of Elemental windows even further.
into passive house design than by creating its own Solutions came on board to advise the team.
passive-certified architectural studio? Birmingham- For the walls, the new thermal envelope consists
based Sjölander da Cruz Architects had bought The existing shed had a north-south orientation, of Kingspan Tek structural insulated panels
an old asbetos-clad agricultural shed near ideal for making the most of passive heat gains. (SIPs) outside the existing steel frame. The
Leamington Spa, and planned to retrofit it into The building is in the green belt, so the existing panels consist of urethane insulation sandwiched
the practice’s new offices. shape and volume had to remain, but the simple between two layers of OSB. Sjölander da Cruz
form lent itself to passive design, minimising the has extensive experience with SIPs, so it was
“We just wanted to create something that was external surface area from which heat could escape. the natural choice of building material. To boost the
a comfortable working environment,” says project U-value further, 100mm of Kingspan Thermawall
architect Shely Begum. The Sjölander da Cruz First, a specialist subcontractor removed the urethane insulation was installed outside the
ph+ 69
new build
panels too. ing through the OSB, so wet plastering the walls
inside provided an extra seal. The final blower
The old steel beams run right from the concrete door test result was 0.4 air changes per hour.
base up to the roof, so wrapping the perimeter in
EPS below ground cut thermal bridging here. “Everybody was chuffed to bits, really chuffed,”
Meanwhile Kingspan Unidek Aero SIPs — which Rob Harwood, construction manager at Arden
contain graphite EPS insulation sandwiched Construction, says of the result. “It was their first
between two layers of particle-board — form [passive house], it was our first one, it was quite
the insulating layer for the roof. a steep learning curve for both. But it all worked.”
The airtight wrap of the building is formed by the Harwood says the support available from Nick
damp proof membrane (DPM) under the floor Grant and Siga was vital to the success of the
insulation, the internal OSB for the walls, and a build. “I think it went relatively smoothly. There
Siga Majpell membrane under the roof panels. were more issues with drainage than there
Siga tapes were used on all the critical junctions, were with anything else,” he says, adding that
and lots of taping was required around the tricky junc- everyone on the team was eager to embrace
tions between the DPM and the steel columns. passive house.
An early airtightness test showed some air leak- “It was something new, it was something
ph+ 71
new build
different, it’s a fantastic setting.” He says he would cess heat loss through the north-facing glass.
happily take on another passive house project.
Shely says: “We paid a huge amount of attention
The studio is heated with a gas combi boiler to the detailing of the building. What we wanted to
that supplies underfloor heating. Meanwhile do was create a balance between the physics
a Paul Novus system provides mechanical and the architecture. You can see that we’ve
heat recovery ventilation (MVHR), and was got huge amount of glazing. We wanted to
installed on one of the mezzanines. bring as much daylight into the building as
possible because it’s a workspace. We wanted it
“What we’ve decided is expose it so you can to feel quite light and airy.”
see the machinery,” Shely says of the MVHR
unit. “We think it looks quite cool, we’ve got Along with the ventilation ducting and electrical
all the ductwork exposed so that you can see wiring, the old rusted steel frame is exposed
how this building works.” inside. This creates a striking contrast between
the white walls and wood finishes. Externally
Extensive glazing on the south and north fa- the building is clad with western red cedar, ac-
cades provide natural cross ventilation too. As centuating its warm, natural feel.
well as bringing in daylight and fresh air, these
windows frame the surrounding countryside, Sjölander da Cruz moved into the building in
and a wildflower meadow on the site. January, and named it River Studio, for a tributary
of the Avon that runs along the edge of the
Having lots of glass could risk leading to over- site. In September the firm began a year long
heating and glare, but the external insulation programme of post-occupancy monitoring.
creates deep reveals to mitigate this, and there
are brise soleils externally on the south and west “In the summer we’ve noticed that even when
facades. Pushing the U-values of the other building it’s quite warm outside, it still feels comfortable,”
elements even further compensated for any ex- Shely says. In winter, she adds, the expanses
(clockwise from top) the old asbestos-clad shed which was retrofitted to the Enerphit standard; erection
of the Kingspan Tek structural insulated panels (SIPs); a close-up of one of the panels, which consist of
urethane insulation sandwiched between two layers of OSB, outside the steel frame; 100mm of additional
Kingspan Thermawall insulation was installed outside the SIPs; a blower door test being carried out to
measure air leakages in the building; a thermal imaging survey carried out by Nick Grant to detect any
areas of heat loss; the building is now clad externally with western red cedar; (p71, main picture) the heat
recovery unit is installed on one of the mezzanines, with all ductwork and machinery exposed; (p69) all
cladding was removed from the old shed, leaving only the original steel frame, which was left exposed inside
the finished studio
ph+ 73
new build
PROJECT OVERVIEW:
Building type: retrofit of mid 20th century
asbestos-clad shed into modern architectural
studio.
Location: Leamington Spa, Warwickshire
Completion date: December 2013
Budget: £267,765.80
Space heating demand (PHPP): 18 kWh/m2/yr
Heat load (PHPP): 14 W/m2
Primary energy demand (PHPP): 95 kWh/m2/yr
Passive house certification: Enerphit certified
Measured energy consumption: Post occu-
pancy monitoring began in September 2014
and will take one year to complete
Airtightness (at 50 Pascals): 0.4 air changes
per hour
Walls: 22mm Western Red Cedar cladding
externally, followed inside by continuous layer
of south-facing glass bring both heat and light Passive house certification: Warm of black insect mesh, 38x50mm vertical timber
into River Studio. Additional wall insulation & floor insulation: battens at 500mm centres, Siga Majvest
Kingspan wind-tight membrane (joints taped with Siga
Slab perimeter insulation: Sto Wigluv 60), 100mm Kingspan Thermawall
“The air quality is one of the things that every-
Window supplier: Spectrum Installations TW55 urethane insulation, 142mm Kingspan
body has noticed,” she says. “There’s a great Roof windows: Velux TEK SIPs with internal OSB serving as airtight
quality of light within the space, and the views Brise soleil: Dales Fabrications layer (Siga Sicrall used to seal OSB joints),
towards the surrounding landscape just make Timber cladding: Vincent Timber 15mm British Gypsum Fireline plasterboard
it a great place to work.” MVHR: Blue Diamond with skim coat finish. Below DPC: Sto EPS
Screed: Flowcrete UK insulation around perimeter of concrete slab.
Ventilation supplier: Lindab Wall U-value: 0.106
SELECTED PROJECT DETAILS Lighting: Artimede
Client & architects: Sjölander da Cruz Architects Roof: Standing seam steel roof externally,
Steel roofing: Tata Steel
Contractor: Arden Construction followed underneath by Tyvkek metal open
Energy consultant: Elemental Solutions drainage membrane, Kingspan Nilvent breath-
M&E Engineer: Alan Clarke Want to know more? able membrane, 18mm WBP deck, Kingspan
Unidek Aerodek SIP comprising 234mm EPS
Civil & structural engineer:
Bob Johnson Consulting Structural Engineers
Click here to view additional information on insulation core between two layers of parti-
Airtightness membranes & tapes: Siga these projects, including an online gallery cleboard, Siga Majpell vapour control layer
SIPs supplier & installer: Lowfield Timber Frames featuring illustrations, photographs, and to underside of Unideck system to provide
SIPs manufacturer: Kingspan project overview panels. airtightness (lapped over OSB in walls by
Mechanical contractor: Blue Diamond 150mm), 15mm British Gypsum Fireline plaster-
Electrical contractor: C&L Electrical This content is exclusively available to our board and skim finish internally. U-value: 0.127
Airtightness tester: Coventry University digital subscribers. Ground floor: Continuous DPM (also the
airtight layer) on existing concrete slab and
brought up to connect with airtight OSB
layer of walls (Siga Rissan 60 used to seal
DPM joints), 120mm Kingspan K3 Floorboard
insulation over the DPM, followed above by
20mm underfloor heating pipes embedded
in 65mm Flowcrete K screed with polyurethane
resin floor finish & polyurethane matt seal.
U-value: 0.13
Windows & door: Internorm HF200 aluminium-
clad timber units. Overall U-value: 0.8 (for
standard sized window).
Roof windows: Velux GGL 3065 triple-
glazed pine-finished roof windows. Overall
U-value: 1.0
Heating system: Worcester Bosch Greenstar
28CDi compact condensing gas boiler (space
heating and hot water).
Ventilation: Paul Novus 450 mechanical heat
recovery ventilation system. Passive House
Institute certified heat recovery efficiency: 89%
Green materials: Western red cedar cladding.
ph+ 75
Images: Passive House Institute
THE NEW PROPOSED PASSIVE
HOUSE CLASSES EXPLAINED
The Passive House Institute’s announcement of new classes of passive house certification – including
renewable energy generation – at this year’s International Passive House Conference caused something
of a stir. Dr Benjamin Krick, the institute’s head of component certification sheds some light on the new
classes and explains the rationale behind proposals which may set up passive house for a fabric first approach
to near – and sub – zero energy building.
The evaluation of a building’s energy demand Take the example of wood in the form of split logs, cording to EnEV, the factor has been reduced
typically takes into account its consumption of which consists principally of renewable primary from 3.0 via 2.7, 2.6 and 2.4 in the past to 2.0
non-renewable primary energy, such as electricity energy – namely the solar energy that the tree now. In the year 2016 it's expected to further
generated by coal, gas or oil-fired power plants. stored in the form of carbon during its growth. decrease to 1.8 – in large part because of the
This primary energy (PE) principle includes Only a small fraction of the energy used to produce growing contribution from renewable energy systems
the evaluation of the generation and supply this wood comes from non-renewable sources, into grid electricity supply, which is regarded as
chain that energy must go through to arrive at such as for cutting, chopping and transporta- having zero primary energy. If we follow this line
our buildings. Energy losses occur on the way tion. We know that if we disregard the stored of thinking, the non-renewable primary energy
from the oil spring in the Saudi Arabian desert solar energy in the logs, the primary energy factor will tend towards zero and will be zero, if
to the oil storage tank at home, due to transport factor of the split logs is approximately 0.05 transition to 100% renewable energy is ac-
and refinement of crude oil to heating oil. These (though according to EnEV a factor of 0.2 has complished – assuming we accept the notion
sorts of losses are evaluated via the primary to be used). On EnEV’s terms it follows that if wood that we can disregard primary energy from re-
energy factor. is used instead of oil to heat a building, more newable energy sources. Should that happen
energy may be consumed. However wood, too, every building, independent of its actual end en-
According to EnEV, the German regulation for is a resource that is limited in its availability. ergy demand, will have a primary energy demand
energy saving in buildings and building systems, for electricity of zero. Already this approach
heating oil has a PE factor of 1.1 – a loss along Electricity is a mix of renewable and non-re- shows that using the non-renewable primary
the generation chain of 10%. However, PE newable sources. Old coal power plants pro- energy demand as the sole scaling system has
factors are generally not determined by exact duce electricity with a non-renewable primary become inappropriate for the sustainable
science but by politics, even though they are energy factor of about three. To produce one evaluation of energy efficiency in buildings.
used to evaluate the energy demand of buildings part electricity, three parts of primary energy in
according to regulations such as EnEV. This the form of coal are burnt. No fossil energy is Future evaluation of the energy supply:
works in a reliable way as long as the energy required for electricity generation in wind or solar PER system
supply system is mainly based on non-renewable plants. For this type of electricity, the non-re- In principle, one possible solution could be to
sources. But the situation changes with higher newable primary energy factor is treated as add the renewable primary energy demand to
shares of renewable energy. zero by EnEV. If the mix of renewable and non the non-renewable primary energy demand.
renewable sources used to generate electricity In this case, wind energy has a total primary energy
Right now, only non-renewable primary energy changes, the resulting non-renewable primary factor of one, and for wood it would be 1.2,
is taken into account in most European countries. energy factor for electricity changes too. Ac- based on EnEV data. At first sight, this solu-
insight
tion seems viable. However, renewable and
non-renewable energies cannot be compared
with each other: while the use of non-renew-
able energy leads to dramatic and permanent
or difficult-to-reverse damage (climate change,
air pollution, nuclear risks), problems resulting
from the use of renewable energies are often
more aesthetic (visual destruction of landscapes,
reflective effect of solar systems on roofs) and
feasible to resolve in principle (e.g. the debate
about the use of biofuels for food vs fuel).
Considering this, it is evident that a simple ad-
dition of renewable and non-renewable primary
energy is not appropriate for evaluating their
combined impact on the environment.
ph+ 77
insight
is required. As described, the PER system Passive House Plus: Space heating demand of 60 kWh/(m2ground*yr), reaches the Passive
can be applied to carry out this evaluation. max. 15 kWh/m2yr; PER demand max. 45 House Plus standard. Compared with variant
kWh/m2tfa*yr; Primary electricity generation 1a, it’s noticeable that the energy generation
The generation and use of renewable energy min. 60 kWh/m2ground*yr based on the building's is less, despite using the same collector. This
sources for buildings makes sense and is re- footprint. can be easily explained by the significantly
quired by the EU Energy Performance of Build- lower domestic hot water demand. Less energy
ings Directive. However, buildings must not be Passive House Premium: Space heating is needed, so the solar system is replacing
reduced to a function as carriers of energy demand max. 15 kWh/m2yr; PER demand max. less energy. In this variant, demand and gen-
generation plants. Approaches which directly 30 kWh/m2tfa*yr; Primary electricity generation eration is balanced with regard to renewable
offset generation and demand in the annual min. approx. 120 kWh/m2ground*yr based on primary energy.
balance will inevitably lead to misguided opti- the buildings‘ footprint.
mizations, because generation of solar elec- Since the passive house in Gerstetten needed
tricity in summer cannot directly offset a demand The premium-class is very hard to achieve only a bit more energy than provided by the
in winter. Between generation and demand there and thus is dedicated to ambitious individuals biomass boiler, due to its high efficiency, the
is a chain of transition, storage and, again, who want to go beyond what might be considered effect on the renewable primary energy demand
transition. economically and ecologically optimal, based by changing the boiler’s fuel from pellets to gas
on current technology. can be nearly neglected (2).
It is relatively easy to transform a bungalow
into a plus energy house in the annual energy What the new passive house classes actually However, if a heat pump is used, the rating
balance. In comparison to the useful area, a mean changes significantly: In variant 3 with an air-
large roof area is available which, when cov- A passive house in Gerstetten, Germany shows to-air heat pump, the PER-demand decreases
ered with photovoltaics, allows for lots of solar how the new passive house classes can be already to 40 kWh/m2tfa*yr. On the demand
generation during the summer. The building achieved. The author thanks the passive house side, the Passive House Plus class is reached,
does not need to be very efficient to obtain an architect Prof. Dr. Werner Friedel for the op- and the PER demand and generation is al-
equilibrium in the energy balance based on portunity to carry out a study on the basis of ready balanced. The switch to a brine-towater
space heating demand. But storage losses this house. At present the building is heated heat pump (3a) reduces the demand further
are typically not included in this equation. And by a wood pellet boiler. On the roof a 74 m2 to 34 kWh/m2tfa*yr, and with 85 m2 of PV the
if a multi-storey building is needed, which has photovoltaic (PV) system is installed (version Passive House Plus class and a significant
a smaller footprint and is more ecological, it 1). The building is highly energy efficient, with PER-surplus are achieved.
will be much harder to accomplish an equilib- an annual heating demand of 11 kWh/m2tfa*yr,
rium in the energy balance due to the worse which is reflected in an airtightness value of For Passive House Premium some things are
roof-to-useful-area ratio. 0.14 ACH. With a PER-demand of 60 kWh/m2tfa*yr missing: optimization of the mechanical and
it just reaches the criteria of Passive House electrical technology alone is not enough. Changes
Here, the PER system offers a solution of a correct Classic, and the PER-generation is 53 to the building envelope are required. If in-
offset of generation and demand: onsite gen- kWh/(m2Ground*yr) – falling short of the stalled Passive House phB- class windows
erated electricity is primary electricity and will threshold for Passive House Plus. are replaced with class phA the annual heat-
be evaluated with a PER factor of one. Unlike ing demand reduces to only 8 kWh/m2tfa*yr.
the current situation where methodologies such If a small 6m2 solar thermal collector is added Together with the shower hot water heat re-
as EnEV, Deap and Sap give a primary energy for hot water, the PER requirement reduces to covery and the optimization of the hot water
reward to onsite renewables by displacing grid 54 kWh/m2tfa*yr, and the generation increases distribution as in variant 1c, and with full-scale
electricity – which has current primary energy to 65 kWh/m2ground*yr (1a). On the generation occupation of the roof with a 123 m2 photovoltaic
factors of more than two – this energy isn’t side, the Passive House Plus target is thus array, version 3b achieves a PER demand of
seen to be displacing more than a kilowatt of achieved, but the building fails the demand of 30 kWh/m2tfa*yr, meeting the target required
grid electricity, because this proposal assumes maximum 45 kWh/m2tfa*yr. Already in this variant by Passive House Premium. But the generation
completely renewable primary electricity with a the building delivers a slight energy surplus figure of 88 kWh/m2ground*yr is still too low,
primary energy factor of one. Meanwhile, appli- with regard to final energy. Tripling the collector although now about twice the amount of energy
cation-dependent PER factors (such as gener- to 18 m2 would change little, since the energy required in the building is generated. Other
ating hot water) are assigned to the demand. produced especially in the summer cannot be actions would be the availability of the garage
fully utilized because the (now 2000 l) hot water roof or south facade with PV, or, for example,
Taking the above into account, the issue of tank is already fully charged (1b). investing in a community wind turbine. A pro-
multi-storey buildings still needs to be resolved. A portion of 3 kW of installed capacity, which is
building uses a certain area – the building’s Version 1c, again with a 6 m2 solar thermal array about five-hundredths of a modern, installed
footprint – with the result that this area is no but also additional heat recovery from shower inland wind plant would be sufficient to achieve
longer available to the public. Through the gen- water, sees an improvement of the hot water Passive House Premium – and almost to pro-
eration of energy it is, however, possible to distribution system. This variant, with a PER- duce three times the amount of energy re-
make positive use of this area for the public. demand of 45 kWh/m2tfa*yr and a production quired.
The Passive House Institute therefore pro-
poses to relate the energy generation not to Impact of PER-classification function of the component parts used
the useful area (or living area or treated floor
area) but to the building’s footprint.
ph+ 79
Photo: Gavin Ó Sé
WILL BUILDING BOOM SEE
LOW ENERGY FAILURES?
Low energy building isn’t complicated, but it’s easy to get wrong. Since Irish house builders downed tools
en masse when the last boom ended, energy efficiency standards for new homes have seen unprecedented
rises of 40% in 2008 and 60% in 2011, shooting far ahead of the UK. But with signs of a new boom emerging,
can the industry get to grips with this brave new world of insulation, airtightness and thermal bridging
and deliver healthy low-energy homes — or are damp and mould set to become the norm in new build?
Simon Jones of ventilation technology company months. Gavin Ó Sé of Greenbuild in Co Wexford new. He’s been discovering condensation and
Aereco took a call recently from an architect was also called in to advise on an almost identical mould in new buildings for at least the last five
looking for advice. The architect was working issue. “The contractor had installed good insulation years. His concerns – and those of many others
on a residential development that had just been and achieved good airtightness results, but in in the industry – centre on the tentative resurgence
completed, but there was a problem. one or two of them, he had been called back in building activity and what it implies for the
for condensation build up,” Ó Sé says. quality of construction.
Jones drove out and met the architect, the en-
gineer and developer at the site. “We took a And Archie O’Donnell of Integrated Energy and Jones points out that during the recession, most
walk around the houses and in dead space areas Coda Architects has also had recent experience house building in Ireland fell into one of two
on the development, areas where you wouldn’t of condensation and mould in new builds. In fact, categories. “One is council driven,” he says. “New
get free flowing air, we found mould and con- all of the professionals interviewed for this piece builds for the likes of Ballymun regeneration
densation. And this is before anyone had even had a ready stock of stories of how poor ventilation or Limerick regeneration, where specs are
moved in. Behind wardrobes and in corners near strategies in particular, and questionable building being led by councils who have demanded
skirting boards; mould and condensation.” practice in general, continue to dog Irish con- certain performance levels. Or else you have
struction. the passive house, one-off builder who has
Jones isn’t the only building professional to have been building ever better homes over the last
run into mould in new houses in the last few These issues, Simon Jones points out, are not half decade.” Both categories of builder have
insight
an obvious vested interest not alone in delivering
a cost-effective project, but also in ensuring
that the structures they build provide a safe,
low cost, high comfort living space for decades
to come.
ph+ 81
insight
The other issue with cavity insulations is moral In July 2010, the Department of the Environment and to leave it to designers to specify the ap-
hazard. “Builders tell you that there’s bits around published a regulatory impact assessment propriate solution for a particular building.”
corners and windows that are quite tricky to (RIA) on the proposals to amend Part L of the
do and quite often they say, ‘sure once we get building regs. The document included a table By creating the impression that natural ventilation
up another five or six courses of blocks, no which listed nine separate dwelling specs as supplemented by extract fans in wet rooms
one will know’.” a guide to achieving compliance with the new will be sufficient to maintain indoor air quality
regime. The spec for all nine included the follow- in super-insulated, airtight homes, the regulations
Archie O’Donnell also has concerns about dry ing example: block-built cavity walls with 100 are making air quality hostage to commercial
lining your average cavity wall. In an email to to 140mm partial fill cavity insulation in a 150mm expediency. If a developer isn’t required to spend
Passive House Plus, he said: “It appears a wide cavity, and 50mm of dry lining on the inner money on delivering a working ventilation strategy,
sensible approach to achieve 0.18 to 0.2 U- leaf. This is exactly the kind of build-up that the he won’t.
value walls: build 100 - 120mm cavity with 60 experts interviewed for this article describe as
- 80mm insulation, and then dry line it with a problematic. “All of the evidence that we see on a weekly
50mm composite board. While this method basis,” says Simon Jones, “and all of the evidence
has big advantages in that it gets very good One of the most worrying aspects of the mould we see through modelling shows that there is
U-Values and uses familiar skills and materi- and condensation problems that appear in new a point at which natural ventilation and intermittent
als, it comes with inherent problems.” builds is that in many cases, these houses com- fans don’t provide adequate indoor air quality.”
ply fully with the requirements of the technical
He explains that when you split the insulation guidance documents, and therefore meet prima Mark Shirley agrees. “Part of the problem at
in two, the temperature of the inner leaf can facie compliance with the building regulations. the moment is that DEAP [the software used
drop below dew point temperature. People Simon Jones says that in the development where to calculate building energy ratings and
ph+ 83
insight
Photo: Gavin Ó Sé
structure of buildings. thermal bridge – potentially adding significant
additional costs just to establish how good or
Moral hazard raises its head again and again bad the chosen details are.
in this debate. Brian Shannon of Building En-
velope Technologies in Wexford says that Alternatively a Y-value of 0.08 can be used for
cheap make-shift airtightness products are details in accordance with the acceptable
going into new houses all the time. He notes construction details (ACD) created to support
that while these products may deliver a target the 2008 regs. But as Lundberg points out,
airtightness level in the short term, they will the ACDs are incomplete – they don’t include
ultimately fail. “If you gave me a house that’s a door threshold detail, or other common de-
achieving an air permeability of 20 and gave tails such as a roof insulated on the ceiling
me a box of masking tape, I’d get that house plane with a rooflight installed at rafter level.
down to passive standard for you, no prob- “Where a dwelling has a roof-light installed
lem, but that masking tape just won’t last.” but uses a 0.08 Y-value, the conclusion can
only therefore be that the BER assessor or
Then there’s thermal bridging. As houses be- client has had thermal modelling carried out
come more thermally efficient, thermal bridging to determine the psi-values of this and any
becomes more important. If it is not adequately other junction requiring assessment, and the
dealt with at key junctions, it can have a severely Y-value happened to work out at 0.08 by pure
demonstrates compliance with Part L] can’t negative impact on the overall performance coincidence.” As Shannon adds, compliance
account for any of the kinds of systems that of a house. TGD L’s response is that the Y- with the ACDs is not independently validated.
companies like Aereco or Partel in Galway are value – the total thermal bridging factor for the
bringing in, where you have a mechanical building – can be derived in several ways. A de- “In DEAP, you can enter a figure of 0.08 for
room vent operated quite often on a humidity fault Y-value of 0.15 W/m2k can be used, though thermal bridging, and that will increase your
sensor or carbon dioxide sensor. These are this would be punitively bad in the case of thermal performance dramatically [compared
good technologies, but unless the builder is buildings with even moderately good thermal to the 0.15 default]. To use that value, all you
going to reap some benefit from making the bridging details, and would make compliance need is a letter from the developer or the architect
investment, it’s hard to see them becoming tricky. Building fabric consultant & NSAI ac- which says you built to ACDs.” He cites a recent
more common.” credited thermal modeller Andy Lundberg of development he visited in which extensive
Passivate warns that TGD L stipulates that thermal bridging issues were utterly misrep-
Note that the mould growth issues identified thermal bridges must not cause mould growth. resented in the energy rating assessment.
in this article all occurred before occupancy – “You can use a value of 0.15 in any case, how-
granted, while the buildings were drying out. ever in doing so you’re stating that none of the Energy efficiency standards for dwellings in
Add people into the mix and the potential risks junctions present a risk of mould growth and Ireland have come a long way over the past
may increase dramatically. In this climate, drying surface condensation, and therefore must have ten years. But one developer is critical of the
clothes inside is more the rule than the exception – been assessed in accordance with the relevant standards he now has to meet. Again, he asked
especially in apartments – while Irish home- standards and conventions for thermal bridge to remain anonymous. “There’s a law of dimin-
owners have a long history of blocking up hole- assessment. That’s absolutely not being done. ishing returns on this environmental stuff,” he
in-the-wall vents. Over-occupancy and what As one of only two NSAI certified modellers, says. “If you went out to buy a new car for your
the industry calls ‘excess’ furnishings can further I’ve not once received a phone call from any- family, your first thoughts wouldn’t be a Bentley
compromise a natural ventilation strategy. one seeking to have junctions assessed so or a Rolls Royce, you’d buy a Toyota Corolla
they can use 0.15.” or a middle range car... From a builder’s point
“It’s my belief that at anything below five air changes of view, we have now been forced to create a
at N50,” says Simon Jones, “a ventilation strat- Lundberg points out that the National BER level of administration and that has to be paid
egy needs to be in place that takes a large el- Research Tool – which contains detailed in- for by the customer.”
ement of control away from mother nature and formation on all published BERs, including in-
away from people. There’s too much at stake formation on Part L compliance – shows 140 Strictly speaking, this is incorrect. As leading
when it comes to indoor air quality.” dwellings built in 2014 with a 0.15 Y-value listed. property economist Tom Dunne explained in
“One can only assume that the BER assessor this magazine’s predecessor Construct Ire-
It is vital to point out that the problem here is in each of these cases has the relevant doc- land3, the market determines what price it’s
inadequate ventilation, not airtightness. The umentation on file to demonstrate that all junc- prepared to pay for property, and new homes
common misconception about airtightness is tions (non-ACD/catalogued) are free of any must be considered as a part of the available
that it is solely about the improvement of ther- mould growth and surface condensation risk, stock that’s up for sale at any given time. Buy-
mal performance. The reality is that it’s about which they are required to!” ers may be prepared to pay more, as the
structure —after extensive research, the Passive aforementioned reports indicate, but suppose
House Institute settled on 0.6 air changes per Another option is to commission a certified the developer bidding to buy the land wasn’t
hour as a target to mitigate the risk of intersti- and registered thermal bridging modelling as- convinced. They’d work out what price they
tial condensation and its implications for the sessor to calculate the Psi-values for each reckoned each unit might go for, deduct the
construction costs – including cost of compli-
Photo: Paul McNally
ph+ 85