Submittal Data

Surge Ingenieria/Telecom/W72
Location: Quito, Ecuador

Date: September 26, 2023

Prepared By: Margarita Ponce


Project: Surge Ingenieria/Telecom/W72

Plan-ID Qty Model No Description Page


WM-01 2 W72AY-B0ZBPXXXJ Wall-Mount™ Air Conditioner 208/230-3 ph 3
WM-02 1 MC4002S-BC Telecom Controller 6

Warranty Document (7-13-2023) 10


F1521 J-Control Description 12
Supply Grille Spread and Throw Characteristics 13
SG/W Series Supply Air Grille Dimensions (2 inch flange) 14
RG/W Series Return Air Grille Dimensions (2 inch flange) 15
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-01 Page: 3
Model Number: W72AY-B0ZBPXXXJ Quantity: 2

AHRI Rated Cooling Performance Supply Air Performance


AHRI Certified Reference # 213082154 Total Supply Air 1972 cfm
AHRI Rated Cooling 71,000 Btuh Blower Motor 0.75 hp
Capacity Heat Blower Speed
EER 10.00 Non-Ducted
Rated Airflow 1900 cfm Filter Static Pressure 0.03 in wg.
Air flow is based on Wet Coil
Cooling Performance @ Project Parameters
Cooling Capacity 71,538 Btuh Electrical Data
Sensible Capacity 50,845 Btuh Power Supply 208/230 Volts
Latent Capacity 20,693 Btuh 3 Phase
Efficiency (at AHRI) 11.00 EER 60 Hertz
Outdoor DB Temp 95.0 °F Minimum Circuit Ampacity 39 Amps
Entering DB Temp 80.0 °F Maximum External Fuse or 45 Amps
Entering WB Temp 67.0 °F Circuit Breaker
Leaving DB Temp 56.1 °F
Leaving WB Temp 55.5 °F All wiring must conform to the National Electrical Code and all local
codes

NOTE: MOCP (Maximum Overcurrent Protection) value listed is the


maximum value as per UL 1995 calculations for MOCP (branch-circuit
conductor sizes shown are based on this MOCP). The actual factory
installed Overcurrent Protective Device (Circuit Breaker) in this model
may be lower than the maximum UL 1995 allowable MOCP value, but
still above the UL 1995 minimum calculated value or Minimum Circuit
Ampacity (MCA} listed.

Approximate Installed Weight


Unit Weight 555 lb
Option Weight 7 lb
Accessory Weight 13 lb
Total Weight 575 lb

Factory Options Selected


B - 208/230 Volt 3 phase
0Z - No Heat with Circuit Breaker
B - Blank-Off Plate
P - 2-Inch Pleated MERV 8
X - Beige
X - Supply Outlet - Standard
X - Standard Coils
J - High Pressure Switch, Low Pressure Switch, Compressor Control Module, Low Ambient Control and Alarm
Relay

Field Installed Accessories


RG-5 - Return air grill - Extruded aluminum with blades fixed at 30 degree angle, 1" Flange
SG-5 - Sidewall supply register with 2 sets of individually adjusted blades, 1" Flange
8403-089 - Honeywell T4 Pro Programmable Thermostat 1 heat / 1 cool, (HP 1 heat / 1 cool)
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-01 Page: 4
Model Number: W72AY-B0ZBPXXXJ Quantity: 2

Standard Product Features


Wall-Mount Air Conditioner
• Non-Fiberglass Foil Faced Insulation: Environmentally friendly high "R" value non-fiberglass insulation that is
made with recycled denim and cotton materials used with a FSK foil face that is both durable and cleanable
• Durable Cabinet Construction: Multiple cabinet construction options are available for different outdoor
conditions. Optional cabinet coatings may be ordered for extreme outdoor environments.
• Easy Filter Access: A separate filter door is provided for ease of filter access during routine unit maintenance.
• Field or Factory Installed Vents: Multiple ventilation options are available as factory installed options that can
be removed for service.
• Electric Strip Heat: Reliable, comfortable heater packages feature an automatic limit and thermal cut-off
safety control.
• Built-in Circuit Breakers: Standard on all electric heat versions of single (208/230 volt) and three phase
(208/230 volt) equipment. Toggle disconnects are standard on all electric heat versions of three phase (460
volt) equipment.
• Reliable, Easy-to-Use Controls: Easily accessible through left or right control panel locations. A lockable
hinged access cover to circuit protection is provided. Adjustable compressor on/off delay timer (CCM) with
diagnostic lights is standard on all models.
• Green Fin Hydrophilic Evaporator Coil: Green fin stock is used to help prevent mold growth, aid with
condensate drainage, and provide a limited amount of protection to corrosive particulates in the airstream.
• Balanced Climate™ Technology (patent pending): High latent capacity humidity & sound reduction removes
up to 35% more humidity than any other wall mount on the market with the use of a 2 stage thermostat or
controlling device. Bard Balanced Climate innovation comes standard on all models.
• Enclosed Condenser Motor: An enclosed casing condenser motor with ball bearings is used for reliable
operation and extended motor life. Enclosed condenser motors are standard on all units.
• High Efficiency Cooling: Scroll compressors for quiet, efficient cooling. Designed with R-410A (HFC) non-
ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements. A liquid line
filter-drier to protect the system from moisture is standard on all units.
• Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2019.
• Certified to ANSI/AHRI Standard 390-2021 for SPVU (Single Package Vertical Units)
• Intertek ETL Listed to Standard for Safety of Household and Similar Electrical Appliances ANSI/UL STD
60335-1 & ANSI/UL STD 60335- 2-40/CSA STD C22.2 No. 60335-1 & CSA STD C22.2 No. 60335-2- 40 Third
Edition
• Bard is an ISO 9001:2015 Certified Manufacturer
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-01 Page: 5
Model Number: W72AY-B0ZBPXXXJ Quantity: 2

Dimensions of Basic Unit for Architectural and Installation Requirements (Inches)

Width Depth Height Supply Return


(W) (D) (H) A B C B E F G I
42 25.52 93 9.88 29.88 15.88 29.88 43.88 12.63 45 30
J K L M N O R S T U V
59.75 35.06 61.72 58.72 8.82 43 1.438 16 10 13.88 15.43
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-02 Page: 6
Model Number: MC4002S-BC Quantity: 1

MC4002S-BC Spanish Language Controller w/Enhanced Alarm & Ethernet Board

The MC4002 has 2 stages of cooling control available for up to two connected air conditioners. It is designed
for systems with or without economizers or for systems with 2-stage or dual compressors. The 2nd stage
available for each air conditioner permits complete and proper control when economizers are installed or when
2-stage or dual compressors are utilized. With the addition of a simple 2 wire humidity controller as an input
signal, it can provide electric reheat dehumidification circuit. It can also be configured for use with heat pumps.

Factory Options Selected


S - 230/208-60-3 & 220/200-50-3
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-02 Page: 7
Model Number: MC4002S-BC Quantity: 1

Standard Product Features


Controller:
• Electronic (non-mercury) design
• Programmable
• Works with or without economizers
• Dehumidification control option
• Can be used with heat pumps
Ease of Installation
• Powered by 24V from A/C units
• Phasing of 24V from units is not required
• Durable metal enclosure adequately sized for ease of conduit and wire installation
• Alarm circuits can be NO or NC logic
MC4002-B Enhanced Version Alarm Board
• Refrigerant alarm from A/C #1, input
• Refrigerant alarm from A/C #2, input
• Power loss alarm A/C #1, Form C (SPDT) output
• Power loss alarm A/C #2, Form C (SPDT) output
• Smoke/fire alarm, Form C (SPDT) output
• Low temperature alarm, Form C (SPDT) output
• 1st stage (H1) high temperature alarm, Form C (SPDT) output
• Refrigerant system lockout A/C #1, Form C (SPDT) output
• Refrigerant system lockout A/C #2, Form C (SPDT) output
• 2nd stage (H2) high temperature alarm, Form C (SPDT) output
• 2nd stage cooling alarm, Form C (SPDT) output
• Controller system failure alarm, Form C (SPDT) output
• Emergency ventilation economizer outputs, Form A (SPNO) for both A/C #1 and A/C #2
• - Emergency ventilation option for either air conditioner with refrigerant alarm @ H1 high temp alarm set point
• - Emergency ventilation option for both air conditioners @ H2 high temp alarm set point
CB5000 COMMUNICATION BOARD
• It allows remote access via Ethernet, depending upon level of authority assigned, to all functions of the
controller system the same as it one was in the building where the controller system is physically installed.
IPV6 with SNMP traps
Certifications & Approvals
• Complies with FCC Rule 15, Subpart B, Class A
• This ISM device also complies with Canadian ICES-001
• Complies with CE Standards EN55011/EN50081 and EN55024 for ISM Equipment, Class A
Controller Enclosure
• 20-Gauge Gray Pre-Painted Metal
• 9.25" W x 13.50" H x 3" D
• Hinged Cover
• Thirteen (13) .875" Diameter Knockouts
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-02 Page: 8
Model Number: MC4002S-BC Quantity: 1
Project: Surge Ingenieria/Telecom/W72 Plan-ID: WM-02 Page: 9
Model Number: MC4002S-BC Quantity: 1
Project: Surge Ingenieria/Telecom/W72 Page: 10
Warranty Document (7-13-2023)
Project: Surge Ingenieria/Telecom/W72 Page: 11
Warranty Document (7-13-2023)
Project: Surge Ingenieria/Telecom/W72 Page: 12
F1521 J-Control Description
Project: Surge Ingenieria/Telecom/W72 Page: 13
Supply Grille Spread and Throw Characteristics
Project: Surge Ingenieria/Telecom/W72 Page: 14
SG/W Series Supply Air Grille Dimensions (2 inch flange)
Project: Surge Ingenieria/Telecom/W72 Page: 15
RG/W Series Return Air Grille Dimensions (2 inch flange)