Steps to change caliber of insertion electromagnetic flow meter:

1. Press the 1st key and the 4th key at the same time to display the parameter setting panel.

2. Press the 4th key to display 00000 and enter the password 01314
The way to enter the password by:
Press and hold the 1 and 2 keys to shift to Left, or press and hold the 1 and 3 keys to shift to Right.
Keys 2 and 3 change the number.

3.Find the content you need to set. You need change DN to DN250 firstly.
Press the 3rd key to find the sensor caliber, set the number to DN250.
And then press the 4th key to exit.

4. After change to actual pipe DN250, we need to calculate a new Sensor Fact for the DN250 meter.
Please strictly follow method as below:

Using the flow on Ultrasonic meter ÷ flow on the electromagnetic meter screen × Sensor Fact in the
electromagnetic meter = new Sensor Fact (Take note of the new sensor fact)

5. Press the 3rd key to find the Sensor Fact value, set the New Sensor fact, then press the 4th key to
exit.(see attached video how to change Sensor Fact).

5. After processing, press 4th for more than 3 seconds to exit