BS EN 15651-1:2012

Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

BSI Standards Publication

Sealants for non-structural


use in joints in buildings and
pedestrian walkways
Part 1: Sealants for facade elements

NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW

raising standards worldwide™


BS EN 15651-1:2012 BRITISH STANDARD

National foreword
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

This British Standard is the UK implementation of EN 15651-1:2012.


It supersedes BS EN 15651-1:2010 which is withdrawn.
The UK participation in its preparation was entrusted to Technical
Committee B/547, Sealants for building and construction.
A list of organizations represented on this committee can be
obtained on request to its secretary.
This publication does not purport to include all the necessary
provisions of a contract. Users are responsible for its correct
application.
© The British Standards Institution 2012. Published by BSI Standards
Limited 2012
ISBN 978 0 580 76842 2
ICS 91.100.50
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 30 September 2012.
Amendments issued since publication
Date Text affected
BS EN 15651-1:2012

EUROPEAN STANDARD EN 15651-1


NORME EUROPÉENNE
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

EUROPÄISCHE NORM September 2012

Supersedes EN 15651-1:2010
ICS 91.100.50

English Version

Sealants for non-structural use in joints in buildings and


pedestrian walkways - Part 1: Sealants for facade elements

Mastics pour joints pour des usages non structuraux dans Fugendichtstoffe für nicht tragende Anwendungen in
les constructions immobilières et pour chemins piétonniers Gebäuden und Fußgängerwegen - Teil 1: Fugendichtstoffe
- Partie 1 : Mastics pour éléments de façade für Fassadenelemente

This European Standard was approved by CEN on 10 August 2012.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels

© 2012 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15651-1:2012: E
worldwide for CEN national Members.
BS EN 15651-1:2012
EN 15651-1:2012 (E)
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Contents Page

Foreword ..............................................................................................................................................................3
1 Scope ......................................................................................................................................................4
2 Normative references ............................................................................................................................4
3 Terms and definitions ...........................................................................................................................5
4 Requirements .........................................................................................................................................5
4.1 Identification requirements and test methods ....................................................................................5
4.1.1 Short description of the sealant ...........................................................................................................5
4.1.2 Thermogravimetric test .........................................................................................................................5
4.1.3 Specific gravity ......................................................................................................................................6
4.1.4 Indentation hardness (Shore hardness) ..............................................................................................6
4.2 Conditioning, test procedure and substrates .....................................................................................6
4.3 Performance requirements and test methods for non-structural sealants for facade
elements .................................................................................................................................................7
4.3.1 General ....................................................................................................................................................7
4.3.2 Sealants for facade elements used in cold climates..........................................................................8
4.3.3 Resistance to flow .................................................................................................................................9
4.4 Performance requirements for non-structural sealants for facade elements for interior
application only......................................................................................................................................9
4.5 Release of dangerous substances.......................................................................................................9
4.6 Reaction to fire .......................................................................................................................................9
4.6.1 General ....................................................................................................................................................9
4.6.2 Mounting and fixing conditions for test samples...............................................................................9
5 Durability ............................................................................................................................................. 12
6 Sampling .............................................................................................................................................. 12
7 Evaluation of conformity .................................................................................................................... 12
7.1 General ................................................................................................................................................. 12
7.2 Initial type testing ............................................................................................................................... 12
7.3 Factory production control ................................................................................................................ 12
8 Marking and labelling ......................................................................................................................... 12
Annex A (informative) Example on the frequency of tests for factory production control ...................... 13
Annex ZA (informative) Clause of this European Standard addressing the provisions of EU
Construction Products Directive....................................................................................................... 14
ZA.1 Scope and relevant characteristics .................................................................................................. 14
ZA.2 Procedure for attestation of conformity of non-structural sealants for external and/or
internal side of facade elements ....................................................................................................... 16
ZA.2.1 Systems of attestation of conformity ............................................................................................... 16
ZA.2.2 EC certificate of conformity and EC declaration of conformity ..................................................... 19
ZA.3 CE marking and labelling ................................................................................................................... 23
ZA.3.1  General ................................................................................................................................................. 23
ZA.3.2  CE marking on the packaging ........................................................................................................... 23
ZA.3.3  CE marking in the accompanying commercial documents ........................................................... 24
Bibliography ..................................................................................................................................................... 26

2
BS EN 15651-1:2012
EN 15651-1:2012 (E)
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Foreword
This document (EN 15651-1:2012) has been prepared by Technical Committee CEN/TC 349 “Sealants for
joints in building construction”, the secretariat of which is held by AFNOR.

This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by March 2013, and conflicting national standards shall be withdrawn at
the latest by June 2014.

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.

This document supersedes EN 15651-1:2010.

This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).

For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.

This document is one of the product European Standards within the framework series of EN 15651 on
Sealants for non-structural use in joints in buildings and pedestrian walkways, as follows:

 Part 1: Sealants for facade elements (this document),

 Part 2: Sealants for glazing,

 Part 3: Sealants for sanitary joints,

 Part 4: Sealants for pedestrian walkways,

 Part 5: Evaluation of conformity and marking.

The following significant technical changes have been implemented in this new edition:

 an Annex ZA has been added;

 the clause on reaction to fire was improved.

According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

3
BS EN 15651-1:2012
EN 15651-1:2012 (E)

1 Scope
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

This European Standard specifies definitions and requirements for non-structural facade sealants intended for
sealing exterior wall joints, window and door perimeter joints in building construction, including the interior
face.

NOTE Provisions on evaluation of conformity (i.e. Initial Type Testing and Factory Production Control) and marking of
these products are given in EN 15651-5.

This European Standard does not apply to non-structural sealants in any of non-paste form, to those used in
internal walls and/or partitions and to oil-based mastics.

2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.

EN 13238, Reaction to fire tests for building products  Conditioning procedures and general rules for
selection of substrates

EN 13501-1:2007+A1, Fire classification of construction products and building elements  Part 1:


Classification using data from reaction to fire tests

EN 15651-5:2012, Sealants for non-structural use in joints in buildings and pedestrian walkways  Part 5:
Evaluation of conformity and marking

EN ISO 868, Plastics and ebonite  Determination of indentation hardness by means of a durometer
(Shore hardness) (ISO 868)

EN ISO 1183-1:2004, Plastics  Methods for determining the density of non-cellular plastics  Part 1:
Immersion method, liquid pyknometer method and titration method (ISO 1183-1:2004)

EN ISO 6927:2012, Buildings and civil engineering works — Sealants — Vocabulary (ISO 6927:2012)

EN ISO 7389, Building construction  Jointing products  Determination of elastic recovery of sealants
(ISO 7389)

EN ISO 7390, Building construction  Jointing products  Determination of resistance to flow of sealants
(ISO 7390)

EN ISO 8339, Building construction  Sealants  Determination of tensile properties (Extension to break)
(ISO 8339)

EN ISO 8340, Building construction  Sealants  Determination of tensile properties at maintained extension
(ISO 8340)

EN ISO 9046, Building construction  Jointing products  Determination of adhesion/cohesion properties of


sealants at constant temperature (ISO 9046)

EN ISO 9047, Building construction  Jointing products  Determination of adhesion/cohesion properties of


sealants at variable temperatures (ISO 9047)

EN ISO 10563, Building construction  Sealants  Determination of change in mass and volume
(ISO 10563)

4
BS EN 15651-1:2012
EN 15651-1:2012 (E)

EN ISO 10590, Building construction  Sealants  Determination of tensile properties of sealants at


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

maintained extension after immersion in water (ISO 10590)

EN ISO 10591, Building construction  Sealants  Determination of adhesion/cohesion properties of


sealants after immersion in water (ISO 10591)

EN ISO 11358, Plastics  Thermogravimetry (TG) of polymers  General principles (ISO 11358)

EN ISO 11600, Building construction  Jointing products  Classification and requirements for sealants
(ISO 11600)

EN ISO 11925-2, Reaction to fire tests  Ignitability of products subjected to direct impingement of flame 
Part 2: Single-flame source test (ISO 11925-2)

ISO 13640, Building construction  Jointing products  Specifications for test substrates

3 Terms and definitions


For the purposes of this document, the terms and definitions given in EN ISO 6927:2012 and the following
apply.

3.1
non-reactive sealant
mainly physical drying mechanism, without significant change in the molecular weight of the main polymer

3.2
reactive sealant
mainly curing by chemical reaction, with significant increase of the molecular weight of the main polymer

3.3
cure
irreversible transformation of a sealant from a liquid or paste-like state into a hardened or rubber-like solid
state

3.4
uncured/wet
state of a sealant prior to the above transformation

4 Requirements

4.1 Identification requirements and test methods

4.1.1 Short description of the sealant

The short description of the non-structural sealant for facade elements shall include brand name, type
(general chemical family), opaque or translucent, waterborne or solvent based or solvent free, reactive or non-
reactive, and one or multi-component (e.g. waterborne acrylic opaque and one component, etc.).

The primer shall be stated for the substrate concerned, if relevant (name, chemical type, etc.).

4.1.2 Thermogravimetric test

The test shall be carried out in accordance with EN ISO 11358 on the uncured or wet sealant, between 35 °C
and 900 °C, temperature slope 10 °C/min, non-oxidative condition (e.g. nitrogen). A single sample shall be

5
BS EN 15651-1:2012
EN 15651-1:2012 (E)

used for this test. A single specimen may be tested and there shall be no significant difference between the
reference curve and derivative (profile).
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

In the case of a multi-component sealant, each component shall be evaluated (if relevant).

4.1.3 Specific gravity

The determination of the specific gravity shall be in accordance with EN ISO 1183-1:2004, on the uncured or
wet sealant, using Method A or Method B, depending on the type of sealant under test. The testing
temperature shall be (23 ± 2) °C. At least three samples shall be tested. The method used and the mean
value, recorded to two decimal places, shall be declared. The tolerance of the declared values shall be within
± 5 %.

In the case of a multi-component sealant, each component shall be evaluated.

4.1.4 Indentation hardness (Shore hardness)

The determination of the indentation hardness shall be in accordance with EN ISO 868. The test shall be
performed on the cured or dried sealant.

The exact conditions of test shall be defined by the manufacturer (i.e. thickness, cure/drying times and
temperature and relative humidity, specific Shore type (A, D…), test time, temperature, etc.).

At least three samples shall be tested and five measurements taken per sample. The mean value and
tolerances of all measurements, recorded to the nearest unit, shall be declared.

4.2 Conditioning, test procedure and substrates

When determining the classification of a facade sealant according to the requirements of this standard, the
same conditioning procedure shall be used in all relevant test methods (Method A or Method B conditioning
shall be used for all relevant tests). For each test method, three test specimens for each substrate shall be
tested. The same batch of sealant (and primer, if used) shall be used in all tests. The same substrates
(material and surface finish) shall be used in all tests.

The specific test conditions shall be in accordance with Table 1.

Table 1 — Specific test conditions

Classes of non-structural sealants for facade elements


Test method
25LM 25HM 20LM 20HM 12,5E 12,5P 7,5P
a
Elongation EN ISO 7389 100 % 100 % 60 % 60 % 60 % 60 % 25 %
EN ISO 8339
EN ISO 8340
EN ISO 10590
Amplitude EN ISO 9046 ± 25 % ± 25 % ± 20 % ± 20 % ± 12,5 % ± 12,5 % ± 7,5 %
EN ISO 9047
a
The value of elongation is given as a percentage of the original width:
elongation % = [(final width – original width) / (original width)] x 100 %

Substrates to be used in all mechanical tests concerned shall be mortar M1 or M2 and/or anodised aluminium
and/or glass, according to ISO 13640.

6
BS EN 15651-1:2012
EN 15651-1:2012 (E)

4.3 Performance requirements and test methods for non-structural sealants for facade
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

elements

4.3.1 General

Classes of non-structural sealants to be used for joints in facade elements in buildings are referred to as
type F according to EN ISO 11600.

A summary of the characteristics and classes, together with corresponding test methods for these
characteristics shall be as given in Table 2.

NOTE The requirements for non-structural sealants for interior application only are covered by Table 4.

Table 2 — Summary of classes for non-structural sealants for facade elements

Class of sealant for facade elements

Characteristic 25LM 25HM 20LM 20HM 12,5E 12,5P 7,5P Method of test

Elastic recovery (%) ≥ 70 ≥ 70 ≥ 60 ≥ 60 ≥ 40 < 40 < 40 EN ISO 7389


Resistance to flow (mm) ≤3 ≤3 ≤3 ≤3 ≤3 ≤3 ≤3 See 4.3.3.
Tensile properties
≤ 0,4 > 0,4 ≤ 0,4 > 0,4
1) Secant modulus (MPa)    EN ISO 8339
(23 °C) (23 °C) (23 °C) (23 °C)
and or and or
≤ 0,6 > 0,6 ≤ 0,6 > 0,6   
(- 20 °C) (- 20 °C) (- 20 °C) (- 20 °C)
≥ 100 ≥ 25
2) Elongation at break (%)     
(23 °C) (23 °C)
Tensile properties at
NF NF NF NF NF   EN ISO 8340
maintained extension
Adhesion/cohesion at
NF NF NF NF NF   EN ISO 9047
variable temperatures
Adhesion/cohesion at
maintained extension NF NF NF NF NF   EN ISO 10590
after water immersion

≤ 10 ≤ 10 ≤ 10 ≤ 10 ≤ 25
Loss of volume (%) a a a a ≤ 25 ≤ 25 EN ISO 10563
≤ 25 ≤ 25 ≤ 25 ≤ 25 ≤ 30
a

Adhesion/cohesion at
     NF NF EN ISO 9046
constant temperature
Adhesion/cohesion after
water immersion:
- Elongation (%) at 23 °C      ≥ 100 ≥ 25 EN ISO 10591
a
Water-based dispersion sealants.
NF = No Failure according to EN ISO 11600.

7
BS EN 15651-1:2012
EN 15651-1:2012 (E)

4.3.2 Sealants for facade elements used in cold climates


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

4.3.2.1 General

This test has been developed to demonstrate that elastic sealants for exterior use perform well at lower
temperatures than those currently tested at in EN ISO 11600 (e.g. common winter temperatures in Northern
Europe). The specific intention is to ensure that the sealant continues to perform at – 30 ºC, which is a
common winter temperature in cold climate areas. The test is not relevant for plastic sealants (as defined by
classes 12,5P and 7,5P in Table 2).

In addition to the requirements given in Table 2, elastic non-structural sealants for facade elements required to
maintain performance in cold climates (- 30 °C) shall fulfil the requirements given in Table 3.

The classification of the sealant given in Table 2 shall be determined prior to this optional additional test and
the corresponding test amplitude shall be applied to this additional test.

The designation CC (cold climate) shall be declared for any sealant meeting the requirements of Table 2. For
example, Type F Class 25LM CC.

Anodised aluminium or/and glass and/or mortar M1 or M2 substrates, according to ISO 13640, shall be used.

4.3.2.2 Tensile properties - Secant modulus to EN ISO 8339 - Test procedure at (- 30 ± 2) °C

The test specimens shall be stored at (- 30 ± 2) ° for at least 4 h before the start of the test. The spacers for
the preparation of the test specimens shall be removed and the test specimen placed in the tensile test
machine and extended at (- 30 ± 2) °C at a rate of (5,5 ± 0,7) mm/min until rupture occurs. The
force/extension diagram shall be recorded.

4.3.2.3 Tensile properties at maintained extension to EN ISO 8340 - Test procedure at (- 30 ± 2) °C

The test specimens shall be stored at (− 30 ± 2) °C for at least 4 h before the start of the test. The spacers for
the preparation of the test specimens shall be removed and the test specimens placed in the tensile test
machine at (- 30 ± 2) °C and extended at a rate of (5,5 ± 0,7) mm/min by 60 % or 100 % of the original width
(to 19,2 mm and 24 mm respectively), The separators shall be used to maintain the elongation at (- 30 ± 2) °C
for 24 h. The test specimens shall be brought to (23 ± 2) °C. The depth of any loss of adhesion or cohesion
shall be measured using a suitable measuring device capable of reading to 0,5 mm.

Table 3 — Requirements to be suitable for use in cold climate areas

Classes of non-structural sealants for sealants for


facade elements in cold climates
Characteristics 25LM 25HM 20LM 20HM 12,5
E Test method

Tensile properties: a a a
MPa ≤ 0,9 NR ≤ 0,9 NR NR 4.3.2.2
- Secant modulus

b b b b b
Tensile properties at - NF NF NF NF NF
4.3.2.3
maintained extension

a
NR = Not required.
b
NF = No failure according to EN ISO 11600.

8
BS EN 15651-1:2012
EN 15651-1:2012 (E)

4.3.3 Resistance to flow


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

The resistance to flow shall be measured according to EN ISO 7390, with the precise test method modified
according to the following details:

A vertical, anodised aluminium U-profile shall be used with dimensions 20 mm × 10 mm. Testing shall be
carried out under two test temperature conditions:

a) temperature of (50 ± 2) °C and relative humidity of (50 ± 10) %;

b) temperature of (5 ± 2) °C.

If the flow exceeds the required value, then the test may be repeated once.

4.4 Performance requirements for non-structural sealants for facade elements for interior
application only

For non-structural sealants for facade elements that are only used for interior application, the minimum
performance requirements given in Table 4 shall be met. Facade sealants only complying with these
requirements shall be clearly marked “suitable for internal use only” and cannot be classified according to
Table 2.

Table 4 — Requirements for sealants for facade elements for interior application only

Requirement for sealants for


Characteristic Method of test
Interior facade elements

Resistance to flow mm ≤5 See 4.3.3.


Tensile properties:
Elongation at break at 23 °C % ≥ 25 EN ISO 8339

Loss of volume % ≤ 45 EN ISO 10563

4.5 Release of dangerous substances

Materials used in products shall not release any dangerous substances in excess of the maximum permitted
levels specified in a relevant European Standard for the material or permitted in the national regulations of the
member state of destination.

NOTE In the absence of specific requirements relating to substances dangerous to health, hygiene and the
environment in this document, see Annex ZA.

4.6 Reaction to fire

4.6.1 General

Products shall be classified in accordance with EN 13501-1:2007+A1. The appropriate reaction to fire class
shall be declared.

4.6.2 Mounting and fixing conditions for test samples

Mounting and fixing conditions for the test samples of the reaction to fire performance shall be as follows for
the following reaction to fire classes:

a) Class A2, B, C or D

9
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Design of specimen:
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

1) substrate: calcium silicate panel

b) Class E

Design of specimen:

1) substrate: beech wood, mean bulk density about 720 kg/m³, or calcium silicate panel according to
EN 13238

2) joint dimension: 20 mm x 10 mm x 250 mm (width x depth x length) , see Figure 1

3) conditioning: 28 days at (23 ± 2) °C and (50 ± 5) % relative humidity (according to EN 13238)

4) number of specimens: 6 (according to EN ISO 11925-2)

5) fire test: impingement of flame in centre to the bottom edge (according to EN 11925-2)

The substrates are not standard-substrates according to EN 13238. They serve only to prepare a
standardised sample according to EN ISO 11925-2.

Furthermore, the defined joint dimension is not a classification parameter with respect to the dimension of the
tested product. If the product meets the test requirements, it should be classified independently from its
dimensions.

10
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

2
1
Key:

sealant
substrate

Figure 1 – Test specimen


BS EN 15651-1:2012

Dimensions in millimetres

11
EN 15651-1:2012 (E)
BS EN 15651-1:2012
EN 15651-1:2012 (E)

5 Durability
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

The durability of a sealed joint is only as good as both the adhesion of the sealant (and primer) to the surfaces
forming the joint and also the cohesive stability of the sealant itself. It is important that the sealant has
sufficient adhesion and cohesion to survive the mechanical and environmental stresses to which the sealed
joint is likely to be exposed.

These characteristics shall be evaluated:

 without any ageing, according to EN ISO 8339 or EN ISO 8340,

 after ageing, according to EN ISO 9046, EN ISO 9047, EN ISO 10590 or EN ISO 10591 depending on
the class of sealants given in Table 2.

The sealant performance is determined by classification to Table 2 and this classification will indicate suitable
durability of the sealant after ageing. Long-term durability of joints based on such sealants is obtained when
they are selected and applied according to the sealant data sheets, taking into account the expected service
conditions on site.

Sealants are easy to use, ready to use and easy to remove when any unavoidable or unexpected degradation
arises.

6 Sampling
General requirements for sampling of the sealant shall be as set out in EN 15651-5.

7 Evaluation of conformity

7.1 General

The factory production control (FPC) needs to be defined by each sealant manufacturer in order to show
compliance to the level of performance indicated in the initial type testing (ITT).

7.2 Initial type testing

General requirements for the initial type testing of the sealant shall be as set out in EN 15651-5.

7.3 Factory production control

Requirements for the initial type testing of the sealant shall be in accordance with EN 15651-5.

An example of suitable frequency of identification and performance tests for FPC is given in Annex A.
Frequencies may be increased during initial production or following an incident of non-conformity.

Any deviation from this guidance should be justified by documented evidence that demonstrates equivalence.

8 Marking and labelling


Requirements for marking and labelling shall be as set out in EN 15651-5.

NOTE For CE marking and labelling, ZA.3 applies.

12
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Annex A
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

(informative)

Example on the frequency of tests for factory production control

An example of a suitable frequency of identification and performance tests for factory production control of
sealants for façade elements is given in Table A.1.

Table A.1 — Example of the frequency of tests for factory production control

One test on the appearance of the sealant such as FA


colour, homogeneity, etc.
One test on the uncured or wet product such as FA
viscosity, density, skin over time, stringiness, extrusion
rate, etc.
For reactive sealants: one test on the cured sealant FB
such as indentation hardness, adhesion peeling test,
tensile properties, etc.
Resistance to flow (4.3.3), loss of volume FC
(EN ISO 10563),
Facade sealants, classes 25LM, 25HM, 20LM, 20HM FC
and 12,5E : determination of adhesion/cohesion
properties at maintained extension after immersion in
water (EN ISO 10590)
All other classified facade sealants: determination of FC
adhesion/cohesion properties of sealants after
immersion in water (EN ISO 10591)
Facade sealants only suitable for interior use: FC
determination of tensile properties (EN ISO 8339)
FA – every batch (definition of batch given in EN 15651-5:2012)
FB – every week
FC – once per year
All tests shall be carried out on the same batch.

13
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Annex ZA
(informative)
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Clause of this European Standard addressing the provisions of EU


Construction Products Directive

ZA.1 Scope and relevant characteristics


This European Standard has been prepared under Mandate M/474 "Sealants for non-structural use in joints in
buildings and pedestrian walkways” given to CEN by the European Commission and the European Free Trade
Association.

The clauses of this and other European Standards shown in this annex meet the requirements of this mandate
given under the EU Construction Products Directive (89/106/EEC).

Compliance with these clauses confers a presumption of fitness of the products covered by this annex for the
intended uses indicated herein: reference shall be made to the information accompanying the CE marking.

WARNING: Other requirements and other EU Directives, not affecting the fitness for intended uses, can
be applicable to the construction products falling within the scope of this annex.

NOTE 1 In addition to any specific clauses relating to dangerous substances contained in this standard, there may be
other requirements applicable to the products falling within its scope (e.g. transposed European legislation and national
laws, regulations and administrative provisions). In order to meet the provisions of the EU Construction Products
Directive, these requirements need also to be complied with, when and where they apply.

NOTE 2 An informative database of European and national provisions on dangerous substances is available at the
Construction web site on EUROPA (accessed through http://ec.europa.eu/enterprise/construction/cpd-ds/ ).

This annex establishes the conditions for the CE marking of non-structural sealants for the external and/or
internal side of facade elements for the uses indicated in Table ZA.1 a) and Za.1 b) and shows the relevant
clauses applicable.

This annex has the same scope as Clause 1 of this standard and is defined by Tables ZA.1 a) and ZA.1 b).

14
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Table ZA.1 a) — Scope and relevant clauses


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Construction products: Sealants for facade


Intended use: Sealants for exterior application

Requirement
clauses in Level(s) or
Essential characteristics Notes
this European class(es)
Standard

REACTION TO FIRE 4.6 Class Classified acc. to EN 13501-1:2007+A1 after


A1 to F being tested acc. to relevant test standards
given therein

RELEASE OF CHEMICALS DANGEROUS TO 4.5 - Evaluation


a
THE ENVIRONMENT AND HEALTH

WATER TIGHTNESS and AIR TIGHTNESS

a) Resistance to flow 4.3.1 - tested acc. to modified EN ISO 7390 and


expressed as a declared flow (in mm)
b
≤ 5 mm or ≤3 mm

b) Loss of volume 4.3.1 tested acc. to EN ISO 10563 and expressed as


a declared loss of volume (in %)
b
≤ 10% or ≤25% or ≤30% or ≤45%

c) Tensile properties (i.e. elongation): 4.3.1 tested acc. to EN ISO 10591 and expressed as
a threshold value (in %)
- after immersion in water at (23 °C),
(Plastic), or ≥ 25 % or ≥ 100 %

- at maintained extension after water Tested acc. to EN ISO 10590 and expressed as
Pass/fail criteria
immersion (Elastic)

d) Tensile properties (i.e. secant 4.3.2 - Low modulus sealants tested according to
modulus): modified EN ISO 8339 and expressed as a
declared value
- for non-structural low modulus sealants
used in joints in cold climate areas ≤0,9 Mpa
(-30°C)

e) Tensile properties (i.e. at maintained 4.3.2 - Tested according to modified EN ISO 8340 and
extension): expressed as a pass/fail criteria
NF
- for non-structural sealants used in joints
in cold climate areas (-30°C)

DURABILITY 5 - Pass/Fail criteria


a
See ZA.1, Notes 1 and 2.
b
These values are introduced to enable CE marking without excluding existing products that are fit for purpose and currently placed
on the European market.
NOTE Depending on the performance requirements of the joint design, these minimum requirements may not be sufficient. Then, a
sealant of higher performance shall be used (see classes in 4.3, Table 2).

15
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Table ZA.1 b) — Scope and relevant clauses


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Construction products: Sealants for façade

Intended use: Sealants for interior application only

Requirement
Level(s)
clauses in this
Essential characteristics or Notes
European
class(es)
Standard

REACTION TO FIRE 4.6 Class Classified acc. to EN 13501-1:2007+A1 after being


A1 to F tested acc. to relevant test standards given therein

RELEASE OF CHEMICALS DANGEROUS TO 4.5 -


a
THE ENVIRONMENT AND HEALTH

WATER TIGHTNESS and AIR TIGHTNESS


4.4 tested acc. to modified EN ISO 7390 and expressed
a) Resistance to flow, and -
as a threshold value (in mm)
b
≤ 5 mm

b) Loss of volume, and tested acc. to EN ISO 10563 and expressed as a


threshold value (in %)
b
≤ 45 %

c) Tensile properties (i.e. elongation): tested acc. to EN ISO 8339 and expressed as a
threshold value (in %)
- at break at (23 °C)
≥ 25 %

DURABILITY 5 Pass/Fail criteria


a
See ZA.1 Notes 1 and 2
b
These values are introduced to enable CE marking without excluding existing products that are fit for purpose and currently placed
on the European market.

NOTE 1 Depending on the performance requirements of the joint design, these minimum requirements may not be sufficient. Then, a
sealant of higher performance shall be used (see classes in 4.3, Table 2).
NOTE 2 Sealants meeting the water tightness and air tightness requirements for exterior sealants are considered to meet the
requirement for sealants for interior application.

The requirement on a certain essential characteristic is not applicable in those Member States (MSs) where
there are no requirements on that characteristic for the intended use of the product. In this case,
manufacturers placing their products on the market of these MSs are not obliged to determine nor to declare
the performance of their products with regard to this characteristic and the option “No performance
determined” (NPD) in the information accompanying the CE marking (see ZA.3) may be used. The NPD
option may not be used, however, where the characteristic is subject to a threshold level.

ZA.2 Procedure for attestation of conformity of non-structural sealants for external


and/or internal side of facade elements

ZA.2.1 Systems of attestation of conformity

The systems of attestation of conformity for the non-structural sealants for external and/or internal side of
facade elements indicated in Tables ZA.1 a) and ZA.1 b) in accordance with the Decision of the Commission
2011-19-EU of 2011-01-14 as given in Annex III of the Mandate for “Sealants for non-structural use in joints in
buildings and pedestrian walkways”, are shown in Table ZA.2 for the indicated intended uses and relevant
classes.

16
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Table ZA.2 — Systems of attestation of conformity


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Attestation of
Product(s) Intended use(s) Level(s) or class(es)
conformity system(s)

Sealants for external


perimeter wall, window and Outdoor (Exterior)
 3
door joints (facade applications
elements)

Sealants for application


only to the interior face of
Indoor (Interior)
external perimeter wall,  4
applications
window and door joints
(facade elements)

A1*, A2*, B*, C* 1


For uses subject to
Sealants for non-structural
reaction to fire (A1**, A2**, B**, C**, D), E 3
use in joints in buildings
regulations
(A1 to E)***, F 4

System 1: See Directive 89/106/EEC Annex III.2 (i), without audit-testing of samples.
System 3: See Directive 89/106/EEC, Annex III.2(ii), Second possibility.
System 4: See Directive 89/106/EEC Annex III.2(ii), Third possibility.

* Products/materials for which a clearly identifiable stage in the production process results in an improvement of
the reaction to fire classification (e.g. an addition of fire retardants or a limiting of organic material).
** Products/materials not covered by footnote (*).
*** Products/materials that do not require to be tested for reaction to fire (e.g. Products/materials of class A1
according to the Commission Decision 96/603/EC, as amended).

The attestation of conformity of the non-structural sealants for external and/or internal side of facade elements
in Tables ZA.1 a) and ZA.1 b) shall be based on the evaluation of conformity procedures indicated in
Tables ZA.3.1 to ZA.3.6 resulting from the application of those clauses of this or other European Standards
indicated therein.

17
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Table ZA.3.1 — Assignment of evaluation of conformity tasks for exterior facade of Euroclasses A1*,
A2*, B*, C* subject to reaction to fire regulations (system 3 plus 1)
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Evaluation of conformity
Tasks Content of the task
clauses to apply
Factory production Parameters related to all characteristics in 7.3 with link to 5.3 of
control (FPC) Table ZA.1 EN 15651-5:2012
Further testing of
Tasks under the
samples taken at All relevant characteristics of Table ZA.1 5.3 of EN 15651-5:2012
responsibility of the
the factory
manufacturer
Initial type testing by All relevant characteristics of Table ZA.1 7.2 with link to 5.2 of
a notified laboratory except: Reaction to fire EN 15651-5:2012
7.2 with link to 5.2 of
Initial type testing Reaction to fire
EN 15651-5:2012
Initial inspection of 7.3 with link to 5.3 of
Tasks under the Reaction to fire
factory and of FPC EN 15651-5:2012
responsibility of the
product certification Continuous
body surveillance, 7.3 with link to 5.3 of
Reaction to fire
assessment and EN 15651-5:2012
approval of FPC

Table ZA.3.2 — Assignment of evaluation of conformity tasks for sealants for exterior facade of
Euroclasses (A1**, A2**, B**, C**, D), E subject to reaction to fire regulations (system 3 plus 3)

Evaluation of conformity
Tasks Content of the task
clauses to apply
Factory production Parameters related to all characteristics in 7.3 with link to 5.3 of
control (FPC) Table ZA.1 EN 15651-5:2012
Tasks under the
responsibility of the Initial type testing by All relevant characteristics of Table ZA.1 7.2 with link to 5.2 of
manufacturer a notified test EN 15651-5:2012
laboratory

Table ZA.3.3 — Assignment of evaluation of conformity tasks for sealants for exterior facade of
Euroclasses (A1 to E)***, F subject to reaction to fire regulations (system 3 plus 4)

Tasks Content of the task Evaluation of conformity


clauses to apply
Factory production Parameters related to all 7.3 with link to 5.3 of
control (FPC) characteristics in Table ZA.1 EN 15651-5:2012
Tasks under the 7.2 with link to 5.2 of
responsibility of the Initial type testing by a All relevant characteristics of
notified testing laboratory Table ZA.1 except: Reaction to fire EN 15651-5:2012
manufacturer

Initial type testing by the Reaction to fire 7.2 with link to 5.2 of
manufacturer EN 15651-5:2012

18
BS EN 15651-1:2012
EN 15651-1:2012 (E)
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Table ZA.3.4 — Assignment of evaluation of conformity tasks for sealants for interior facade of
Euroclasses A1*, A2*, B*, C* subject to reaction to fire regulations (system 4 plus 1)

Evaluation of conformity
Tasks Content of the task
clauses to apply
Factory production Parameters related to all 7.3 with link to 5.3 of
control (FPC) characteristics in Table ZA.1 EN 15651-5:2012
Further testing of
Tasks under the All relevant characteristics of
samples taken at the 5.3 of EN 15651-5:2012
responsibility of the Table ZA.1
factory
manufacturer
All relevant characteristics of 7.2 with link to 5.2 of
Initial type testing
Table ZA.1 except: Reaction to fire EN 15651-5:2012
7.2 with link to 5.2 of
Initial type testing Reaction to fire
EN 15651-5:2012
Initial inspection of 7.3 with link to 5.3 of
Tasks under the Reaction to fire
factory and of FPC EN 15651-5:2012
responsibility of the
product certification Continuous
body surveillance, 7.3 with link to 5.3 of
Reaction to fire
assessments and EN 15651-5:2012
approval of FPC

Table ZA.3.5 — Assignment of evaluation of conformity tasks for sealants for interior facade of
Euroclasses (A1**, A2**, B**, C**, D), E subject to reaction to fire regulations (system 4 plus 3)

Evaluation of conformity
Tasks Content of the task
clauses to apply
Factory production Parameters related to all characteristics 7.3 with link to 5.3 of
control (FPC) in Table ZA.1 EN 15651-5:2012
Tasks under the
responsibility of the Initial type testing All relevant characteristics of 7.2 with link to 5.2 of
manufacturer Table ZA.1 except: Reaction to fire EN 15651-5:2012
Initial type testing by a Reaction to fire 5.2 of EN 15651-5:2012
notified test laboratory

Table ZA.3.6 — Assignment of evaluation of conformity tasks for sealants for interior facade not
subject to reaction to fire regulations or of Euroclasses (A1 to E)***, F subject to reaction to fire
regulations (system 4 plus 4)

Evaluation of conformity
Tasks Content of the task
clauses to apply
Factory production Parameters related to all characteristics 7.3 with link to 5.3 of
control (FPC) in Table ZA.1 EN 15651-5:2012
Tasks under the
responsibility of the All relevant characteristics of
manufacturer Initial type testing 5.2 of EN 15651-5:2012
Table ZA.1

ZA.2.2 EC certificate of conformity and EC declaration of conformity

The declaration and certificate shall be presented in the language or languages accepted in the Member State
in which the sealant is intended to be used.

19
BS EN 15651-1:2012
EN 15651-1:2012 (E)

ZA.2.2.1 Sealants for exterior facade under system 3 plus 1


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

Sealants for exterior facade under system 3 plus 1 (see Table ZA.3.1): When compliance with the conditions
of this Annex is achieved, the certification body shall draw up a certificate of conformity (EC Certificate of
conformity), which entitles the manufacturer to affix the CE marking. The certificate shall include:

 name, address and identification number of the notified certification body,

 name and address of the manufacturer, or his authorised representative established in the EEA, and
place of production,

NOTE 1 The manufacturer may also be the person responsible for placing the sealant onto the EEA market, if he takes
responsibility for CE marking.

 description of the sealant (use, type, class...),

 provisions to which the sealant conforms (i.e. Annex ZA of this EN),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

 the number of the certificate,

 conditions of validity of the certificate, where applicable,

 name of, and position held by, the person empowered to sign the certificate.

In addition, the manufacturer shall draw up and retain a declaration of conformity (i.e. EC declaration of
conformity) including the following:

 name and address of the manufacturer, or his authorised representative established in the EEA,

 name and address of the certification body,

 description of the sealant (use, type, class...), and a copy of the information accompanying the CE
marking,

NOTE 2 Where some of the information required for the declaration is already given in the CE marking, it does not
need to be repeated.

 provisions to which the sealant conforms (i.e. Annex ZA of this EN), and a reference to the ITT report(s)
and factory production control records (if appropriate),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

 number of the accompanying EC certificate of conformity,

 name and address of the notified laboratory,

 name of, and position held by, the person empowered to sign the declaration on behalf of the
manufacturer or of his authorised representative.

ZA.2.2.2 Sealants for exterior facade under system 3 plus 3

Sealants for exterior facade under system 3 plus 3 (see Table ZA.3.2): When compliance with the conditions
of this Annex is achieved, the manufacturer or his agent established in the EEA shall prepare and retain a
declaration of conformity, which entitles the manufacturer to affix the CE marking. This declaration shall
include:

20
BS EN 15651-1:2012
EN 15651-1:2012 (E)

 name and address of the manufacturer, or his authorised representative established in the EEA, and the
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

place of production,

 description of the sealant (use, type, class...), and copy of the information accompanying the CE marking,

 provisions to which the sealant conforms (i.e. Annex ZA of this EN),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

 name and address of the notified laboratory,

 name of, and position held by, the person empowered to sign the declaration on behalf of the
manufacturer or of his authorised representative.

ZA.2.2.3 Sealants for exterior facade under system 3 plus 4

Sealants for exterior facade under system 3 plus 4 (see Table ZA.3.3): When compliance with this Annex is
achieved, the manufacturer of his agent established in the EEA shall prepare and retain a declaration of
conformity (EC Declaration of conformity), which entitles the manufacturer to affix the CE marking. This
declaration shall include:

 name and address of the manufacturer, or his authorised representative established in the EEA, and the
place of production,

 description of the sealant (use, type, class...), and copy of the information accompanying the CE marking,

 provisions to which the sealant conforms (i.e. Annex ZA of this EN),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

 name and address of the notified laboratory,

 name of, and position held by, the person empowered to sign the declaration on behalf of the
manufacturer or of his authorised representative.

ZA.2.2.4 Sealants for interior facade under system 4 plus 1

Sealants for interior facade under system 4 plus 1 (see Table ZA.3.4): When compliance with the conditions of
this Annex is achieved, the certification body shall draw up a certificate of conformity (EC Certificate of
conformity), which entitles the manufacturer to affix the CE marking. The certificate shall include:

 name, address and identification number of the certification body,

 name and address of the manufacturer, or his authorised representative established in the EEA, and
place of production,

 description of the sealant (use, type, class…),

 provisions to which the sealant conforms (i.e. Annex ZA of this EN),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

 the number of the certificate,

 conditions of validity of the certificate, where applicable,

 name of, and positions held by, the person empowered to sign the certificate.

21
BS EN 15651-1:2012
EN 15651-1:2012 (E)

In addition, the manufacturer shall draw up and retain a declaration of conformity (i.e. EC Declaration of
conformity) including the following:
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

 name and address of the manufacturer, or his authorised representative established in the EEA,

 name and address of the certification body,

 description of the sealant (use, type, class, ...) and a copy of the information accompanying the CE
marking,

 provisions to which the sealant conforms (i.e. Annex ZA of this standard),

 particular conditions applicable to the use of the sealants (e.g. provisions for use under certain
conditions),

 number of the accompanying EC Certificate of conformity,

 name of, and position held by, the person empowered to sign the declaration on behalf of the
manufacturer or of his authorised representative.

ZA.2.2.5 Sealants for interior facade under system 4 plus 3

Sealants for interior facade under system 4 plus 3 (see Table ZA.3.5): When compliance with the conditions of
this Annex is achieved, and once the notified body has drawn up the certificate mentioned below, the
manufacturer or his agent established in the EEA shall prepare and retain a declaration of conformity, which
entitles the manufacturer to affix the CE marking. This declaration shall include:

 name and address of the manufacturer, or his authorised representative established in the EEA, and the
place of production,

 description of the sealant (use, type, class…) and copy of the information accompanying the CE marking,

 provisions to which the sealant conforms (i.e. Annex ZA of this EN),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

 name and address of the notified laboratory,

 name of, and position held by, the person empowered to sign the declaration on behalf of the
manufacturer or of his authorised representative.

ZA.2.2.6 Sealants for interior facade under system 4 plus 4

Sealants for interior facade under system 4 plus 4 (see Table ZA.3.6): When compliance with this Annex is
achieved, the manufacturer of his agent established in the EEA shall prepare and retain a declaration of
conformity (EC Declaration of conformity), which entitles the manufacturer to affix the CE marking. This
declaration shall include:

 name and address of the manufacturer, or his authorised representative established in the EEA, and the
place of production,

 description of the sealant (use, type, class…) and copy of the information accompanying the CE marking,

 provisions to which the sealant conforms (i.e. Annex ZA of this EN),

 particular conditions applicable to the use of the sealant (e.g. provisions for use under certain conditions),

22
BS EN 15651-1:2012
EN 15651-1:2012 (E)

 name of, and position held by, the person empowered to sign the declaration on behalf of the
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

manufacturer or of his authorised representative.

ZA.3 CE marking and labelling

ZA.3.1 General

The manufacturer or his authorised representative established within the EEA is responsible for the affixing of
the CE marking, which consists of the CE marking symbol as given by Directive 93/68/EEC, and for the
appropriate accompanying information.

NOTE It may be appropriate to specify a combination of location for the CE marking symbol and the accompanying
information. For example, a minimum of information could appear on the packaging (see the example in Figure ZA.1), with
the complete information appearing on the accompanying commercial documents (see the example in Figure ZA.2).

ZA.3.2 CE marking on the packaging

For the CE marking affixed on the packaging of the sealant the following information shall be given together
with the CE marking symbol:

a) reference to this European Standard (i.e. EN 15651-1);

b) identification number of the notified certification body (for a sealant under AoC system 1 only);

c) the last two digits of the year in which the marking was affixed;

d) The name of the Manufacturer;

e) short description of the sealant:

1) type of sealant: “F”,

2) intended uses: e.g. “for external or/and internal side of facade elements”, designation "F EXT-INT",
and, when relevant for cold climate, designation “CC”, in accordance with 4.3.2.

Figure ZA.1 gives an example CE marking to be given on the packaging of a non-structural sealant intended
to be used in joints on the external and internal side of facade elements.

CE marking symbol given in Directive 93/68/EEC

Identification number of the notified certification body*


0123
12 Last two digits of the year in which the marking was affixed
AnyCo Ltd Name or identifying mark of the manufacturer
NOTE Registered address of the manufacturer may also be added.

EN 15651-1 Number of the European Standard


F EXT- INT Type of sealant and intended use
* For a sealant under AoC system 1 only.

Figure ZA.1 – Example CE marking given on the packaging of the non-structural sealant intended to
be used in joints on the external and internal side of facade elements

23
BS EN 15651-1:2012
EN 15651-1:2012 (E)

All other information required by ZA.3.3, e.g. information on characteristics shall be given with the
accompanying documents.
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

ZA.3.3 CE marking in the accompanying commercial documents

The CE marking symbol and the following information shall be given in the accompanying commercial
documents (e.g. a delivery note):

a) reference to this European Standard (i.e. EN 15651-1);

b) identification number of the certification body (for a sealant under AoC system 1 only);

c) the last two digits of the year in which the marking was affixed;

d) name or identifying mark of the manufacturer (see NOTE 1 in ZA.2.2.1 or ZA.2.2.2);

NOTE 1 Registered address of the manufacturer may also be added.

e) number of the EC certificate of conformity (for a sealant under AoC system 1 only);

f) complete description of the sealant (information from identification requirements in 4.1.1);

g) the information on the essential characteristics listed in Table ZA.1:

1) reaction to fire: declared class according to EN 13501-1:2007+A1 based on tests (see 4.6);

2) release of chemicals dangerous to the environment and health: where relevant (see NOTES 1 and 2
in ZA.1);

3) water tightness and air tightness, based on the values of the proxy characteristics;

4) durability, expressed as "Pass".

The “No performance determined” (NPD) option shall not be used where the characteristic is subject to a
threshold level. Otherwise, the NPD option may be used when and where the characteristic, for a given
intended use, is not subject to regulatory requirements in the Member State(s) of destination.

Figure ZA.2 gives an example CE marking to be given in the commercial documents, accompanying the
packaging of a non-structural sealant intended to be used in joints only on the internal side of facade elements
(also under AoC system 1*).

24
BS EN 15651-1:2012
EN 15651-1:2012 (E)
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

CE marking symbol given in Directive 93/68/EEC

01234 Identification number of the notified certification body*

Name or identifying mark of the manufacturer


AnyCo Ltd
NOTE Registered address of the manufacturer may also be added.

12 Last two digits of the year in which the marking was affixed
01234-CPD-00234 Number of the EC certificate of conformity*

EN 15651-1 Number of the European Standard with the year of its


publication
Non-structural sealants
for joints only on the internal side of facade Complete description of the sealant and its intended uses,
elements including its type, together with conditioning method and
substrate
- Type F INT
- Conditioning: Method A * For a sealant under AoC system 1 only.
- Substrate: Aluminium with Primer XYZ

REACTION TO FIRE Class E Information on all mandated characteristics of the sealant

RELEASE OF CHEMICALS Evaluated


DANGEROUS TO THE ENVIRONMENT
AND HEALTH

WATER TIGHTNESS and AIR TIGHTNESS


- resistance to flow ≤ 5 mm
- loss of volume ≤ 45 %
- tensile properties, i.e. ≥ 25 %
elongation after immersion in
water at 23 °C
DURABILITY Pass

Figure ZA.2 – Example CE marking given in the commercial documents, accompanying the packaging
of the non-structural sealant intended to be used in joints only on the internal side of facade elements

In addition to any specific information relating to dangerous substances shown above, the sealant should also
be accompanied, when and where required and in the appropriate form, by documentation listing any other
legislation on dangerous substances for which compliance is claimed, together with any information required
by that legislation.

NOTE 2 European legislation without national derogations needs not be mentioned.

NOTE 3 Affixing the CE marking symbol means, if a sealant is subject to more than one directive that it conforms to all
applicable directive.

25
BS EN 15651-1:2012
EN 15651-1:2012 (E)

Bibliography
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

[1] EN 13823, Reaction to fire tests for building products  Building products excluding floorings exposed
to the thermal attack by a single burning item

26
Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

This page deliberately left blank


Licensed Copy: Edinburgh Napier User, Edinburgh Napier University, 18/07/2013 13:09, Uncontrolled Copy, (c) The British Standards Institution 2013

British Standards Institution (BSI)


BSI is the independent national body responsible for preparing British Standards and other
standards-related publications, information and services. It presents the UK view on standards in
Europe and at the international level.
BSI is incorporated by Royal Charter. British Standards and other standardisation products are
published by BSI Standards Limited .

Revisions Information on standards


British Standards and PASs are periodically updated by amendment or BSI provides a wide range of information on national, European
revision. Users of British Standards and PASs should make sure that they and international standards through its Knowledge Centre.
possess the latest amendments or editions. Tel: +44 (0)20 8996 7004 Fax: +44 (0)20 8996 7005
It is the constant aim of BSI to improve the quality of our products and Email: knowledgecentre@bsigroup.com
services. We would be grateful if anyone finding an inaccuracy or ambiguity
while using British Standards would inform the Secretary of the technical BSI Subscribing Members are kept up to date with standards developments
committee responsible, the identity of which can be found on the inside front and receive substantial discounts on the purchase price
cover. Similary for PASs, please notify BSI Customer Services. of standards. For details of these and other benefits contact Membership
Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001 Administration.
Tel: +44 (0)20 8996 7002 Fax: +44 (0)20 8996 7001
BSI offers BSI Subscribing Members an individual updating service called Email: membership@bsigroup.com
PLUS which ensures that subscribers automatically receive the latest editions
of British Standards and PASs. Information regarding online access to British Standards and PASs
Tel: +44 (0)20 8996 7669 Fax: +44 (0)20 8996 7001 via British Standards Online can be found at
Email: plus@bsigroup.com www.bsigroup.com/BSOL
Further information about British Standards is available on the BSI website
Buying standards at www.bsi-group.com/standards
You may buy PDF and hard copy versions of standards directly using a
credit card from the BSI Shop on the website www.bsigroup.com/shop.
In addition all orders for BSI, international and foreign standards publications
Copyright
All the data, software and documentation set out in all British Standards and
can be addressed to BSI Customer Services.
other BSI publications are the property of and copyrighted by BSI, or some
Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001 person or entity that own copyright in the information used (such as the
Email: orders@bsigroup.com international standardisation bodies) has formally licensed such information
to BSI for commerical publication and use. Except as permitted under the
In response to orders for international standards, BSI will supply the British Copyright, Designs and Patents Act 1988 no extract may be reproduced,
Standard implementation of the relevant international standard, unless stored in a retrieval system or transmitted in any form or by any means –
otherwise requested. electronic, photocopying, recording or otherwise – without prior written
permission from BSI. This does not preclude the free use, in the course of
implementing the standard, of necessary details such as symbols, and size,
type or grade designations. If these details are to be used for any other
purpose than implementation then the prior written permission of BSI must
be obtained. Details and advice can be obtained from the Copyright &
Licensing Department.
Tel: +44 (0)20 8996 7070
Email: copyright@bsigroup.com

BSI
389 Chiswick High Road London W4 4AL UK
Tel +44 (0)20 8996 9001
Fax +44 (0)20 8996 7001
www.bsigroup.com/standards

raising standards worldwide™